![Fujitsu AOYG07KMTA Скачать руководство пользователя страница 48](http://html.mh-extra.com/html/fujitsu/aoyg07kmta/aoyg07kmta_design-and-technical-manual_2344218048.webp)
Multiple outdoor unit installation
• Provide at least 250 mm of space between the outdoor units if multiple units are installed.
• When routing the piping from the side of an outdoor unit, provide space for piping.
• No more than 3 units must be installed side by side.
When 3 units or more are arranged in a line, provide the space as shown in the following
example “
When an obstruction in the upper space:
”.
•
When the upper space is open:
Unit: mm
Obstacles at rear only
Obstacles at front only
200 or more
250 or more
1,000 or more
250 or more
Obstacles at front and rear
200 or more
1,000 or more
250 or more
•
When an obstruction in the upper space:
Unit: mm
Obstacles at rear and above.
1,500 or more
200 or more
250 or more
250 or more
Max. 300
1,500 or more
DESIGN & TECHNICAL MANUAL
- 44 -
OUTDOOR UNIT
AOYG07-14KMTA
Содержание AOYG07KMTA