1. Specifications
Type
Wall mounted
Inverter heat pump
Model name
ASYG18KLCA
ASYG24KLCA
Power supply
230 V ~ 50 Hz
Available voltage range
198—264 V
Capacity
Cooling
Rated
kW
5.20
7.10
Btu/h
17,700
24,200
Min.—Max.
kW
0.9—5.5
0.9—7.7
Btu/h
3,000—18,700
3,000—26,200
Heating
Rated
kW
6.30
8.00
Btu/h
21,400
27,200
Min.—Max.
kW
0.6—6.6
0.9—9.0
Btu/h
2,000—22,500
3,000—30,700
Input power
Cooling
Rated
kW
1.685
2.42
Min.—Max.
0.14—2.09
0.18—2.74
Heating
Rated
1.800
2.225
Min.—Max.
0.10—1.93
0.15—2.66
Fan
HIGH
W
32
57
MED
25
34
LOW
16
17
QUIET
10
10
Current
Cooling
Rated
A
7.5
10.9
Heating
8.0
10.4
EER
Cooling
kW/kW
3.09
2.93
COP
Heating
3.50
3.60
Sensible capacity
Cooling
kW
3.93
4.92
Power factor
Cooling
%
98.0
Heating
98.0
Moisture removal
L/h (pints/h)
1.9 (3.3)
3.1 (5.5)
Maximum operating current *1
Cooling
A
9.5
13.5
Heating
13.5
17.5
Fan
Airflow rate
Cooling
HIGH
m
3
/h
865
1,040
MED
780
880
LOW
665
685
QUIET
555
555
Heating
HIGH
995
1,040
MED
810
800
LOW
700
680
QUIET
590
580
Type × Q'ty
Cross flow fan × 1
Motor output
W
61
Sound pressure level *2
Cooling
HIGH
dB (A)
47
51
MED
44
45
LOW
40
38
QUIET
35
33
Heating
HIGH
50
52
MED
45
45
LOW
41
41
QUIET
37
37
Heat exchanger type
Dimensions (H × W × D)
mm
Main: 384 × 630 × 20.0
Sub: 126 × 630 × 13.30
Main: 384 × 630 × 20.0
Sub1: 84 × 630 × 13.30
Sub2: 126 × 630 × 13.30
Fin pitch
Man: 1.1, Sub: 1.4
Man: 1.1, Sub1: 1.4, Sub2: 1.4
Rows × Stages
Main: 2 × 24, Sub: 1 × 6
Main: 2 × 24, Sub1: 1 × 4, Sub2: 1 × 6
Pipe type
Copper tube
Fin type
Aluminum
Enclosure
Material
Polystyrene
Color
White
Approximate color of Munsell N 9.25/
Dimensions
(H × W × D)
Net
mm
293 × 790 × 249
Gross
320 × 840 × 375
Weight
Net
kg
9.5
10.0
Gross
12.0
12.5
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4)
Ø 6.35 (Ø 1/4)
Gas
Ø 9.52 (Ø 3/8)
Ø 12.70 (Ø 1/2)
Method
Flare
Drain hose
Material
PP+HDPE
Size
mm
Ø 13.8 (I.D.), Ø 15.8 to Ø 16.7 (O.D.)
Operation range
Cooling
°C
18 to 32
%RH
80 or less
Heating
°C
16 to 30
Remote controller type
Wireless
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB
– Pipe length: 5 m, Height difference: 0 m (Between outdoor unit and indoor unit)
• Protective function might work when using it outside the operation range.
• *1: Maximum current is maximum value when operated within the operation range.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
DESIGN & TECHNICAL MANUAL
- 2 -
WALL MOUNTED
ASYG18, 24KLCA
Содержание AOYG18KLTA
Страница 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASYG18KLCA ASYG24KLCA ...
Страница 10: ...3 Wiring diagrams 3 1 Models ASYG18KLCA and ASYG24KLCA 6 WALL MOUNTED ASYG18 24KLCA ...
Страница 28: ... 24 WALL MOUNTED ASYG18 24KLCA ...
Страница 29: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG18KLTA AOYG24KLTA ...
Страница 38: ...5 Wiring diagrams 5 1 Model AOYG18KLTA 5 2 Model AOYG24KLTA 34 OUTDOOR UNIT AOYG18 24KLTA ...