background image

En-4

(3) Obstacles at front and rear only

500

1500 or more

When an obstruction is present also in the upward area 

(Unit : mm)

Obstacles at rear and above only

1500

500

Max. 300

1500

3.3.3. Outdoor units installation in multi row 

(Unit : mm)

(1) Single parallel unit arrangement

150

600

1000

2000 or more

(2) Multiple parallel unit arrangement

500

600

1500

3000 or more

3.4. Transporting the unit

 

WARNING

Do not touch the 

fi

 ns.

Otherwise, personal injury could result.

 

CAUTION

When carrying the unit, hold the handles on the right and left sides and be careful.
If the outdoor unit is carried from the bottom, hands or 

fi

 ngers may be pinched.

Carry slowly in the manner as shown on “Fig. B” holding the handles “Fig. A” in right 

• 

and left sides. (Be careful not to touch with hands or objects.)

Be sure to hold the handles on the sides of the unit. Otherwise, the suction grilles on 

• 

the sides of the unit may be deformed.

Fig. A

Handle

Suction grille

Handle

Suction grille

Fig. B

Front view

Rear view

3.5. Installation

(Unit : mm)

4 - 

Φ

 12 Hole

132

AIR

650

119

50

50

16

370

 

Install 4 anchor bolts at the locations indicated with arrows in the above 

fi

 gure.

• 

To reduce vibration, do not install the unit directly on the ground. Install it on a secure 

• 

base (such as concrete blocks).

The foundation shall support the legs of the unit and have a width of 50 mm or more.

• 

Depending on the installation conditions, the outdoor unit may spread its vibration 

• 

during operation, which may cause noise and vibration. Therefore, attach damping 
materials (such as damping pads) to the outdoor unit during installation.

Install the foundation, making sure that there is enough space for installing the 

• 

connection pipes.

Secure the unit to a solid block using foundation bolts. (Use 4 sets of commercially 

• 

available M10 bolts, nuts, and washers.)

The bolts should protrude 20 mm. 

• 

(Refer to the 

fi

 gure below.)

If overturning prevention is required, purchase the necessary commercially available 

• 

items.

Bolt

20 mm

Nut

Base

Fix securely with bolts on a solid block. (Use 4 sets of commercially available M10 bolt, 
nut and washer.)

4. PIPE SELECTION

4.1. Selecting the pipe material

 

CAUTION

Do not use existing pipes.

Use pipes that have clean external and internal sides without any contamination which 
may cause trouble during use, such as sulfur, oxide, dust, cutting waste, oil, or water.

It is necessary to use seamless copper pipes.
Material: Phosphor deoxidized seamless copper pipes.
It is desirable that the amount of residual oil is less than 40 mg/10 m.

Do not use copper pipes that have a collapsed, deformed, or discolored portion 
(especially on the interior surface). Otherwise, the expansion valve or capillary tube may 
become blocked with contaminants.

Improper pipe selection will degrade performance. As an air conditioner using R410A 
incurs pressure higher than when using conventional refrigerant, it is necessary to 
choose adequate materials.

Note:

Thicknesses of copper pipes used with R410A are as shown in the table.
Never use copper pipes thinner than those indicated in the table even if they are available 
on the market.

9379069403_IM.indb   4

9379069403_IM.indb   4

1/29/2013   4:44:19 PM

1/29/2013   4:44:19 PM

Содержание AOYG60LATT

Страница 1: ...vicio autorizado MANUALE DI INSTALLAZIONE UNITÀ ESTERNA A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΞΩΤΕΡΙΚΗ ΜΟΝΑΔΑ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO UNIDADE EXTERIOR Apenas para pessoal de assistência autorizado РУКОВОДСТВО ПО УСТАНОВКЕ ВНЕШНИЙ МОДУЛЬ Только для авторизованного обслуживающего персонала MONTAJ KILAVUZU DIŞ ÜNİTE Yalnızca...

Страница 2: ...ncluding children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with the appliance Do not touch the aluminum fins of heat exchanger built in the indoor or outdoor unit...

Страница 3: ...nce other than the prescribed refrigerant into the refrigeration cycle If air enters the refrigeration cycle the pressure in the refrigeration cycle will become abnormally high and cause the piping to rupture If there is a refrigerant leak make sure that it does not exceed the concentration limit If a refrigerant leak exceeds the concentration limit it can lead to accidents such as oxygen starvati...

Страница 4: ...tion space shown in the following examples is based on an ambient temperature under cooling operation of 35 C DB at the air intake of the outdoor unit Provide more space around the air intake than shown in the examples if the ambient temperature exceeds 35 C DB or if the thermal load of all of the outdoor units exceeds the capacity Consider the transportation route installation space maintenance s...

Страница 5: ...n which may cause noise and vibration Therefore attach damping materials such as damping pads to the outdoor unit during installation Install the foundation making sure that there is enough space for installing the connection pipes Secure the unit to a solid block using foundation bolts Use 4 sets of commercially available M10 bolts nuts and washers The bolts should protrude 20 mm Refer to the fig...

Страница 6: ...ont lateral side rear side and bottom Fig A When connecting at the bottom remove the service panel and piping cover on the front of the outdoor unit and open the knock out hole provided at the bottom corner of the piping outlet It can be installed as shown on Fig B cutting out the 2 slits as indicated on Fig C When cutting slits use a steel saw Fig A Service panel Front connection Bottom connectio...

Страница 7: ...tighten the flare nut correctly Outer panel may be distorted if fastened only with a wrench Be sure to fix the elementary part with a spanner and fasten with a wrench refer to below diagram Do not apply force to the blank cap of the valve or hang a wrench etc on the cap It may cause leakage of refrigerant Blank cap Flare nut Torque wrench Holding wrench Torque wrench 90 Flare nut mm in Tightening ...

Страница 8: ...harge from the liquid phase side whose composition is stable Adding refrigerant through the gas pipe will cause a malfunction Check if the steel cylinder has a siphon installed or not before filling There is an indication with siphon for filling liquid on the steel cylinder Filling method for cylinder with siphon R410A Gas Liquid Set the cylinder vertical and fill with the liquid Liquid can be fil...

Страница 9: ...mission cable come in contact with valves Gas Never install a power factor improvement condenser Instead of improving the power factor the condenser may overheat Be sure to perform the earthing grounding work Do not connect earthing grounding wires to a gas pipe water pipe lightning rod or earthing grounding wire for a telephone Connection to a gas pipe may cause a fire or explosion if gas leaks C...

Страница 10: ... the insulation sheet after the wiring is complete s d 7 PIPE INSTALLATION 2 WARNING Install the insulated pipes so that they do not touch the compressor 7 1 Installing insulation Use an insulation on the refrigerant pipes to prevent condensation and dripping Fig A Determine the thickness of the insulation material by referring to Table A Table A Selection of insulation for using an insulation mat...

Страница 11: ...ting is activated Lighting pattern of L5 L6 and L7 indicates peak cut level B Refer to 9 LOCAL SETTING Switch Function or operation method SW1 DIP switch For selecting cooling or heating during test operation Positions 2 to 4 of DIP switch are not used SW2 Push switch To switch between Local setting and Error code display SW3 Push switch To switch between the individual Local settings and the Erro...

Страница 12: ... LOW NOISE Blink PEAK CUT MODE 4 Press ENTER switch SW4 TEST RUN L1 L2 L3 L4 PUMP DOWN LOW NOISE PEAK CUT MODE Sign Lights on 5 Press SELECT switch SW3 and adjust LED display as shown in below figure PEAK CUT L5 L6 L7 Blink Blink Blink Blink Blink 0 of rated input ratio 50 of rated input ratio 75 of rated input ratio 100 of rated input ratio 9 1 1 Setting for low noise SW2 SW3 SW4 SW5 LED display ...

Страница 13: ...ay Normal operation by pressing EXIT switch SW5 When pressed number is lost during operation restart from the beginning of operation procedure after returning to Operation status display normal operation by pressing the EXIT switch once s d 10 TEST RUN CAUTION Always turn on the power 6 hours prior to the start of the operation in order to protect the compressor 10 1 Check items before performing ...

Страница 14: ...sed refrigerant may flow into the piping after the compressor stops Step 5 Closing direction Step 4 Hexagon wrench Liquid pipe Gas pipe Closing direction 6 LED display changes after 1 minute as shown in the figure below ERROR TEST RUN PUMP DOWN LOW NOISE PEAK CUT POWER MODE L1 L2 L3 L4 L5 L6 L7 Fans and compressor stop automatically If the pump down is successfully completed the above LED display ...

Страница 15: ... 2 Compressor temp sensor error 2 7 3 Heat Ex middle temp sensor error 2 7 3 Outdoor unit Heat Ex liquid temp sensor error 2 7 4 Outdoor temp sensor error 2 7 7 Heat sink temp sensor error 2 7 7 PFC heat sink temp sensor error 2 8 4 Current sensor 1 error stoppage permanently 2 8 6 High pressure switch 1 error 2 8 6 Pressure sensor error 2 9 4 Trip detection stoppage permanently 2 9 5 Compressor m...

Отзывы: