En-3

 CAUTION

Install heat insulation around both the gas and liquid pipes. Failure to do so may 

cause water leaks.

Use heat insulation with heat resistance above 248 °F (120 °C). Reverse cycle model 

only.

In addition, if the humidity level at the installation location of the refrigerant piping is 

expected to exceed 70%, install heat insulation around the refrigerant piping. If the 

expected humidity level is 70-80%, use heat insulation that is 3/4 in (15 mm) or thicker 

and if the expected humidity exceeds 80%, use heat insulation that is 13/16 in (20 

mm) or thicker.

If heat insulation is used that is not as thick as specified, condensation may form on 

the surface of the insulation. In addition, use heat insulation with heat conductivity of 

0.045 W/(m•K) or less (at [68 °F (20 °C)]).

2.6. Electrical requirement

The indoor unit is powered from the outdoor unit or branch box. Do not power indoor unit 
from separate power source.

 WARNING

Standard for electrical wiring and equipment differs in each country or region. Before you 

start electrical working, confirm related regulations, codes, or standards.

 

Cable specification

Cable

Cable size

Remarks

Connection cable

14AWG

3 cable+Ground (earth),  

1φ 208/230 V

Max. Cable Length: Limit voltage drop to less than 2%. Increase cable gauge if voltage 

drop is 2% or more.

2.7. Optional parts

Refer to each installation manual for the method of installing optional parts.

Parts name

Model No.

Application

Wired remote controller (*1) (*2)

UTY-RNR

Z

For air conditioner operation  

(2-wired type)

Simple remote controller (*1)

UTY-RSR

UTY-RHR

External input and output PCB

UTY-XCSXZ2

For control input/output port

External connect kit

UTY-XWZXZ5

UTY-XWZX

Communication kit

UTY-TWRXZ2 For the installation of 2-wired 

remote controller

WLAN adapter

UTY-TFSXF

For wireless LAN control

•  Optional parts are subject to change without notice.

*1: Optional Communication kit (UTY-TWRXZ2) is necessary for installation.

*2:  The wired remote controller (UTY-RNR

Z

) and the wireless controller cannot be 

used simultaneously.

3.  INSTALLATION WORK

3.1. Selecting an installation location

Decide the mounting position with the customer as follows:
(1)  Install the indoor unit level on a strong wall which is not subject to vibration.

(2)  The inlet and outlet ports should not be obstructed: the air should be able to blow all 

over the room.

(3)  Install the unit a dedicated electrical branch circuit.

(4)  Do not install the unit where it will be exposed to direct sunlight.

(5)  Install the unit where connection to the outdoor unit or branch box is easy.

(6)  Install the unit where the drain pipe can be easily installed.

(7)  Take servicing, etc. into consideration and leave the spaces shown in “3.1.1. 

Installation dimensions”. Also install the unit where the filter can be removed.

Correct initial installation location is important because it is difficult to move unit after it is 

installed.

 WARNING

 Install the air conditioner in a location which can withstand a load of at least 3 times the 

weight of the main unit and which will not amplify sound or vibration. If the installation 

location is not strong enough, the indoor unit may fall and cause injuries.

Withstandable weight (Unit weight × 3*)

116 lbs (52.5 kg)

*In accordance with UL standards.

 CAUTION

• Do not install the unit in the following areas:

- Area with high salt content, such as at the seaside. It will deteriorate metal parts, 

causing the parts to fail or the unit to leak water.

 Area filled with mineral oil or containing a large amount of splashed oil or steam, such 

as a kitchen. 

It will deteriorate plastic parts, causing the parts to fail or the unit to leak water.

-  Area that generates substances that adversely affect the equipment, such as sulfuric 

gas, chlorine gas, acid, or alkali. 

It will cause the copper pipes and brazed joints to corrode, which can cause 

refrigerant leakage.

 Area that can cause combustible gas to leak, contains suspended carbon fibers or 

flammable dust, or volatile inflammables such as paint thinner or gasoline.

 

If gas leaks and settles around the unit, it can cause a fire.

-  Area where animals may urinate on the unit or ammonia may be generated.

•  Do not use the unit for special purposes, such as storing food, raising animals, 

growing plants, or preserving precision devices or art objects.

It can degrade the quality of the preserved or stored objects.

•  Do not install where there is the warning of combustible gas leakage.

• 

 Do not install the unit near a source of heat, steam, or flammable gas.

•  Install the unit where drainage does not cause any trouble.

• Install the indoor unit, outdoor unit, branch box, power supply cable, connection 

cable, and remote controller cable at least 40 in (1 m) away from a television or radio 

receivers. The purpose of this is to prevent TV reception interference or radio noise. 

(Even if they are installed more than 40 in (1 m) apart, you could still receive noise 

under some signal conditions.)

•  If children under 10 years old may approach the unit, take preventive measures so 

that they cannot reach the unit.

• 

 Install the indoor unit on the wall where the height from the floors more than 70 in 

 

(1.8 m).

 

3.1.1. Installation dimensions

Keep the distance between the wall hook bracket or indoor unit to the surrounding walls 

as indicated in the following figure. 

Wall hook bracket

Outline of the indoor unit

[ 2-1/2 (63)   or more ]

3-7/16 (88) 

 

or more

[ 1-15/16 

(50) or 

more ]

[ 1-15/16 (50)  

or more ]

2-3/4 (70)  

or more

60 (1500)  

or more

71 (1800) or more

Unit: in (mm)

5-1/2 (140)  

or more

3.2. Removing and replacing parts

3.2.1. Intake grille removal and installation

 

Intake grille removal

(1)  Open the intake grille.

(2)  While pressing the left and right mounting shafts outward gently, pull the intake grille.

Mounting shaft

Mounting shaft

9387082593-01_IM.indb   3

9387082593-01_IM.indb   3

28-Oct-21   13:52:45

28-Oct-21   13:52:45

Содержание ASUH36LPAS

Страница 1: ...nnect all wiring tightly Loose wiring may cause overheating at connection points and a possible fire hazard When Transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make su...

Страница 2: ... malfunction of your property 2 PRODUCT SPECIFICATION 2 1 Precautions for using R410A refrigerant The basic installation work procedures are the same as conventional refrigerant R22 models However pay careful attention to the following points Since the working pressure is 1 6 times higher than that of conventional refrigerant R22 models some of the piping and installation and service tools are spe...

Страница 3: ...be removed Correct initial installation location is important because it is difficult to move unit after it is installed WARNING Install the air conditioner in a location which can withstand a load of at least 3 times the weight of the main unit and which will not amplify sound or vibration If the installation location is not strong enough the indoor unit may fall and cause injuries Withstandable ...

Страница 4: ...Top hooks 3 places Top holes 3 places Indoor unit Middle hooks 5 places Middle hooks 5 places 3 Attach the 10 screws 4 Attach the wire cover 2 screws 5 Attach the 4 caps 6 Attach the intake grille CAUTION Take caution when removing or installing the front panel If the front panel falls there is a risk of injury 3 3 Pipe installation 3 3 1 Indoor unit piping direction The piping can be connected in...

Страница 5: ... the drain hose so that it is at the bottom of the piping Install the piping so that the drain hose is at the bottom Connection cable GOOD PROHIBITED Vinyl tape Connection pipe Drain hose Connection pipe Saddle Drain hose Lifted up For Left rear piping Drain hose Left piping Drain hose Left bottom piping Drain hose Interchange the drain cap and the drain hose Installing the drain cap Use a hexagon...

Страница 6: ... pipe with a sharp cutter as shown on the right and bend it after exposing the pipe After bending the pipe as you want be sure to put the heat insu lating pipe back on the pipe and secure it with tape Pipe Insulating pipe Cutter Cut line Flare connection CAUTION Be sure to install the pipe against the port on the indoor unit correctly If the center ing is improper the flare nut cannot be tightened...

Страница 7: ...ightened 5 Do not tighten the terminal screws too much otherwise the screws may break Screw with special washer Wire Ring terminal Terminal blocks Wire Screw with special washer Ring terminal 6 Refer to the following table for the terminal screw tightening torques Tightening torque lbf in N m M3 5 screw 7 0 to 8 8 0 8 to 1 0 M4 screw 10 6 to 15 9 1 2 to 1 8 M5 screw 17 7 to 26 5 2 0 to 3 0 To conn...

Страница 8: ...oller turn off 2 Press down MODE for more than 5 seconds The current custom code will be displayed initially set to 3 Press TEMP SELECT to change the custom code between A B C D Match the custom code on the display to the air conditioner custom code 4 Press MODE again The custom code will be set The display will return to the original display To change the air conditioner custom code contact an au...

Страница 9: ...ble Use crimp type insulated butt connector to join field cable and wire kit wire Connect the wire with connecting wire with solder IMPORTANT Be sure to insulate the connection between the wires Locally purchased External connect kit option Solder and insulate the connected parts 4 1 3 Installing the External input output PCB 1 Remove the Intake grille front panel and control cover Refer to 3 2 Re...

Страница 10: ... code The custom code that is set through this process are applicable only to the custom in the function setting 1 Press TEMP SELECT to change the custom code between A B C D Match the code on the display to the air conditioner custom code initially set to If the custom code does not need to be selected press MODE and proceed to STEP 2 2 Press MODE to accept the custom code and proceed to STEP 2 T...

Страница 11: ...tory setting Function number Setting value Setting description 61 00 Auxiliary heater control 1 01 Auxiliary heater control 2 02 Heat pump prohibition control 03 Heater selection control using outdoor temperature 1 04 Heater selection control using outdoor temperature 2 05 Auxiliary heater control by outdoor temperature 3 06 Auxiliary heat pump control 07 Auxiliary heat pump control by outdoor tem...

Страница 12: ... 1 Is operation of each button on the remote control unit normal 2 Does each lamp light normally 3 Do air flow direction louvers operate normally 4 Is the drain normal 5 Do not have an abnormal noise and vibration during operation 6 Is there an error left in the error memory After installation check that the display is 00 normal For checking whether the display shows 00 refer to Service check in t...

Страница 13: ...ting error 2 7 27 Primary unit secondary unit setup error simultaneous multi split type 2 9 29 Connection unit number error in wired remote controller system 3 1 31 Power supply interruption error 3 2 32 Indoor unit PCB model information error Error display Error code Description LED1 green LED2 orange LED3 green 3 3 33 Indoor unit motor electricity consumption detection error 3 5 35 Manual auto s...

Страница 14: ...or Information Page 1 5 Address Error Code Back Next Page How to check the error memory When an error occurs the operation lamp Green and the timer lamp Orange indicate the error content by blinking To check the error memory follow the procedures below 1 Stop the operation of the air conditioner and then disconnect the power supply 2 Reconnect the power supply 3 In one of the following two methods...

Отзывы: