SAFETY PRECAUTIONS

11 

Be sure to read this Manual thoroughly before installation.

The warnings and precautions indicated in this Manual contain important information 

pertaining to your safety. Be sure to observe them.

Hand this Manual, together with the Operating Manual, to the customer. Request the 

customer to keep them on hand for future use, such as for relocating or repairing the unit.

After installation, explain correct operation to the customer, using the operating manual.

 

WARNING

This mark indicates procedures which, if improperly performed, 

might lead to the death or serious injury of the user.

Never touch electrical components immediately after the power supply has been turned 

off. Electrical shock may occur. After turning off the power, always wait 5 minutes or 

more before touching electrical components.
Request your dealer or a professional installer to install the indoor unit in accordance 

with this Installation Manual. An improperly installed unit can cause serious accidents 

such as water leakage, electric shock, or fire. If the indoor unit is installed in disregard 

of the instructions in the Installation Manual, it will void the manufacturer’s warranty.
Do not turn ON the power until all work has been completed. Turning ON the power 

before the work is completed can cause serious accidents such as electric shock or fire.

If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant 

comes in contact with a flame, it produces a toxic gas.

Installation work must be performed in accordance with national wiring standards by 

authorized personnel only.

Do not use this equipment with air or any other unspecified refrigerant in the refrigerant 

lines.

Excess pressure can cause a rupture.

During installation, make sure that the refrigerant pipe is attached firmly before you run 

the compressor. 

Do not operate the compressor under the condition of refrigerant piping not attached 

properly with 2-way or 3-way valve open. This may cause abnormal pressure in the 

refrigeration cycle that leads to rupture and even injury.
When installing and relocating the air conditioner, do not mix gases other than the 

specified refrigerant (R410A) to enter the refrigerant cycle.

If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to 

an abnormally high value and cause rupture, injury, etc.
For the air conditioner to operate satisfactorily, install it as outlined in this installation 

manual.
Connect the indoor unit and outdoor unit with the air conditioner piping and cable 

available standards parts.  

This installation manual describes the correct connections using the installation set 

available from our standard parts.
Also, do not use an extension cable.
Do not purge the air with refrigerants but use a vacuum pump to vacuum the 

installation.
There is not extra refrigerant in the outdoor unit for air purging.
Use a vacuum pump for R410A exclusively.

Using the same vacuum pump for different refrigerants may damage the vacuum pump 

or the unit.
Use a clean gauge manifold and charging hose for R410A exclusively.
During the pump-down operation, make sure that the compressor is turned off before 

you remove the refrigerant piping.

Do not remove the connection pipe while the compressor is in operation with 2 way or  

3 way valve open. This may cause abnormal pressure in the refrigeration cycle that 

leads to rupture and even injury.

 CAUTION

This mark indicates procedures which, if improperly performed, 

might possibly result in personal harm to the user, or damage 

to property.

Read carefully all security information before use or install the air conditioner.
Do not attempt to install the air conditioner or a part of the air conditioner by yourself.

This unit must be installed by qualified personnel with a capacity certificate for handling 

refrigerant fluids. Refer to regulation and laws in use on installation place.

The installation must be carried out in compliance with regulations in force in the place 

of installation and the installation instructions of the manufacturer.
This unit is part of a set constituting an air conditioner. It must not be installed alone or 

with non-authorized by the manufacturer.
Always use a separate power supply line protected by a circuit breaker operating on all 

wires with a distance between contact of 3mm for this unit.
The unit must be correctly grounded and the supply line must be equipped with a 

differential breaker in order to protect the persons.
The units are not explosion proof and therefore should not be installed in explosive 

atmosphere.
This unit contains no user-serviceable parts. Always consult authorized service 

personnel to repairs.
When moving, consult authorized service personnel for disconnection and installation 

of the unit.
Children should be monitored to ensure they do not play with the device.

This appliance is not intended for use by persons (including children) with reduced 

physical, sensory or mental capabilities, or lack of experience and knowledge, unless 

they have been given supervision or instruction concerning use of the appliance by a 

person responsible for their safety. Children should be supervised to ensure that they 

do not play with the appliance.

ABOUT THE PRODUCT

21 

Precautions for using R410A refrigerant

21 11 

 

WARNING

The basic installation work procedures are the same as conventional refrigerant models.

However, pay careful attention to the following points:

Since the working pressure is 1.6 times higher than that of conventional refrigerant 

 

(R22) models, some of the piping and installation and service tools are special. (See 

the table below.)

 

Especially, when replacing a conventional refrigerant (R22) model with a new 

refrigerant R410A model, always replace the conventional piping and flare nuts with 

the R410A piping and flare nuts.

Models that use refrigerant R410A have a different charging port thread diameter 

 

to prevent erroneous charging with conventional refrigerant (R22) and for safety. 

Therefore, check beforehand. [The charging port thread diameter for R410A is  

1/2 UNF 20 threads per inch.]

Be careful that foreign matter (oil, water, etc.) does not enter the piping than with 

 

refrigerant models. Also, when storing the piping, securely seal the openings by 

pinching, taping, etc.

When charging the refrigerant, take into account the slight change in the composition 

 

of the gas and liquid phases. And always charge from the liquid phase where 

refrigerant composition is stable.

Contents

SAFETY PRECAUTIONS

1. 

  ……………………………………………………………… 1

ABOUT THE PRODUC

2. 

T

Precautions for using R410A refrigerant

2.1. 

  ………………………………………… 1

Special tools for R410A

2.2. 

  …………………………………………………………… 2

Accessories

2.3. 

  ………………………………………………………………………… 2

System configuration

2.4. 

  ……………………………………………………………… 2

INSTALLATION WOR

3. 

K

Selecting an installation location

3.1. 

  ………………………………………………… 3

Drain installation

3.2. 

  …………………………………………………………………… 3

Installation dimensions

3.3. 

  …………………………………………………………… 3

Transportation of the unit

3.4. 

  ………………………………………………………… 4

Installation of the unit

3.5. 

  ……………………………………………………………… 4

PIPE INSTALLATION 

4. 

I

Flare connection (pipe connection)

4.1. 

  ……………………………………………… 4

ELECTRICAL WIRIN

5. 

G

The precautions of electrical wiring

5.1. 

  ……………………………………………… 5

Electrical requirement

5.2. 

 ……………………………………………………………… 6

Unit wiring

5.3. 

 …………………………………………………………………………… 6

Connection diagrams

5.4. 

  ……………………………………………………………… 6

Outdoor unit

5.5. 

 ………………………………………………………………………… 6

PIPE INSTALLATION I

6. 

I

Vacuum

6.1. 

 ……………………………………………………………………………… 7

Additional charging

6.2. 

  ………………………………………………………………… 7

POWER

7. 

  …………………………………………………………………………………… 8

TEST RU

8. 

N

Make a TEST RUN in accordance with the installation Manual  

8.1. 

for the indoor unit …………………………………………………………………… 8

Outdoor unit LEDS

8.2. 

  ………………………………………………………………… 8

PUMP DOWN

9. 

……………………………………………………………………………… 8

INSTALLATION MANUAL

PART NO. 9374872121-03

9374872121-03_IM.indb   1

2/10/2555   10:07:46

Содержание aoyg30lat4

Страница 1: ...AZIONE ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ MANUAL DE INSTALAÇÃO РУКОВОДСТВО ПО УСТАНОВКЕ MONTAJ KILAVUZU For authorized personnel only PART NO 9374872121 03 Nur für autorisiertes Personal Pour le personnel agréé uniquement Solo para personal autorizado Ad uso esclusivo del personale autorizzato Για εξουσιοδοτημένο προσωπικό σέρβις Apenas para técnicos autorizados Для уполномоченного персонала Yetkili servis p...

Страница 2: ... all security information before use or install the air conditioner Do not attempt to install the air conditioner or a part of the air conditioner by yourself This unit must be installed by qualified personnel with a capacity certificate for handling refrigerant fluids Refer to regulation and laws in use on installation place The installation must be carried out in compliance with regulations in f...

Страница 3: ...ce 230 V 50 Hz Power cable Connection cable Refrigerant pipe d c H1 H1 H2 b a CONNECTABLE INDOOR UNIT CAPACITY TYPE 222222222 CAUTION The total capacity of the indoor units connected must be between 27 000 and 49 000BTU Be sure to check the connecting pattern in technical manual when installed since connection pattern is specified in it Operation cannot be guaranteed if connected by a method not s...

Страница 4: ... accumulation snow fall or freezing take appropriate measures to protect it from those elements To ensure a stable operation install inlet and outlet ducts Install the outdoor unit in a location that is away from exhaust or the vent ports that discharge vapor soot dust or debris Install the indoor unit outdoor unit power supply cable connection cable and remote controller cable at least 1 m away f...

Страница 5: ...h as concrete blocks The foundation shall support the legs of the unit and have a width of 50mm or more Depending on the installation conditions the outdoor unit may spread its vibration during operation which may cause noise and vibration Therefore attach damping materials such as damping pads to the outdoor unit during installation Install the foundation making sure that there is enough space fo...

Страница 6: ...63 to 75 630 to 750 19 05 3 4 dia 90 to 110 900 to 1100 HOW TO USE ADAPTER Connection ports of outdoor unit 444444444 When using the ADAPTER be careful not to overtighten the nut or the smaller pipe may be damaged Apply a coat of refrigeration oil to the threaded connection port of the outdoor unit where the flare nut comes in Use appropriate wrenches to avoid damaging the connection thread by ove...

Страница 7: ...t comply with the applicable local and national code Unit wiring 555555 When stripping off the coating of a lead wire always use a special tool such as a wire stripper If there is no special tool available carefully strip the coating with a knife etc Earth Ground wire 30 mm 100 mm or more Power supply cable Earth Ground wire 15 mm 60 mm or more Connection cable How to connect wiring to the termina...

Страница 8: ... it is satisfactory If a pressure decrease is confirmed there is a leak so it is necessary to specify the leak location and make minor adjustments Discharge the nitrogen gas and starting removing the gas with a vacuum pump Open the valve of the gauge manifold fully Operate the vacuum pump and start pump down Check that the compound pressure gauge reads 0 1 MPa 76 cmHg operate the vacuum pump for 3...

Страница 9: ...sor error for Indoor unit D 5 times 3 way valve temp sensor error for Indoor unit A 6 times 3 way valve temp sensor error for Indoor unit B 6 times 3 way valve temp sensor error for Indoor unit C 6 times 3 way valve temp sensor error for Indoor unit D 6 times Compressor temp sensor error 7 times Heat sink temp sensor error 8 times High pressure switch 1 error 9 times High pressure switch 2 error 1...

Отзывы: