![Fujitsu AUXG30LRLB Скачать руководство пользователя страница 33](http://html.mh-extra.com/html/fujitsu/auxg30lrlb/auxg30lrlb_service-instruction_2343790033.webp)
Inverter cover
01-30
1-26. DESCRIPTION OF DISPLAY UNIT For Model 45,54
•
Display lamp
Function or operation method
(1) POWER / MODE
Green
Lights on while power on. Local setting in outdoor unit or
error code is displayed with blink.
(2) ERROR
Red
Blinks during abnormal air-conditioner operation.
(3) PUMP DOWN
(L1)
Orange Lights on during pump down operation.
(4) LOW NOISE MODE
(L2, L3)
Orange Lights on during “Low noise” mode when local setting is activated.
(Lighting pattern of L2 and L3 indicates low noise level)
(5) PEAK CUT
(L4, L5, L6)
Orange Lights on during “Peak cut” mode when local setting is activated.
(Lighting pattern of L4, L5 and L6 indicates peak cut level)
SW1 SW2
SW3 SW4
SW5
(1)
(2) (3)
(4)
(5)
LED DISPLAY
Various settings can be adjusted by changing Push switches on the board of the outdoor unit.
( Excerpt from the "INSTALATION MANUAL" )
Switch
Function or operation method
SW1
To switch between “Local setting” and “Error code display”.
SW2
To switch between the individual “Local settings” and the
“Error code displays”.
SW3
To fix the individual “Local settings ” and the “Error code displays”.
SW4
To return to “Operation status display”.
SW5
To start the pump down operation.
MODE
SELECT
ENTER
EXIT / INITIALIZE
PUMP DOWN
PUSH SWITCH
1-00. ERROR HISTORY MODE
1-26-1 Layout of Display Unit