![Fujitsu AOYG07KMTA Скачать руководство пользователя страница 35](http://html.mh-extra.com/html/fujitsu/aoyg07kmta/aoyg07kmta_design-and-technical-manual_2344218035.webp)
¢
Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ-
ment.
NOTE:
Setting will not be changed if invalid numbers or setting values are selected.
Function setting list
Function no.
Functions
1)
00
Remote controller address setting
2)
11
Filter sign
3)
30/31
Room temperature control for indoor unit sensor
4)
35/36
Room temperature control for wired remote controller sensor
5)
40
Auto restart
6)
42
Room temperature sensor switching
7)
44
Remote controller custom code
8)
46
External input control
9)
48
Room temperature sensor switching (Aux.)
10)
49
Indoor unit fan control for energy saving for cooling
1) Remote controller address setting
NOTE:
This setting is configurable only by wireless remote controller, but not configurable by
Polar 3-wired remote controller.
Multiple indoor units can be operated by using one wired remote controller.
Set the unit number of each indoor unit.
Function number
Setting value
Setting description
Factory setting
00
00
Unit no. 0
♦
01
Unit no. 1
02
Unit no. 2
03
Unit no. 3
04
Unit no. 4
05
Unit no. 5
06
Unit no. 6
07
Unit no. 7
08
Unit no. 8
09
Unit no. 9
10
Unit no. 10
11
Unit no. 11
12
Unit no. 12
13
Unit no. 13
14
Unit no. 14
15
Unit no. 15
NOTES:
• When connecting Polar 3-wired remote controller, set the remote controller address in the or-
der of 0, 1, 2, ....., and 15.
• When different type of indoor units (such as wall mounted type and cassette type, cassette
type and duct type, or other combinations) are connected using group control system, some
functions may no longer be available.
- 31 -
WALL MOUNTED
ASYG07-14KMTA
Содержание AOYG07KMTA
Страница 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASYG07KMTA ASYG09KMTA ASYG12KMTA ASYG14KMTA ...
Страница 10: ...3 Wiring diagrams 3 1 Models ASYG07KMTA ASYG09KMTA ASYG12KMTA and ASYG14KMTA 6 WALL MOUNTED ASYG07 14KMTA ...
Страница 42: ... 38 WALL MOUNTED ASYG07 14KMTA ...
Страница 43: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG07KMTA AOYG09KMTA AOYG12KMTA AOYG14KMTA ...
Страница 52: ...5 Wiring diagrams 5 1 Models AOYG07KMTA AOYG09KMTA AOYG12KMTA and AOYG14KMTA 48 OUTDOOR UNIT AOYG07 14KMTA ...