5. INDOOR FAN CONTROL
The airflow can be switched in 5 steps such as Auto, Quiet, Lo, Me, Hi, while the indoor fan only runs.
When fan mode is set at [Auto], it operates on [Me] fan Speed.
01-05
2. FAN OPERATION
3. COOLING OPERATION
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature,
as shown in Figure3.
On the other hand, if switched in [Hi] [Quiet], the indoor motor will run at a constant airflow of [Cool]
operation modes Quiet, Lo, Me, Hi, as shown in Table 6.
( Fig.4 : Airflow change - over ( Cooling : Auto ) )
When the room
temperature rises
When the room
temperature drops
TR : Room temperature
Ts : Setting temperature
TR-Ts > 2°C
1°C > TR-Ts
2°C > TR-Ts > 1°C
=
TR-Ts > 2.5°C
=
1.5°C > TR-Ts
2.5°C > TR-Ts > 1.5°C
=
Hi mode
Me mode
Lo mode
1. Fan speed
( Table 6 : Indoor fan speed )
Operation mode
Air flow mode
Speed (rpm)
Heating
4. DRY OPERATION
Refer to the Table 6.
During the dry mode operation, the fan speed setting can not be changed.
Hi
Me+
Me
Lo
Quiet
S-Lo
Cool air prevention
Powerful
1380 (1420)
1320 (1360)
1280 (1330)
1160 (1220)
980 (1040)
710 (770)
600 (600)
480 (480)
Operation mode
Air flow mode
Speed (rpm)
Cooling/ Fan
Dry
X zone 680 (750)
J zone 660 (730)
Hi
Me
Lo
Quiet
*Soft Quiet
Powerful
1380 (1420)
1320 (1360)
1160 (1220)
930 (990)
680 (750)
600 (670)
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs.
(Hi > Me, Me > Lo, Lo > Quiet, Quiet > Soft Quiet)
5. HEATING OPERATION
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature,
as shown in Fig. 5
On the other hand, if switched in [Hi] [Quiet], the indoor motor will run at a constant airflow
of [Heat] operation modes Quiet, Lo, Me, High, as shown in Table 6.
( Fig.5 : Airflow change - over ( Heating : Auto ) )
TR-Ts > -1.5°C
=
-2.5°C > TR-Ts
-1.5°C > TR-Ts > -2.5°C
=
TR-Ts > -1°C
=
-2°C > TR-Ts
-1°C > TR-Ts > -2°C
=
When the room
temperature rises
When the room
temperature drops
TR : Room temperature
Ts : Setting temperature
Lo mode
Me mode
Me+ mode
( ) model 14
( ) model 14
Содержание AOYG07LMCE
Страница 4: ...2016 11 21 3 OUTDOOR UNIT 15 663 mm 20 293 mm 68 454 mm 535 mm ...
Страница 21: ...1611G4556 ...
Страница 24: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 46: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Страница 52: ...3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...