20. VARIOUS PROTECTIONS
(1). DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas
temperature.
ASYA24LCC
104 C
101 C
110 C
ASYA30LCC
ASYA24LCC
OT (Control / Release)
10.5A / 10.0A
17 C
13.0A / 12.5A
12 C
15.0A / 14.5A
17.0A / 16.5A
ASYA24LCC
ASYA30LCC
ASYA30LCC
7.0A / 6.5A
46 C
9.5A / 9.0A
40 C 11.5A / 11.0A
9.0A / 8.5A
10.0A /9.5A
13.0A / 12.5A
11.0A /10.5A
13.0A /12.5A
15.0A /14.5A
When the discharge temperature becomes higher than Temperature ,the compressor frequency
is decreased 20 Hz, and it continues to decrease the frequency for 20 Hz every 120 seconds until
the temperature becomes lower than Temperature .
When the discharge temperature becomes lower than Temperature ,the control of the control of the
compressor frequency is released.
When the discharge temperature becomes higher than Temperature ,the compressor is stopped
and the indoor unit LED starts blinking.
(Table 17 : Discharge Temperature Over Rise Prevension Control / Release Temperature)
Temperature
Temperature Temperature
(2). CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceeds
the current limit velue that was set up with the outdoor temperature.
The compressor frequency returns to the designated frequency of the indoor unit at the time
when the frequency becomes lower than the release value.
(Table 18 : Current Release Operation Value / Release Value)
[ Heating ]
[ Cooling / Dry ]
OT : Outdoor Temperature
OT (Control / Release) OT (Control / Release)
OT (Control / Release)
5 C
50 C
46 C
17 C
12 C
05-18
16.0A / 15.5A
18.0A /17.5A
40 C
5 C
(3). ANTIFREEZING CONTROL (Cooling and Dry mode)
The compressor frequency is decrease on cooling & dry mode when the indoor heat exchanger
temperature sensor detects the temperature lower than Temperature .
Then, the anti-freezing control is released when it becomes higher than Temperature .
ASYA24LCC
ASYA30LCC
(Table 19 : Anti-freezing Protection Operation / Release Temperature)
Temperature
Temperature
4 C
7 C
Temperature
Outdoor
Over than 12 C
13 C
104 C
101 C
110 C
Over than 12 C
Less than 12 C
Less than 12 C
4 C
4 C
4 C
7 C
13 C
Содержание AOYR24LCC
Страница 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 9: ...D I M E N S I O N S Model ASYA30LCC 02 02 Unit mm inch 998 39 1 4 228 9 320 12 5 8 ...
Страница 11: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 14: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 17: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 38: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Страница 69: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Страница 70: ......
Страница 71: ......
Страница 72: ......
Страница 73: ......
Страница 74: ......
Страница 75: ...REPLACEMENT PARTS 09 06 Model AOYR24LCC ...
Страница 76: ......
Страница 77: ......
Страница 78: ......
Страница 79: ......
Страница 80: ......
Страница 108: ...REPLACEMENT PARTS 09 39 Model AOYR30LCT PROCESS Wiring ...
Страница 109: ...REPLACEMENT PARTS 09 40 Model AOYR30LCT PROCESS Wiring ...
Страница 110: ...REPLACEMENT PARTS 09 41 Model AOYR30LCT PROCESS Wiring ...
Страница 111: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Страница 116: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS20032006 FEB 2006 Printed in Japan ...