4-15-4. WIRED REMOTE CONTROLLER
DIP SWITCH SETTING
1-1 Dual remote controller setting
Set the remote controller DIP switch No.1 and 2 according to the following table.
1. SW setting
(
Factory setting)
Number of
remote
controller
DIP-SW
No.1
DIP-SW
No.2
DIP-SW
No.1
DIP-SW
No.2
Master unit
Slave unit
ON
ON
ON
OFF
OFF
OFF
1 (Normal)
2 (Dual)
1-2 Group control setting
Number of indoor unit connection (One/Multiple)
This is switched according to the number of connected indoor units.
(
Factory setting)
Number of indoor unit
One unit connection
DIP-SW
No.3
ON
Multiple unit connection
OFF
1-3 Model setting
The system type of the outdoor unit can be selected by setting up DIP switch No.4 as follows.
(
Factory setting)
Model
Heat Pump model
DIP-SW
No.4
ON
Cooling only model
OFF
1-4 Auto changeover setting
Selecting auto changeover validity / invalidity.
(
Factory setting)
Auto changeover
Invalidity
DIP-SW
No.5
ON
Validity
OFF
1-5 Memory backup setting
Set to ON to use batteries for the memory backup. If batteries are not used,
all of the settings stored in memory will be deleted if there is a power failure.
(
Factory setting)
This function is wired remotecontroll only.
Memory backup
Invalidity
DIP-SW
No.6
ON
Validity
OFF
Содержание AUU42R
Страница 1: ...R410A 4 CASSETTE TYPE AUU42RCLX D2D_AU021E 02 2006 04 21 ...
Страница 10: ...CASSETTE TYPE AUU42R CASSETTE TYPE AUU42R 04 09 4 5 REFRIGERANT CIRCUIT MODELS AUU42R AOU42R ...
Страница 12: ...CASSETTE TYPE AUU42R CASSETTE TYPE AUU42R 04 11 4 6 2 INDOOR UNIT MODEL AUU42R G N ...
Страница 22: ...CASSETTE TYPE AUU42R CASSETTE TYPE AUU42R 04 21 SOUND LEVEL CHECK POINT 3ft 3 3 8in 1m ...