The maximum value of the indoor fan speed is set as shown in Fig.6 based on the detected
temperature by the indoor heat-exchanger sensor on heating mode.
( Fig.6 : Cool air prevension control )
01-06
6. COOL AIR PREVENTION CONTROL (Heating mode)
42°C
30°C
34°C
Indoor heat exchanger
temperature rises
Indoor heat exchanger
temperature drops
Hi
Me+
Lo
Cool air
prevention
39°C
37°C
37°C
32°C
28°C
S-Lo
Switch the airflow [Auto] at cooling mode, and the indoor fan motor will run as shown in Fig.7.
When the defrost operation starts, the indoor fan runs according to cool air preventtion control for 20 seconds.
And the fan is stopped if 20 seconds have passed.
When 60 seconds have passed after defrost operation is released,
the fan runs according to cool air preventtion control
7. MOISTURE RETURN PREVENTION CONTROL (Cooling mode& Dry mode)
9. DEFROST OPERATION
Switch the airflow at cooling mode, and the indoor fan motor will run as shown in Fig.7.
It depends on the Function setting "Indoor unit fan control for energy saving".
8. INDOOR UNIT FAN (CONTROL FOR ENERGY SAVING (Cooling mode))
( Fig.7 : Indoor fan control )
Compressor
ON
OFF
Indoor fan
Setting air flow
Indoor fan
(as shown in Table 7)
S-Lo
OFF
10
30
60
180
60
180
60
10
30
(sec)
( Table 7 : Indoor fan speed )
X zone
J zone
07/09/12
680rpm
660rpm
680rpm
Dry
Cooling
42°C
30°C
34°C
Indoor heat exchanger
temperature rises
Indoor heat exchanger
temperature drops
Powerful
Hi
Lo
Cool air
prevention
39°C
37°C
37°C
32°C
28°C
S-Lo
<Normal operation>
<Powerful operation>
14
750rpm
730rpm
750rpm
Model
Содержание AOYG07LMCE
Страница 4: ...2016 11 21 3 OUTDOOR UNIT 15 663 mm 20 293 mm 68 454 mm 535 mm ...
Страница 21: ...1611G4556 ...
Страница 24: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 46: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Страница 52: ...3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...