CAUTION

For the air conditioner to operate satisfactorily, install it as outlined in this installation 

manual.

Connect the indoor unit and outdoor unit with the air conditioner piping and cables 

available standards parts.This installation manual describes the correct connections 

using the installation set available from our standard parts.

Installation work must be performed in accordance with national wiring standards by 

authorized personnel only.

Do not use an extension cable.
Do not turn on the power until all installation work is complete.
Do not purge the air with refrigerants but use a vacuum pump to vacuum the 

installation.

There is not extra refrigerant in the outdoor unit for air purging.
Use a vacuum pump for R410A exclusively.

Using the same vacuum pump for different refrigerants may damage the vacuum 

pump or the unit.

Use a clean gauge manifold and charging hose for R410A exclusively.
If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant 

comes in contact with a flame, it produces a toxic gas.
After a long period of disuse in an environment 32 °F (0 °C) or lower, supply power to 

the unit at least 12 hours before re-starting the unit.

• 

Be careful not to scratch the air conditioner when handling it.

•  All Fujitsu General products are manufactured to metric units and tolerances. 

United States customary units are provided for reference only. In cases where exact 

dimensions and tolerances are required, always refer to metric units.

2.  ABOUT THE PRODUCT

2. 1.  Precautions for using R410A refrigerant

 

WARNING

The basic installation work procedures are the same as conventional refrigerant 

models.

However, pay careful attention to the following points:

Since the working pressure is 1.6 times higher than that of conventional refrigerant 

(R22) models, some of the piping and installation and service tools are special. (See 

the table below.)

Especially,  when  replacing  a  conventional  refrigerant  (R22)  model  with  a  new 

refrigerant R410A model, always replace the conventional piping and flare nuts with 

the R410A piping and flare nuts.

Models that use refrigerant R410A have a different charging port thread diameter 

to prevent erroneous charging with conventional refrigerant (R22) and for safety. 

Therefore, check beforehand. [The charging port thread diameter for R410A is 

 

1/2-20 UNF.]

Be careful that foreign matter (oil, water, etc.) does not enter the piping than with 

refrigerant models. Also, when storing the piping, securely seal the openings by 

pinching, taping, etc.

When charging the refrigerant, take into account the slight change in the composition 

of the gas and liquid phases, and always charge from the liquid phase side whose 

composition is stable.

2. 2.  Special tools for R410A refrigerant

Tool name

Contents of change

Gauge manifold

Pressure is high and cannot be measured with a conventional 

gauge. To prevent erroneous mixing of other refrigerants, the 

diameter of each port has been changed.

It is recommended the gauge with seals 30 in. Hg to 769 psi 

(-0.1 to 5.3 MPa) for high pressure. 30 in. Hg to 551 psi (-0.1 to 

3.8 MPa) for low pressure.

Charge hose

To increase pressure resistance, the hose material and base 

size were changed.

Vacuum pump

A conventional vacuum pump can be used by installing a 

vacuum pump adapter.

Gas leakage 

detector

Special gas leakage detector for HFC refrigerant R410A.

Copper pipes

It is necessary to use seamless copper pipes and it is desirable that the amount of residual 

oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or 

discolored portion (especially on the interior surface). Otherwise, the expansion valve or 

capillary tube may become blocked with contaminants.

As an air conditioner using R410A incurs pressure higher than when using conventional 

refrigerant, it is necessary to choose adequate materials. 

Thicknesses of copper pipes used with R410A are as shown in the table. Never use 

copper pipes thinner than that in the table even when it is available on the market.

Thicknesses of Annealed Copper Pipes (R410A)

Pipe outside diameter [in. (mm)]

Thickness [in. (mm)] 

1/4 (6.35)

0.032 (0.80)

3/8 (9.52)

0.032 (0.80)

1/2 (12.70)

0.032 (0.80)

5/8 (15.88)

0.039 (1.00)

3/4 (19.05)

0.047 (1.20)

2. 3.  Accessories

 

WARNING

For installation purposes, be sure to use the parts supplied by the manufacturer or 

other prescribed parts. The use of non-prescribed parts can cause serious accidents 

such as the unit falling, water leakage, electric shock, or fire.

Do not throw away the connecting parts until the installation has been complete.

Name and shape

Q’ty

Application

Installation  

manual

1

(This book)

Drain cap

5

For outdoor unit drain piping work 

[36 type only]

Drain pipe

1

Adapter assy

 1/2 in.    →   3/8 in.

(12.70 mm)   (9.52 mm)

1

For use when connecting indoor unit 

models [7 to 12 type] to outdoor port A

[24, 36 type only]

Adapter assy

 1/2 in.    →   5/8 in.

(12.70 mm)   (15.88 mm)

1

For use when connecting indoor unit 

models [24 type] to outdoor port A

[36 type only]

2. 4. 

System configuration

Layout example for the indoor units and outdoor unit

OUTDOOR UNIT : 36 type

a

b

c

d

H1

H1

H2

Power source

208/230 V ~ 60 Hz

Power supply cable

Connection cable

Refrigerant pipe

OUTDOOR UNIT

INDOOR UNITS

UNIT D

7-12

UNIT C

7-12

UNIT B

7-12

UNIT A

7-24

9374747153_IM.indb   2

2014/12/19   14:57:14

Содержание AOU36RLXFZ1

Страница 1: ...Español En 1 AIR CONDITIONER OUTDOOR UNIT PART No 9374747153 INSTALLATION MANUAL For authorized personnel only MANUEL D INSTALLATION Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado ...

Страница 2: ...oil or equivalent used for the outdoor unit to the matching surfaces of the flare and union tubes before connecting them then tighten the nut with a torque wrench for a leak free connection Check carefully for leaks before starting the test run NOTE Depending on the system type liquid and gas lines may be either narrow or wide Therefore to avoid confusion the refrigerant tubing for your particular...

Страница 3: ...ing taping etc When charging the refrigerant take into account the slight change in the composition of the gas and liquid phases and always charge from the liquid phase side whose composition is stable 2 2 Special tools for R410A refrigerant Tool name Contents of change Gauge manifold Pressure is high and cannot be measured with a conventional gauge To prevent erroneous mixing of other refrigerant...

Страница 4: ... 9 52 7 12 C 1 4 6 35 3 8 9 52 7 12 B 1 4 6 35 3 8 9 52 7 12 A 1 4 6 35 1 2 12 70 7 12 1 15 18 24 2 1 2 When connecting models 7 12 to the outdoor unit the included adapter is neces sary For more information refer to 4 1 3 How to use adapter Port D ø1 4 in ø3 8 in ø6 35 mm ø9 52 mm Port C ø1 4 in ø3 8 in ø6 35 mm ø9 52 mm Port B ø1 4 in ø3 8 in ø6 35 mm ø9 52 mm Port A ø1 4 in ø1 2 in ø6 35 mm ø12...

Страница 5: ... unit and each indoor unit H1 49 ft 15 m Max height difference between indoor units H2 33 ft 10 m Min length for each indoor unit a b or c 16 ft 5 m Total min length a b c 49 ft 15 m 1 If the total piping is longer than 98 ft 30 m additional refrigerant charging is neces sary For more information refer to 6 2 Additional charging OUTDOOR UNIT 18 type a b H1 H1 H2 UNIT B 7 12 OUTDOOR UNIT INDOOR UNI...

Страница 6: ... cable at least 40 in 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 40 in 1 m apart you could still receive noise under some signal conditions Branch switch and circuit breaker Branch switch and circuit breaker 40 in 1 m or more 40 in 1 m or more If children under 10 years old may approa...

Страница 7: ...rain as much as possible 9 Install the unit where connection to the indoor unit is easy 3 3 1 Single outdoor unit installation When the upward area is open When there are obstacles at the back side 4 in 100 m m or m ore When there are obstacles at the back and front sides AIR 4 in 100 m m or m ore 24 in 600 mm or more 3 2 Drain installation 36 type only CAUTION Perform drain work in accordance wit...

Страница 8: ...g on the installation conditions the outdoor unit may spread its vibration during operation which may cause noise and vibration Therefore attach damping materials such as damping pads to the outdoor unit during installation Install the foundation making sure that there is enough space for installing the connection pipes Secure the unit to a solid block using foundation bolts Use 4 sets of commerci...

Страница 9: ...bent repeatedly at the same place it will break If pipes are shaped by hand be careful not to collapse them Do not bend the pipes at an angle of more than 90 When pipes are repeatedly bent or stretched the material will harden making it difficult to bend or stretch them any more Do not bend or stretch the pipes more than 3 times 4 1 2 Pipe connection CAUTION Be sure to install the pipe against the...

Страница 10: ...ning of ground fault device When the electrical switchboard is installed outdoors place it under lock and key so that it is not easily accessible Do not fasten the power supply cable and connection cable together Always keep to the maximum length of the connection cable Exceeding the maximum length may lead to erroneous operation The static electricity that is charged to the human body can damage ...

Страница 11: ...ine Grounding line Power supply line Single phase 208 230 V 18 type 1 2 3 1 2 3 G G G G 1 2 3 1 L1 2 3 L2 G INDOOR UNIT OUTDOOR UNIT INDOOR UNIT A INDOOR UNIT B TERMINAL TERMINAL UNIT A UNIT B TERMINAL DISCONNECT SWITCH Locally purchased Inter unit Power lines Grounding line 208 230 V 208 230 V 208 230 V 208 230 V 208 230 V 208 230 V Power supply line Single phase 208 230 V DISCONNECT SWITCH Local...

Страница 12: ...UNIT A connection cable 24 type Power supply cable UNIT C connection cable UNIT B connection cable UNIT A connection cable 18 type Power supply cable UNIT B connection cable UNIT A connection cable 5 Be sure to seal the holes when applying the putty Place the cables side by side Do not overlap the cables 6 Put the service cover and valve cover back after completion of the work ...

Страница 13: ... way valve 3 Open the valve of the gauge manifold fully 4 Operate the vacuum pump and start pump down 5 Check that the compound pressure gauge reads 0 1 MPa 500 microns operate the vacuum pump for 30 minutes or more in each valve 6 At the end of pump down close the valve of the gauge manifold fully and stop the vacuum pump It checks that leave as it is for about 10 minutes and a needle does not re...

Страница 14: ...setting Factory setting To set the Base heater forced off function set the DIP switch as follows 9 TEST RUN The test run method may be different for each indoor unit that is connected Refer to the installation instruction sheet included with each indoor unit CAUTION Always turn on the power 12 hours prior to the start of the operation in order to ensure compressor protection 1 Indoor unit 1 Is ope...

Страница 15: ... lamp and timer indicator lamp will begin to flash simultaneously during test run When using the MANUAL AUTO button of the indoor unit The remote control unit is lost and so on Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds The forced cooling operation cannot start if the MANUAL AUTO button is not kept on pressing for more than 10 seconds 4 Close the valve stem...

Отзывы: