- 71 -
CASSETTE TYPE
AUXG18-5
4LRL
B
6) Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor may be
required. Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both “01”.
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
7) Auto restart
Enables or disables automatic restart after a power interruption.
NOTE:
Auto restart is an emergency function such as for power outage etc. Do not attempt to use
this function in normal operation. Be sure to operate the unit by remote controller or external
device.
8) Room temperature sensor switching
(Only for wired remote controller)
When using the wired remote controller temperature sensor, change the setting to "Both" (01).
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
NOTE:
Remote controller sensor must be turned on by using the remote controller.
Function number
Setting value
Setting description
Factory
setting
35
(For cooling)
36
(For heating)
00
No correction
♦
01
No correction 0.0°C
02
-0.5 °C
More cooling
Less heating
03
-1.0 °C
04
-1.5 °C
05
-2.0 °C
06
-2.5 °C
07
-3.0 °C
08
-3.5 °C
09
-4.0 °C
10
+0.5 °C
Less cooling
More heating
11
+1.0 °C
12
+1.5 °C
13
+2.0 °C
14
+2.5 °C
15
+3.0 °C
16
+3.5 °C
17
+4.0 °C
Function number
Setting value
Setting description
Factory setting
40
00
Enable
♦
01
Disable
Function number
Setting value
Setting description
Factory setting
42
00
Indoor unit
♦
01
Both
Содержание AUXG18LRLB
Страница 7: ...Part 1 INDOOR UNIT CASSETTE TYPE AUXG18LRLB AUXG24LRLB AUXG30LRLB AUXG36LRLB AUXG45LRLB AUXG54LRLB ...
Страница 58: ... 52 CASSETTE TYPE AUXG18 54LRLB 8 2 Sound level check point Microphone Microphone Center 1 5 m Center ...
Страница 86: ... 80 CASSETTE TYPE AUXG18 54LRLB ...
Страница 87: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG18LBCA AOYG24LBCA AOYG30LBTA AOYG36LBTA AOYG45LBTA AOYG54LBTA ...
Страница 104: ... 98 CASSETTE TYPE AUXG18 54LRLB 3 2 Models AOYG30LBTA and AOYG36LBTA ...
Страница 105: ... 99 CASSETTE TYPE AUXG18 54LRLB 3 3 Models AOYG45LBTA and AOYG54LBTA ...
Страница 106: ... 100 CASSETTE TYPE AUXG18 54LRLB 4 Wiring diagrams 4 1 Models AOYG18LBCA and AOYG24LBCA ...
Страница 107: ... 101 CASSETTE TYPE AUXG18 54LRLB 4 2 Model AOYG30LBTA ...
Страница 108: ... 102 CASSETTE TYPE AUXG18 54LRLB 4 3 Model AOYG36LBTA ...
Страница 109: ... 103 CASSETTE TYPE AUXG18 54LRLB 4 4 Models AOYG45LBTA and AOYG54LBTA ...