En-8

POWER

71 

 

WARNING

Always use a special branch circuit and install a special receptacle to supply power to 

the air conditioner.
Use a special branch circuit breaker and receptacle matched to the capacity of the air 

conditioner. (Install in accordance with standard.)

Perform wiring work in accordance with standards so that the air conditioner can be 

operated safely and positively.
Install a leakage special branch circuit breaker in accordance with the related laws 

and regulations and electric company standards.

 

CAUTION

When the voltage is low and the air conditioner is difficult to start, contact the power 

company the voltage raised.

TEST RUN

81 

The test run method may be different for each indoor unit that is connected. Refer to the 

installation Manual included with each indoor unit.

 CAUTION

Always turn on the power 12 hours prior to the start of the operation in order to ensure 

compressor protection.

Make a TEST RUN in accordance with the installation Manual 

81 11 

for the indoor unit

CHECK ITEMS

81 11 11 
(1) INDOOR UNIT

Is operation of each button on the remote controller normal?

(

1

)

 

Does each lamp light normally?

(

2

)

 

Do the air flow-direction louver operate normally?

(

3

)

 

Is the drain normal?

(

4

)

 

Is there any abnormal noise and vibration during operation?

(

5

)

 

(2) OUTDOOR UNIT

Is there any abnormal noise and vibration during operation?

(

1

)

 

Will noise, wind, or drain water from the unit disturb the neighbors?

(

2

)

 

Is there any gas leakage?

(

3

)

 

Do not operate the air conditioner in the test running state for a long time.

 

For the operation method, refer to the operating manual and perform operation check. 

 

Outdoor unit LEDS

81 21 

When a malfunction occurs in the outdoor unit, the LED on the circuit board lights to 

indicate the error. Refer to the following table for the description of each error according to 

the LED.

Error contents

LED 1

LED 2

LED 3

LED 4

Communication error 

(outdoor unit to indoor unit A) ●1 time

-

-

-

Communication error 

(outdoor unit to indoor unit B)

-

●1 time

-

-

Communication error 

(outdoor unit to indoor unit C)

-

-

●1 time

-

Communication error 

(outdoor unit to indoor unit D)

-

-

-

●1 time

Discharge temp. sensor error

●2 times

-

-

-

Outdoor unit Heat Ex. middle temp. sensor error

●3 times

-

-

-

Outdoor temp. sensor error

●4 times

-

-

-

2 way valve temp. sensor error(for Indoor unit A)

●5 times

-

-

-

2 way valve temp. sensor error(for Indoor unit B)

-

●5 times

-

-

2 way valve temp. sensor error(for Indoor unit C)

-

-

●5 times

-

2 way valve temp. sensor error(for Indoor unit D)

-

-

-

●5 times

3 way valve temp. sensor error(for Indoor unit A)

●6 times

-

-

-

3 way valve temp. sensor error(for Indoor unit B)

-

●6 times

-

-

3 way valve temp. sensor error(for Indoor unit C)

-

-

●6 times

-

3 way valve temp. sensor error(for Indoor unit D)

-

-

-

●6 times

Compressor temp. sensor error

●7 times

-

-

-

Heat sink temp. sensor error

●8 times

-

-

-

High pressure switch 1 error

●9 times

-

-

-

High pressure switch 2 error

●10 times

-

-

-

Indoor unit capacity error

●11 times

-

-

-

Trip detection

●12 times

-

-

-

Compressor rotor position detection error

●13 times

-

-

-

Error contents

LED 1

LED 2

LED 3

LED 4

Trip terminal L error

●14 times

-

-

-

Outdoor unit fan motor error

●15 times

-

-

-

Outdoor unit PCB microcomputer 

communication error

●17 times

-

-

-

Discharge temperature error

●18 times

-

-

-

Compressor temperatuer error

●19 times

-

-

-

4 way valve error

●20 times

-

-

-

Outdoor unit PCB model information error

●21times

-

-

-

Active filter error, PFC circuit error

●22 times

-

-

-

● : flashing  

- : Off

LED is on a reverse 

side of the board.

Hole

LED4

LED3

LED2

LED1

PUMP DOWN

91 

PUMP DOWN OPERATION

To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal, 

recover refrigerant by doing the cooling operation or forced cooling operation according to 

the following procedure. (When the cooling operation cannot start in winter, and so on, start 

the forced cooling operation.) 

Do the air purging of the charge hose by connecting the charging hose of gauge 

(

1

)

 

manifold to the charging port of 3 way valve (At lease one unit of connected units) and 

opening the low pressure valve slightly.

Close the valve stem of 2 way valve (All connected units) completely.

(

2

)

 

Start the cooling operation or following forced cooling operation. (All connected units) 

(

3

)

 

When using the remote controller Press the TEST RUN button after starting the cooling 

operation by the remote controller. The operation indicator lamp and timer indicator 

lamp will begin to flash simultaneously during test run. When using the MANUAL AUTO 

button of the indoor unit (The remote controller is lost, and so on.) Keep on pressing 

the MANUAL AUTO button of the indoor unit for more than 10 seconds. (The forced 

cooling operation cannot start if the MANUAL AUTO button is not kept on pressing for 

more than 10 seconds.)

Close the valve stem of 3 way valve (All connected units) when the reading on the 

(

4

)

 

compound pressure gauge becomes 0.05~0 Mpa (0.5~0 kg/cm

2

).

Stop the operation. (All connected units) Press the START/STOP button of the remote 

(

5

)

 

controller to stop the operation. Press the MANUAL AUTO button when stopping the 

operation from indoor unit side. (It is not necessary to press on keeping for more than 

10 seconds.)

 

9374872121-03_IM.indb   8

2/10/2555   10:08:04

Содержание aoyg30lat4

Страница 1: ...AZIONE ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ MANUAL DE INSTALAÇÃO РУКОВОДСТВО ПО УСТАНОВКЕ MONTAJ KILAVUZU For authorized personnel only PART NO 9374872121 03 Nur für autorisiertes Personal Pour le personnel agréé uniquement Solo para personal autorizado Ad uso esclusivo del personale autorizzato Για εξουσιοδοτημένο προσωπικό σέρβις Apenas para técnicos autorizados Для уполномоченного персонала Yetkili servis p...

Страница 2: ... all security information before use or install the air conditioner Do not attempt to install the air conditioner or a part of the air conditioner by yourself This unit must be installed by qualified personnel with a capacity certificate for handling refrigerant fluids Refer to regulation and laws in use on installation place The installation must be carried out in compliance with regulations in f...

Страница 3: ...ce 230 V 50 Hz Power cable Connection cable Refrigerant pipe d c H1 H1 H2 b a CONNECTABLE INDOOR UNIT CAPACITY TYPE 222222222 CAUTION The total capacity of the indoor units connected must be between 27 000 and 49 000BTU Be sure to check the connecting pattern in technical manual when installed since connection pattern is specified in it Operation cannot be guaranteed if connected by a method not s...

Страница 4: ... accumulation snow fall or freezing take appropriate measures to protect it from those elements To ensure a stable operation install inlet and outlet ducts Install the outdoor unit in a location that is away from exhaust or the vent ports that discharge vapor soot dust or debris Install the indoor unit outdoor unit power supply cable connection cable and remote controller cable at least 1 m away f...

Страница 5: ...h as concrete blocks The foundation shall support the legs of the unit and have a width of 50mm or more Depending on the installation conditions the outdoor unit may spread its vibration during operation which may cause noise and vibration Therefore attach damping materials such as damping pads to the outdoor unit during installation Install the foundation making sure that there is enough space fo...

Страница 6: ...63 to 75 630 to 750 19 05 3 4 dia 90 to 110 900 to 1100 HOW TO USE ADAPTER Connection ports of outdoor unit 444444444 When using the ADAPTER be careful not to overtighten the nut or the smaller pipe may be damaged Apply a coat of refrigeration oil to the threaded connection port of the outdoor unit where the flare nut comes in Use appropriate wrenches to avoid damaging the connection thread by ove...

Страница 7: ...t comply with the applicable local and national code Unit wiring 555555 When stripping off the coating of a lead wire always use a special tool such as a wire stripper If there is no special tool available carefully strip the coating with a knife etc Earth Ground wire 30 mm 100 mm or more Power supply cable Earth Ground wire 15 mm 60 mm or more Connection cable How to connect wiring to the termina...

Страница 8: ... it is satisfactory If a pressure decrease is confirmed there is a leak so it is necessary to specify the leak location and make minor adjustments Discharge the nitrogen gas and starting removing the gas with a vacuum pump Open the valve of the gauge manifold fully Operate the vacuum pump and start pump down Check that the compound pressure gauge reads 0 1 MPa 76 cmHg operate the vacuum pump for 3...

Страница 9: ...sor error for Indoor unit D 5 times 3 way valve temp sensor error for Indoor unit A 6 times 3 way valve temp sensor error for Indoor unit B 6 times 3 way valve temp sensor error for Indoor unit C 6 times 3 way valve temp sensor error for Indoor unit D 6 times Compressor temp sensor error 7 times Heat sink temp sensor error 8 times High pressure switch 1 error 9 times High pressure switch 2 error 1...

Отзывы: