- 117 -
CASSETTE
TYPE
AUXG18-54L
RLB
9. Electrical characteristics
*1: The maximum current is the total current of indoor unit and outdoor unit.
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate
devices complied to the regional standard.
*3: Limit voltage drop to less than 2%. Increase conductor size if voltage drop is 2% or more.
Model name
AOYG18LBCA
AOYG24LBCA
Power supply
Voltage
V
230
Frequency
Hz
50
Max. operating current*1
A
13.5
18.5
Wiring spec. *2
Circuit breaker current
A
25
30
Power cable
mm
2
4.0
Connection cable *3
mm
2
1.5—2.5
Limited wiring length
m
31
Model name
AOYG30LBTA AOYG36LBTA AOYG45LBTA AOYG54LBTA
Power
supply
Voltage
V
230
Frequency
Hz
50
Max. operating current*1
A
17.0
20.0
20.5
21.5
Wiring
spec. *2
Circuit breaker
current
A
30
Power cable
mm
2
4.0
6.0
Connection cable *3 mm
2
1.5—2.5
Limited wiring
length
m
51
Содержание AUXG18LRLB
Страница 7: ...Part 1 INDOOR UNIT CASSETTE TYPE AUXG18LRLB AUXG24LRLB AUXG30LRLB AUXG36LRLB AUXG45LRLB AUXG54LRLB ...
Страница 58: ... 52 CASSETTE TYPE AUXG18 54LRLB 8 2 Sound level check point Microphone Microphone Center 1 5 m Center ...
Страница 86: ... 80 CASSETTE TYPE AUXG18 54LRLB ...
Страница 87: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG18LBCA AOYG24LBCA AOYG30LBTA AOYG36LBTA AOYG45LBTA AOYG54LBTA ...
Страница 104: ... 98 CASSETTE TYPE AUXG18 54LRLB 3 2 Models AOYG30LBTA and AOYG36LBTA ...
Страница 105: ... 99 CASSETTE TYPE AUXG18 54LRLB 3 3 Models AOYG45LBTA and AOYG54LBTA ...
Страница 106: ... 100 CASSETTE TYPE AUXG18 54LRLB 4 Wiring diagrams 4 1 Models AOYG18LBCA and AOYG24LBCA ...
Страница 107: ... 101 CASSETTE TYPE AUXG18 54LRLB 4 2 Model AOYG30LBTA ...
Страница 108: ... 102 CASSETTE TYPE AUXG18 54LRLB 4 3 Model AOYG36LBTA ...
Страница 109: ... 103 CASSETTE TYPE AUXG18 54LRLB 4 4 Models AOYG45LBTA and AOYG54LBTA ...