En-2

Thicknesses of Annealed Copper Pipes

Nominal 

diameter

Outer 

diameter

Thickness

Maximum 

length

Maximum height 

(between indoor and out-

door)

1/4 in

6.35 mm

0.8 mm

30 m (99 ft)

20 m (66 ft)

5/8 in

15.88 mm

1.0 mm

 WARNING

To install a unit that uses R410A refrigerant, use dedicated tools and piping materials 
that have been manufactured speci

fi

 cally for R410A use. Because the pressure of 

R410A refrigerant is approximately 1.6 times higher than R22, failure to use dedicated 
piping material or improper installation can cause rupture or injury. Furthermore, it can 
cause serious accidents such as water leakage, electric shock, or 

fi

 re.

2.3. Power

• The rated voltage

230 V   AC  50 Hz.

 WARNING

Before turning on the power, check if the voltage is within the 220 V -10 % to 240 V 
+10 % range.

Always use a special branch circuit and install a special receptacle to supply power to 
the room air conditioner.

Use a circuit breaker and receptacle matched to the capacity of the air conditioner.

Install a leakage circuit breaker in accordance with the related laws and regulations 
and electric company standards.

The circuit breaker is installed in the permanent wiring. Always use a circuit that can 
trip all the poles of the wiring and has an isolation distance of at least 3 mm between 
the contacts of each pole.

 CAUTION

The power source capacity must be the sum of the air conditioner current and the cur-
rent of other electrical appliances. When the current contracted capacity is insuf

fi

 cient, 

change the contracted capacity.
When the voltage is low and the air conditioner is dif

fi

 cult to start, contact the power 

company the voltage raised.

2.4. Electric requirement

•  Electric wire size and fuse capacity:

Cable

Conductor size [mm

2

]

Type

Power supply cable

MAX.

4.0

Type60245 IEC57

MIN.

3.5

Connection cable

MAX.

2.5

Type60245 IEC57

MIN.

1.5

Fuse capacity (A)

30

2.5. Additional charge

Refrigerant suitable for a piping length of 15 m is charged in the outdoor unit at the factory.
When the piping is longer than 15 m, additional charging is necessary.
Between 15 m and 30 m, when using a connection pipe other than that in the table, charge 
additional refrigerant with 20 g/1 m as the criteria.
For the additional amount, see the table below.

Pipe length

15 m

20 m

25 m

30 m

Rate

Additional refrigerant

None

+100 g

+200 g

+300 g

20 g/m

 CAUTION

When adding refrigerant, add the refrigerant from the charging port at the completion 
of work.
The maximum length of the piping is 30 m. If the units are further apart than this, correct 
operation can not be guaranteed.

2.6. Accessories

The following installation accessories are supplied.
Use them as required.

Drain pipe

1

Drain cap

3

Installation manual

1

One set of following parts are necessary installation of this product.

Name

Connection pipe assembly
Connection cable
Wall pipe
Decorative tape
Vinyl tape
Wall cap
Saddle
Drain hose
Tapping screws
Sealant

3.  SELECTING THE MOUNTING POSITION

•  Decide the mounting position with the customer as follows.
•  Do not set to a place where there is oily smoke, oil is used in the factory, the unit can 

contact sea breeze, sul

fi

 de gases will be generated in the hot spring area, corrosive 

gases will be generated, animal may urine on the unit and ammonia will be generated 
and a dusty place.

3.1. Outdoor unit

(1) If possible, do not install the unit where it will be exposed to direct sunlight. 

(If necessary, Install a blind that does not interfere with the air 

fl

 ow.)

(2)  Do not install the unit where a strong wind blows or where it is very dusty.
(3)  Do not install the unit where people pass.
(4)  Take you neighbors into consideration so that they are not disturbed by air blowing into their 

windows or by noise.

(5)  Provide the space shown in 

fi

 gure so that the air

fl

 ow is not blocked. Also for ef

fi

 cient 

operation, leave open three of the four directions front, rear, and both sides.

(6)  Install the unit where keep away more than 3 m from the antenna of TV set and Radio.
(7)  Outdoor unit should be set to a place where both drainage and itself will not be 

affected when heating.

 WARNING

Install at a place that can withstand the weight of the outdoor units and install positively 
so that the units will not topple or fall.

 CAUTION

Do not install where there is the danger of combustible gas leakage.
Do not install near heat sources.
If children under 10 years old may approach the unit, take preventive measures so that 
they cannot reach the unit.

4. INSTALLATION DIAGRAM

[OUTDOOR UNIT]

10 cm or over

60 cm or over

10 cm or over

30 cm or over

30 cm or 
over

5 cm or over

INDOOR UNIT

•  Do not directly install it on the 

ground, otherwise it will cause 
failure.

•  To obtain better operation ef-

ficiency, when the outdoor unit 
is installed, be sure to open the 
front and left side.

54 cm

32 cm

Outdoor 

unit 

bottom

Drain 

pipe

Drain cap

Drain cap

9332808039_IM.indb   2

9332808039_IM.indb   2

2012-10-8   11:34:48

2012-10-8   11:34:48

Содержание AOYG24LFC

Страница 1: ...h s i l g n E INSTALLATION MANUAL For authorized service personnel only INSTALLATION MANUAL AOYG24LFC OUTDOOR UNIT PART No 9332809039 ...

Страница 2: ...egulation and laws in use on installation place The installation must be carried out in compliance with regulations in force in the place of installation and the installation instructions of the manufacturer This unit is part of a set constituting an air conditioner It must not be installed alone or with non authorized by the manufacturer The unit must be correctly earthed grounded and the supply ...

Страница 3: ...0 g 200 g 300 g 20 g m CAUTION When adding refrigerant add the refrigerant from the charging port at the completion of work The maximum length of the piping is 30 m If the units are further apart than this correct operation can not be guaranteed 2 6 Accessories The following installation accessories are supplied Use them as required Drain pipe 1 Drain cap 3 Installation manual 1 One set of followi...

Страница 4: ...e plug Do not use the earth screw for an external connector Only use for interconnection between two units 5 5 Connecting the piping CONNECTION 1 Install the outdoor unit wall cap supplied with the optional installation set or pro cured at the site to the wall pipe 2 Connect the outdoor unit and indoor unit piping 3 After matching the center of the flare surface and tightening the nut hand tight t...

Страница 5: ...open the valve stems of the 2 way valve and 3 way valve using a hexagon wrench After the valve stem begins to turn turn it with a torque of less than 2 9 N m 30 kgf cm until it stops turning 11 Firmly tighten the 2 way valve and 3 way valve blank cap and the charging port cap 3 way valve 2 way valve Charging port cap Vacuum pump Charge hose Charge hose Charging port Blank cap Valve stem Flare nut ...

Отзывы: