2) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the esti-
mated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function number
Setting value
Setting description
Factory setting
11
00
Standard (400 hours)
01
Long interval (1,000 hours)
02
Short interval (200 hours)
03
No indication
♦
3) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufac-
turer’s recommended value).
Function number
Setting value
Setting description
Factory
setting
30
(For cooling)
31
(For heating)
00
Standard setting
♦
01
No correction 0.0 °C
02
-0.5 °C
More cooling
Less heating
03
-1.0 °C
04
-1.5 °C
05
-2.0 °C
06
-2.5 °C
07
-3.0 °C
08
-3.5 °C
09
-4.0 °C
10
+0.5 °C
Less cooling
More heating
11
+1.0 °C
12
+1.5 °C
13
+2.0 °C
14
+2.5 °C
15
+3.0 °C
16
+3.5 °C
17
+4.0 °C
DESIGN & TECHNICAL MANUAL
- 32 -
WALL MOUNTED
ASYG07-14KMTA
Содержание AOYG07KMTA
Страница 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASYG07KMTA ASYG09KMTA ASYG12KMTA ASYG14KMTA ...
Страница 10: ...3 Wiring diagrams 3 1 Models ASYG07KMTA ASYG09KMTA ASYG12KMTA and ASYG14KMTA 6 WALL MOUNTED ASYG07 14KMTA ...
Страница 42: ... 38 WALL MOUNTED ASYG07 14KMTA ...
Страница 43: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG07KMTA AOYG09KMTA AOYG12KMTA AOYG14KMTA ...
Страница 52: ...5 Wiring diagrams 5 1 Models AOYG07KMTA AOYG09KMTA AOYG12KMTA and AOYG14KMTA 48 OUTDOOR UNIT AOYG07 14KMTA ...