background image

En-10

8. HOW TO OPERATE DISPLAY UNIT

8.1. Various setting methods

 WARNING

Never touch electrical components such as the terminal blocks or reactor except the 
switch on the display board. It may cause a serious accident such as electric shock.

 CAUTION

Once refrigerant charging is completed, be sure to open the valve prior to performing 
the local settings. Otherwise, the compressor may fail.

Discharge any static electricity from your body before touching the push switches. Never 
touch any terminal or pattern of any parts on the control board.

The positions of the switches on the outdoor unit control board are shown in the 

fi

 gure 

• 

below.

Terminal blocks

Reactors

Various settings can be adjusted by changing DIP switches and push switches on the 

• 

board of the outdoor unit.

DIP switch

Push 
switches

LED display

The printed characters for the LED display are shown below.

• 

SW1

SW2

SW3

SW4

SW5

SW6

(1)

(2) (3) (4)

(5)

(6)

LED display part

8.2. Description of display

Display lamp

Function or operation method

(1) POWER/MODE

Green

Lights on while power on Local setting in 
outdoor unit or error code is displayed with 
blink.

(2) ERROR

Red

Blinks during abnormal air-conditioner 
operation. 

(3) TEST 

RUN 

(L1)

Orange

Lights on during test operation.

(4) PUMP 

DOWN 

(L2)

Orange

Lights on during pump down operation.

(5)  LOW NOISE MODE 

(L3, L4)

Orange

Lights on during “Low noise” function when 
local setting is activated. 
(Lighting pattern of L3 and L4 indicates 
low noise level) 

B

 Refer to “9. LOCAL 

SETTING”.

(6) PEAK 

CUT 

(L5, L6, L7)

Orange

Lights on during “Peak cut” function when 
local setting is activated.
(Lighting pattern of L5, L6 and L7 indicates 
peak cut level) 

B

 Refer to “9. LOCAL 

SETTING”.

Switch

Function or operation method

SW1

DIP switch

For selecting cooling or heating during test 
operation.
Positions 2 to 4 of DIP switch are not used.

SW2

Push switch

To switch between “Local setting” and “Error code 
display”.

SW3

Push switch

To switch between the individual “Local settings” 
and the “Error code displays”.

SW4

Push switch

To 

fi

 x the individual “Local settings”, “Test run” and 

the “Error code displays”.

SW5

Push switch

EXIT

SW6

Push switch

To start the pump down operation.

DIP switches 1 to 4 at shipment from the factory are set as follows.

• 

DIP switch

1

2

3

4

COOL

OFF

OFF

OFF

s

d

9. LOCAL SETTING

 CAUTION

Discharge the static electricity from your body before setting up the switches.
Never touch the terminals or the patterns on the parts that are mounted on the board.

9.1. Low noise mode (Local work)

Outdoor unit may be operated with lower noise than normal operation when following 
below local work.

Low noise operation is available by installation of an additional commercially available 

• 

timer or contact input from the ON-OFF switch to the CN19 connector (an external 
contact input sold separately) on the control board of the outdoor unit.

* Performance may be de

fi

 cient depending on outdoor temperature or conditions etc.

< Example of circuit diagram >

Outdoor unit control 
board

Remote control 
panel

Adapter for 
external input

CN19

Power supply

Red

White

Black

1

2

3

1

2

3

SW1

Local purchase

(1)   Make a circuit of the above 

fi

 gure with 

an “Adapter for external input” sold 
separately. 

(2)  Low noise operation can be set up with 

the operation of external display portion. 

SW1...ON
Level 1
(Shipment condition)
Level 2

SW1...OFF 
Normal operation

9379069403_IM.indb   10

9379069403_IM.indb   10

1/29/2013   4:44:20 PM

1/29/2013   4:44:20 PM

Содержание AOYG60LATT

Страница 1: ...vicio autorizado MANUALE DI INSTALLAZIONE UNITÀ ESTERNA A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΞΩΤΕΡΙΚΗ ΜΟΝΑΔΑ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO UNIDADE EXTERIOR Apenas para pessoal de assistência autorizado РУКОВОДСТВО ПО УСТАНОВКЕ ВНЕШНИЙ МОДУЛЬ Только для авторизованного обслуживающего персонала MONTAJ KILAVUZU DIŞ ÜNİTE Yalnızca...

Страница 2: ...ncluding children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with the appliance Do not touch the aluminum fins of heat exchanger built in the indoor or outdoor unit...

Страница 3: ...nce other than the prescribed refrigerant into the refrigeration cycle If air enters the refrigeration cycle the pressure in the refrigeration cycle will become abnormally high and cause the piping to rupture If there is a refrigerant leak make sure that it does not exceed the concentration limit If a refrigerant leak exceeds the concentration limit it can lead to accidents such as oxygen starvati...

Страница 4: ...tion space shown in the following examples is based on an ambient temperature under cooling operation of 35 C DB at the air intake of the outdoor unit Provide more space around the air intake than shown in the examples if the ambient temperature exceeds 35 C DB or if the thermal load of all of the outdoor units exceeds the capacity Consider the transportation route installation space maintenance s...

Страница 5: ...n which may cause noise and vibration Therefore attach damping materials such as damping pads to the outdoor unit during installation Install the foundation making sure that there is enough space for installing the connection pipes Secure the unit to a solid block using foundation bolts Use 4 sets of commercially available M10 bolts nuts and washers The bolts should protrude 20 mm Refer to the fig...

Страница 6: ...ont lateral side rear side and bottom Fig A When connecting at the bottom remove the service panel and piping cover on the front of the outdoor unit and open the knock out hole provided at the bottom corner of the piping outlet It can be installed as shown on Fig B cutting out the 2 slits as indicated on Fig C When cutting slits use a steel saw Fig A Service panel Front connection Bottom connectio...

Страница 7: ...tighten the flare nut correctly Outer panel may be distorted if fastened only with a wrench Be sure to fix the elementary part with a spanner and fasten with a wrench refer to below diagram Do not apply force to the blank cap of the valve or hang a wrench etc on the cap It may cause leakage of refrigerant Blank cap Flare nut Torque wrench Holding wrench Torque wrench 90 Flare nut mm in Tightening ...

Страница 8: ...harge from the liquid phase side whose composition is stable Adding refrigerant through the gas pipe will cause a malfunction Check if the steel cylinder has a siphon installed or not before filling There is an indication with siphon for filling liquid on the steel cylinder Filling method for cylinder with siphon R410A Gas Liquid Set the cylinder vertical and fill with the liquid Liquid can be fil...

Страница 9: ...mission cable come in contact with valves Gas Never install a power factor improvement condenser Instead of improving the power factor the condenser may overheat Be sure to perform the earthing grounding work Do not connect earthing grounding wires to a gas pipe water pipe lightning rod or earthing grounding wire for a telephone Connection to a gas pipe may cause a fire or explosion if gas leaks C...

Страница 10: ... the insulation sheet after the wiring is complete s d 7 PIPE INSTALLATION 2 WARNING Install the insulated pipes so that they do not touch the compressor 7 1 Installing insulation Use an insulation on the refrigerant pipes to prevent condensation and dripping Fig A Determine the thickness of the insulation material by referring to Table A Table A Selection of insulation for using an insulation mat...

Страница 11: ...ting is activated Lighting pattern of L5 L6 and L7 indicates peak cut level B Refer to 9 LOCAL SETTING Switch Function or operation method SW1 DIP switch For selecting cooling or heating during test operation Positions 2 to 4 of DIP switch are not used SW2 Push switch To switch between Local setting and Error code display SW3 Push switch To switch between the individual Local settings and the Erro...

Страница 12: ... LOW NOISE Blink PEAK CUT MODE 4 Press ENTER switch SW4 TEST RUN L1 L2 L3 L4 PUMP DOWN LOW NOISE PEAK CUT MODE Sign Lights on 5 Press SELECT switch SW3 and adjust LED display as shown in below figure PEAK CUT L5 L6 L7 Blink Blink Blink Blink Blink 0 of rated input ratio 50 of rated input ratio 75 of rated input ratio 100 of rated input ratio 9 1 1 Setting for low noise SW2 SW3 SW4 SW5 LED display ...

Страница 13: ...ay Normal operation by pressing EXIT switch SW5 When pressed number is lost during operation restart from the beginning of operation procedure after returning to Operation status display normal operation by pressing the EXIT switch once s d 10 TEST RUN CAUTION Always turn on the power 6 hours prior to the start of the operation in order to protect the compressor 10 1 Check items before performing ...

Страница 14: ...sed refrigerant may flow into the piping after the compressor stops Step 5 Closing direction Step 4 Hexagon wrench Liquid pipe Gas pipe Closing direction 6 LED display changes after 1 minute as shown in the figure below ERROR TEST RUN PUMP DOWN LOW NOISE PEAK CUT POWER MODE L1 L2 L3 L4 L5 L6 L7 Fans and compressor stop automatically If the pump down is successfully completed the above LED display ...

Страница 15: ... 2 Compressor temp sensor error 2 7 3 Heat Ex middle temp sensor error 2 7 3 Outdoor unit Heat Ex liquid temp sensor error 2 7 4 Outdoor temp sensor error 2 7 7 Heat sink temp sensor error 2 7 7 PFC heat sink temp sensor error 2 8 4 Current sensor 1 error stoppage permanently 2 8 6 High pressure switch 1 error 2 8 6 Pressure sensor error 2 9 4 Trip detection stoppage permanently 2 9 5 Compressor m...

Отзывы: