- 121 -
CASSETTE
TYPE
AUXG18-54L
RLB
Peak cut mode
By performing following on-site work, operation that suppresses the current value can be enabled:
• The air conditioner is set to the “Peak cut mode” when closing the contact input of a commercial
timer or on/off switch to a connector on the control PCB of the outdoor unit.
Circuit diagram example
Optional part
• Contact capacity: DC 24 V or more, 10 mA or more.
• *: Make the distance from the PCB to the connected
unit within 10 m.
• Construct a circuit as shown in this figure with using
optional parts mentioned below.
• Input signal: On in “Peak cut mode”
• Input signal: Off in normal operation
• To set the level of “Peak cut mode”, refer to
“Peak
cut mode”
on page 127.
Part name
Model name
Exterior
External connect kit
UTY-XWZXZ3
Outdoor unit
control PCB
Connected unit
Example: Switch
Connector
1
2
Signal
Locally purchased
*10 m
On
Off
On
Off
Input signal
Peak cut mode
Содержание AUXG18LRLB
Страница 7: ...Part 1 INDOOR UNIT CASSETTE TYPE AUXG18LRLB AUXG24LRLB AUXG30LRLB AUXG36LRLB AUXG45LRLB AUXG54LRLB ...
Страница 58: ... 52 CASSETTE TYPE AUXG18 54LRLB 8 2 Sound level check point Microphone Microphone Center 1 5 m Center ...
Страница 86: ... 80 CASSETTE TYPE AUXG18 54LRLB ...
Страница 87: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG18LBCA AOYG24LBCA AOYG30LBTA AOYG36LBTA AOYG45LBTA AOYG54LBTA ...
Страница 104: ... 98 CASSETTE TYPE AUXG18 54LRLB 3 2 Models AOYG30LBTA and AOYG36LBTA ...
Страница 105: ... 99 CASSETTE TYPE AUXG18 54LRLB 3 3 Models AOYG45LBTA and AOYG54LBTA ...
Страница 106: ... 100 CASSETTE TYPE AUXG18 54LRLB 4 Wiring diagrams 4 1 Models AOYG18LBCA and AOYG24LBCA ...
Страница 107: ... 101 CASSETTE TYPE AUXG18 54LRLB 4 2 Model AOYG30LBTA ...
Страница 108: ... 102 CASSETTE TYPE AUXG18 54LRLB 4 3 Model AOYG36LBTA ...
Страница 109: ... 103 CASSETTE TYPE AUXG18 54LRLB 4 4 Models AOYG45LBTA and AOYG54LBTA ...