DANGER
This part (Choke coil) generates high voltages.
Never touch this part.
SPECIAL INSTALLATION SETTING
PUMP DOWN (Refrigerant collecting operation)
Perform the following procedures to collect the refrigerant when moving
the indoor unit or the outdoor unit.
(1) Press the push-button switch on the circuit board once.
The LED on the circuit board starts flashing (one second ON/one se-cond
OFF). This indicates the start of PUMP DOWN operation.
When the switch is pressed while the compressor is in operation, PUMP
DOWN operation starts automatically.
When the switch is pressed while the compressor is in stop, the com-pressor
starts to operate automatically, and then move on to PUMP
DOWN operation.
(2) PUMP DOWN operation continues for about 1 minute. When PUMP
DOWN operation is completed, the compressor stops automatically.
Then close the 2-way valve and 3-way valve immediately.
(3) Turn the power off.
ERROR CONTENTS
(outdoor unit)
1. Make a TEST RUN in accordance with the
installation instruction sheet for the indoor unit.
2. OUTDOOR UNIT LEDS
When a malfunction occurs in the outdoor unit, the LED on the circuit
board lights to indicate the error. Refer to the following table for the de-
scription of each error according to the LED.
CAUTION
Always turn on the power 12 hours prior to the start of the
operation in order to ensure compressor protection
LED
FLASH (0.1sec ON/0.1sec OFF)
FLASH (0.5sec ON/0.5sec OFF)
FLASH (2sec ON/2sec OFF)
FLASH (5sec ON/5sec OFF)
FLASH (0.1sec ON/2sec OFF)
FLASH (5sec ON/0.1sec OFF)
Lighting
ERROR CONTENTS
Temperature sensor error
IPM protection
Current trans. error
Outdoor fan error
Compressor rotor position cannot
be detected
ACTPM error
Overheat discharge temperature
protection
PUMP DOWN SW
2006.08.21
13
Содержание AOY30LNAWL
Страница 4: ... Unit mm OUTDOOR UNIT 77 900 830 21 9 400 330 31 12 196 147 170 99 370 650 Air Flow 2006 08 21 3 ...
Страница 16: ...56 55 108 41 150 67 138 164 INDOOR UNIT 2006 08 21 15 ...
Страница 17: ...816 817 287 236 553 288 287 875 INDOOR UNIT 2006 08 21 16 ...
Страница 18: ...6 11 7 5 2 4 3 1 OUTDOOR UNIT 2006 08 21 17 ...
Страница 19: ...9 8 10 13 15 OUTDOOR UNIT 2006 08 21 18 ...
Страница 20: ...24 21 27 25 12 28 17 18 26 20 19 29 23 22 26 OUTDOOR UNIT 2006 08 21 19 ...
Страница 26: ...0608G3120 ...