ADDITIONAL CHARGE CALCULATION
9.
MODEL : AOTG54LC
Refrigerant type
R410A
Refrigerant amount
g
3,450
IF ADDITIONAL REFRIGERANT IS REQUIRED
When the piping is longer than pre-charge length, additional charging is necessary.
•
For the additional amount, see the table below.
•
Additional charging amount
•I.U.: Indoor unit
•L1: Max. piping length
•H1: Max. height difference
< Indoor unit to outdoor unit >
H1
L1
I.U.
L1 >
Pre-charge length
Refrigerant pipe size
[mm(in.)]
Additional charging amount [g]
Rate
[g/m]
St
an
da
rd
Piping length
30 m or less 40 m 50 m 60 m 70 m
Liquid 9.52 (3/8)
None
500 1,000 1,500 2,000
50
Gas
15.88 (5/8)
Si
ze u
p
Piping length
30 m or less 40 m 50 m
50
Liquid 9.52 (3/8)
None
500 1,000
Gas
19.05 (3/4)
Piping length
15 m or less 25 m 35 m
100
Liquid 12.70 (1/2)
None
1,000 2,000
Gas
15.88 (5/8)
19.05 (3/4)
Содержание AOTG54LCTL
Страница 1: ...DESIGN TECHNICAL MANUAL INDOOR OUTDOOR AOTG54LCTL ARTG54LHTC AIR CONDITIONER Duct type ...
Страница 2: ...1 INDOOR UNIT DTR_AR056E_05 2016 04 27 DUCT TYPE ARTG54LHTC ...
Страница 14: ... 01 11 DUCT TYPE ARTG54LHTC DUCT TYPE ARTG54LHTC DIMENSIONS 444 MODEL ARTG54LH Unit mm ...
Страница 16: ... 01 13 DUCT TYPE ARTG54LHTC DUCT TYPE ARTG54LHTC WIRING DIAGRAMS 555 MODEL ARTG54LH ...
Страница 41: ...SINGLE TYPE AOTG54LCTL 2 OUTDOOR UNIT DTR_AO114E_04 2016 04 27 ...
Страница 49: ... 02 07 OUTDOOR UNIT AOTG54LCTL OUTDOOR UNIT AOTG54LCTL REFRIGERANT CIRCUIT 555 MODEL AOTG54LC ...
Страница 50: ... 02 08 OUTDOOR UNIT AOTG54LCTL OUTDOOR UNIT AOTG54LCTL WIRING DIAGRAMS 666 MODEL AOTG54LC ...