1. Specifications
Type
Inverter heat pump
Model name
AOYG09KHCAN
AOYG12KHCAN
AOYG14KHCAN
Power supply
230 V ~ 50 Hz
Power supply intake
Outdoor unit
Available voltage range
198—264 V
Starting current
A
2.7
3.6
5.2
Fan
Airflow rate
Cooling
m
3
/h
1,810
2,050
2460
Heating
1,550
1,780
Type × Q'ty
Propeller fan × 1
Motor output
W
49
Sound pressure level *
Cooling
dB (A)
43
47
53
Heating
42
45
47
Sound power level
Cooling
dB (A)
56
60
65
Heating
55
58
60
Heat exchanger type
Dimensions
(H × W × D)
mm
Main1: 588 × 881 × 18.2
Main2: 588 × 851 × 18.2
Fin pitch
Main1: 1.3
Main2: 1.3
Rows × Stages
1 × 28
Pipe type
Copper
Fin type
Type (Material)
Corrugate (Aluminum)
Surface treat-
ment
PC fin
Compressor
Type × Q'ty
DC rotary × 1
Motor output
W
810
900
Refrigerant
Type (Global warming potential)
R32 (675)
Charge
g
1,100
Refrigerant oil
Type
FW68S
Amount
cm
3
350
Enclosure
Material
Steel sheet
Color
Beige
Approximate color of Munsell 10YR 7.5/1.0
Dimensions
(H × W × D)
Net
mm
620 × 790 × 290
Gross
713 × 945 × 395
Weight
Net
kg
36
Gross
40
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4)
Gas
Ø 9.52 (Ø 3/8)
Method
Flare
Pre-charge length
m
15
Max. length
20
Max. height difference
15
Operation range
Cooling
°C
-10 to 46
Heating
-25 to 24
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/ 19 °CWB, and outdoor temperature of 35 °CDB/ 24 °CWB.
– Heating: Indoor temperature of 20 °CDB/ 15 °CWB, and outdoor temperature of 7 °CDB/ 6 °CWB.
– Pipe length: 5 m, Height difference: 0 m.
• Protective function might work when using it outside the operation range.
• *: Sound pressure level
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
- 34 -
1. Specifications
OUTDOOR UNIT
AOYG09-14KHCAN
OUTDOOR UNIT
AOYG09-14KHCAN