21. FORCED COOLING OPERATION
05-20
The forced cooling operation starts up when MANUAL / AUTO button is pressed more than
10 seconds.
During the forced cooling operation, it keeps operation regardless of detection value of room
temperature sensor.
Operation LED and Timer LED light up while the unit is on the forced cooling operation.
The forced cooling operation is released after 60 minutes from starting time.
22. COMPRESSOR STOP CONTROL
When the detection value of outdoor temperature sensor is lower than Temp in the table below,
the compressor is stopped.
(Table 23 : Operation temperature of compressor stop control)
Temp
ASYA24LCC
ASYA30LCC
Cooling
Heating
-15 C
-15 C
Содержание AOYR24LCC
Страница 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 9: ...D I M E N S I O N S Model ASYA30LCC 02 02 Unit mm inch 998 39 1 4 228 9 320 12 5 8 ...
Страница 11: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 14: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 17: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 38: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Страница 69: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Страница 70: ......
Страница 71: ......
Страница 72: ......
Страница 73: ......
Страница 74: ......
Страница 75: ...REPLACEMENT PARTS 09 06 Model AOYR24LCC ...
Страница 76: ......
Страница 77: ......
Страница 78: ......
Страница 79: ......
Страница 80: ......
Страница 108: ...REPLACEMENT PARTS 09 39 Model AOYR30LCT PROCESS Wiring ...
Страница 109: ...REPLACEMENT PARTS 09 40 Model AOYR30LCT PROCESS Wiring ...
Страница 110: ...REPLACEMENT PARTS 09 41 Model AOYR30LCT PROCESS Wiring ...
Страница 111: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Страница 116: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS20032006 FEB 2006 Printed in Japan ...