En-14
Example
If 4 indoor units are connected.
Remote
controller
Indoor unit
Indoor unit
Indoor unit
Indoor unit
RC AD SW
0
RC AD SW
1
RC AD SW
2
RC AD SW
3
RC AD SW
0
1
2
3
4
5
6
7
Address
0
1
2
3
4
5
6
7
RC AD SW
8
9
A
B
C
D
E
F
Address
8
9
10
11
12
13
14
15
]1
7.2. Custom code setting
Selecting the custom code prevents the indoor unit mix-up.
(Fig. B)
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote
controller.
Fig. B
Code change
Indoor unit
Remote
controller
Confusion
A B C D
A B C D
• Custom code setting for indoor unit
Set the DIP SW SET 3 SW1, 2, referring to the Table B.
Dip switch
“SET 3”
ON
OFF
SW SW SW SW
1 2 3 4
Table B
Custom code
A (Factory setting)
B
C
D
DIP SW
SET 3
SW1
OFF
ON
OFF
ON
DIP SW
SET 3
SW2
OFF
OFF
ON
ON
]1
7.3. Function setting
• FUNCTION SETTING can be performed with the wired or
wireless remote control.
(The remote control is optional equipment)
• Refer to the wired or wireless remote control manual for
detailed setting information. (Set IU AD, REF AD SW to 0)
• Refer to “7.1. Setting the address” for indoor unit address
and refrigerant circuit address settings.
• Turn the power of the indoor unit ON before starting the
setting.
* Turning on the power indoor units initializes EEV, so make
sure the piping air tight test and vacuuming have been
conducted before turning on the power.
* Also check again to make sure no wiring mistakes were
made before turning on the power.
Function details
Function Function
number
Setting
number
Default
Details
Filter
indicator
interval
11
00
Default
○
Adjust the filter cleaning interval
notification. If the notification is
too early, change to setting 01. If
the notification is too late, change
to setting 02.
01
Longer
02
Shorter
Filter
indicator
action
13
00
Enable
○
Enable or disable the filter
indicator. Setting 02 is for use
with a central remote control.
01
Disable
02
Display
only on
central
remote
control
Horizon-
tal swing
airflow
direction
24
00
Default
○
Adjust the horizontal swing airflow
direction.
(For horizontal swing equipped
models)
01
Left half
02 Right half
Cool air
tem-
perature
trigger
30
00
Default
○
Adjust the cool air trigger
temperature. To lower the trigger
temperature, use setting 01. To
raise the trigger temperature, use
setting 02.
01 Adjust (1)
02 Adjust (2)
Hot air
tem-
perature
trigger
31
00
Default
○
Adjust the hot air trigger
temperature. To lower the trigger
temperature by 6 degrees C, use
setting 01. To lower the trigger
temperature by 4 degrees C, use
setting 02. To raise the trigger
temperature, use setting 03.
01 Adjust (1)
02 Adjust (2)
03 Adjust (3)
Auto
restart
40
00
Enable
Enable or disable automatic
system restart after a power
outage.
01
Disable
○
External
control
46
00 Start/Stop
○
Allow an external controller to
start or stop the system, or to
perform an emergency shutdown.
* If an emergency shutdown is
performed from an external
controller, all refrigerant systems
will be disabled.
01 Emergency
stop
Error
report
target
47
00
All
○
Change the target for reporting
errors. Errors can either be
reported in all locations, or only
on the wired remote.
01
Display
only on
central
remote
control
9371057033-02_IM_en.indd 14
2/20/2009 3:13:40 PM