4. 1. 3.  How to use adapter (Connection ports of outdoor unit)

•  When using the ADAPTER, be careful not to overtighten the nut, or the smaller pipe 

may be damaged.

• 

Apply a coat of refrigeration oil to the threaded connection port of the outdoor unit 

where the flare nut comes in.

• 

Use appropriate wrenches to avoid damaging the connection thread by 

overtightening the flare nut.

•  Apply wrenches on both of flare nut (local part), and ADAPTER to tighten them.

Adapter tightening torque

Adapter type [in. (mm)]

Tightening torque [lbf·ft. (N·m)]

ø1/2 (ø12.70) → ø3/8 (ø9.52)

36.1 to 45.0 (49 to 61)

ø1/2 (ø12.70) → ø5/8 (ø15.88)

36.1 to 45.0 (49 to 61)

5.  ELECTRICAL WIRING

 

WARNING

Wiring connections must be performed by a qualified person in accordance with 

specifications.

The rated supply of this product is 60Hz, 208/230V. Use a voltage within the range of 

187-253V.
Before connecting the wires, make sure the power supply is OFF.
When installing this system in high humidity locations, install using ground fault 

equipment breakers (often referred to in other countries as an ELCB [earth leakage 

current breaker]) to reduce the risk of leaking current which may result in electric 

shock or potential fire.
Be sure to install a breaker of the specified capacity. 

When selecting breaker, please comply with the laws and the regulations of each 

country. 

One breaker must be installed on the power supply of the outdoor unit.

Wrong selection and setup of the breaker will cause electric shock or fire.
Do not connect AC power supply to the transmission line terminal board.

Improper wiring can damage the entire system.

Connect the connector cord securely to the terminal.

Faulty installation can cause a fire.
Make sure to secure the insulation portion of the connector cable with the cord clamp. 

A damaged insulation can cause a short circuit.
Never install a power factor improvement condenser. Instead of improving the power 

factor, the condenser may overheat.

Before servicing the unit, turn the power supply switch OFF. Then, do not touch 

electric parts for 10 minutes due to the risk of electric shock.
Make sure to perform grounding work. Improper grounding work can cause electric 

shocks.

 

CAUTION

The primary power supply capacity is for the air conditioner itself, and does not include 

the concurrent use of other devices.

Do not use crossover power supply wiring for the outdoor unit.

If the electrical power is inadequate, contact your electric power company.

Install a breaker in a location that is not exposed to high temperatures.

If the temperature surrounding the breaker is too high, the amperage at which the 

breaker cuts out may decrease.
We suggest installing GFEB [Ground Fault Equipment Breaker] or follow local 

electrical code.

This system uses an inverter, which means that when used with a ground fault breaker 

you must use breakers that can handle harmonics such as a GFEB (30 mA or greater) 

in order to prevent malfunctioning of ground fault device.

When the electrical switchboard is installed outdoors, place it under lock and key so 

that it is not easily accessible.

Do not fasten the power supply cable and connection cable together.
Always keep to the maximum length of the connection cable. Exceeding the maximum 

length may lead to erroneous operation.

The static electricity that is charged to the human body can damage the control PC 

Board when handling the control PC Board for address setting, etc.

Please keep caution to the following points.

Provide the grounding of Indoor unit, Outdoor unit and Option equipment.

Cut off the power supply (breaker).

Touch the metal section (such as the unpainted control box section) of the indoor or 

outdoor unit for more than 10 seconds. Discharge the static electricity in your body.

Never touch the component terminal or pattern on the PC Board.

5. 1.  Electrical requirement

 

CAUTION

Be sure to install a breaker of the specified capacity.
Regulation of cables and breaker differs from each locality, refer in accordance with 

local rules.

Voltage rating

1Φ 208/230V (60Hz)

Operating range

187-264V

Cable

Conduit cable size 

*1)

Remarks

Power supply cable

36/24 type  10AWG

2 cable + Ground, 1 Ø 208/230V

18 type       12AWG

Connection cable

14AWG

3 cable + Ground, 1 Ø 208/230V

1) Selected sample: Select the correct cable type and size according to the country or 

region’s regulations.

Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the

wire diameter when the wire length is long.

Breaker

Specification

 *

2)

Circuit breaker

36/24 type  Current : 30(A)
18 type 

Current : 20(A)

Earth leakage breaker

Leakage current : 30mA 0.1sec or less *

3)

2) Select the appropriate breaker of the described specification according to the national 

or regional standards.

3) Select the breaker that enough load current can pass through it.

5. 2.  Unit wiring

•  When stripping off the coating of a lead wire, always use a special tool such as a wire 

stripper. If there is no special tool available, carefully strip the coating with a knife etc.

1-3/16 in. (30 mm)

1-15/16 in.(50 mm)

Earth wire

Power supply cable

and connection cable

How to connect wiring to the terminal
Caution when wiring cable

(1)  Use ring type terminals with insulating sleeves as shown in the figure to connect to 

the terminal block.

(2)  Securely clamp the ring type terminals to the wires using an appropriate tool so that 

the wires do not come loose.

(3)  Use the specified wires, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws. Do not use a 

screwdriver that is too small, otherwise, the screw heads may be damaged and 

prevent the screws from being properly tightened.

(5)  Do not tighten the terminal screws too much, otherwise, the screws may break.
(6)  See the table below for the terminal screw tightening torques.

Sleeve

Strip : 3/8 in. (10 mm)

Ring type terminal

Wire

Screw with special washer

Ring type terminal

Terminal blocks

Screw with special washer 

Wire

Ring type terminal

Tightening torque [lbf·in. (N·m)]

M4 screw

10.6 to 15.9 (1.2 to 1.8)

9374747153_IM.indb   9

2014/12/19   14:57:18

Содержание AOU36RLXFZ1

Страница 1: ...Español En 1 AIR CONDITIONER OUTDOOR UNIT PART No 9374747153 INSTALLATION MANUAL For authorized personnel only MANUEL D INSTALLATION Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado ...

Страница 2: ...oil or equivalent used for the outdoor unit to the matching surfaces of the flare and union tubes before connecting them then tighten the nut with a torque wrench for a leak free connection Check carefully for leaks before starting the test run NOTE Depending on the system type liquid and gas lines may be either narrow or wide Therefore to avoid confusion the refrigerant tubing for your particular...

Страница 3: ...ing taping etc When charging the refrigerant take into account the slight change in the composition of the gas and liquid phases and always charge from the liquid phase side whose composition is stable 2 2 Special tools for R410A refrigerant Tool name Contents of change Gauge manifold Pressure is high and cannot be measured with a conventional gauge To prevent erroneous mixing of other refrigerant...

Страница 4: ... 9 52 7 12 C 1 4 6 35 3 8 9 52 7 12 B 1 4 6 35 3 8 9 52 7 12 A 1 4 6 35 1 2 12 70 7 12 1 15 18 24 2 1 2 When connecting models 7 12 to the outdoor unit the included adapter is neces sary For more information refer to 4 1 3 How to use adapter Port D ø1 4 in ø3 8 in ø6 35 mm ø9 52 mm Port C ø1 4 in ø3 8 in ø6 35 mm ø9 52 mm Port B ø1 4 in ø3 8 in ø6 35 mm ø9 52 mm Port A ø1 4 in ø1 2 in ø6 35 mm ø12...

Страница 5: ... unit and each indoor unit H1 49 ft 15 m Max height difference between indoor units H2 33 ft 10 m Min length for each indoor unit a b or c 16 ft 5 m Total min length a b c 49 ft 15 m 1 If the total piping is longer than 98 ft 30 m additional refrigerant charging is neces sary For more information refer to 6 2 Additional charging OUTDOOR UNIT 18 type a b H1 H1 H2 UNIT B 7 12 OUTDOOR UNIT INDOOR UNI...

Страница 6: ... cable at least 40 in 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 40 in 1 m apart you could still receive noise under some signal conditions Branch switch and circuit breaker Branch switch and circuit breaker 40 in 1 m or more 40 in 1 m or more If children under 10 years old may approa...

Страница 7: ...rain as much as possible 9 Install the unit where connection to the indoor unit is easy 3 3 1 Single outdoor unit installation When the upward area is open When there are obstacles at the back side 4 in 100 m m or m ore When there are obstacles at the back and front sides AIR 4 in 100 m m or m ore 24 in 600 mm or more 3 2 Drain installation 36 type only CAUTION Perform drain work in accordance wit...

Страница 8: ...g on the installation conditions the outdoor unit may spread its vibration during operation which may cause noise and vibration Therefore attach damping materials such as damping pads to the outdoor unit during installation Install the foundation making sure that there is enough space for installing the connection pipes Secure the unit to a solid block using foundation bolts Use 4 sets of commerci...

Страница 9: ...bent repeatedly at the same place it will break If pipes are shaped by hand be careful not to collapse them Do not bend the pipes at an angle of more than 90 When pipes are repeatedly bent or stretched the material will harden making it difficult to bend or stretch them any more Do not bend or stretch the pipes more than 3 times 4 1 2 Pipe connection CAUTION Be sure to install the pipe against the...

Страница 10: ...ning of ground fault device When the electrical switchboard is installed outdoors place it under lock and key so that it is not easily accessible Do not fasten the power supply cable and connection cable together Always keep to the maximum length of the connection cable Exceeding the maximum length may lead to erroneous operation The static electricity that is charged to the human body can damage ...

Страница 11: ...ine Grounding line Power supply line Single phase 208 230 V 18 type 1 2 3 1 2 3 G G G G 1 2 3 1 L1 2 3 L2 G INDOOR UNIT OUTDOOR UNIT INDOOR UNIT A INDOOR UNIT B TERMINAL TERMINAL UNIT A UNIT B TERMINAL DISCONNECT SWITCH Locally purchased Inter unit Power lines Grounding line 208 230 V 208 230 V 208 230 V 208 230 V 208 230 V 208 230 V Power supply line Single phase 208 230 V DISCONNECT SWITCH Local...

Страница 12: ...UNIT A connection cable 24 type Power supply cable UNIT C connection cable UNIT B connection cable UNIT A connection cable 18 type Power supply cable UNIT B connection cable UNIT A connection cable 5 Be sure to seal the holes when applying the putty Place the cables side by side Do not overlap the cables 6 Put the service cover and valve cover back after completion of the work ...

Страница 13: ... way valve 3 Open the valve of the gauge manifold fully 4 Operate the vacuum pump and start pump down 5 Check that the compound pressure gauge reads 0 1 MPa 500 microns operate the vacuum pump for 30 minutes or more in each valve 6 At the end of pump down close the valve of the gauge manifold fully and stop the vacuum pump It checks that leave as it is for about 10 minutes and a needle does not re...

Страница 14: ...setting Factory setting To set the Base heater forced off function set the DIP switch as follows 9 TEST RUN The test run method may be different for each indoor unit that is connected Refer to the installation instruction sheet included with each indoor unit CAUTION Always turn on the power 12 hours prior to the start of the operation in order to ensure compressor protection 1 Indoor unit 1 Is ope...

Страница 15: ... lamp and timer indicator lamp will begin to flash simultaneously during test run When using the MANUAL AUTO button of the indoor unit The remote control unit is lost and so on Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds The forced cooling operation cannot start if the MANUAL AUTO button is not kept on pressing for more than 10 seconds 4 Close the valve stem...

Отзывы: