6. Room temperature sensor switching function
• (Only for wired remote controller)
When using the Wired remote controller temperature sensor, change the setting to "Both" (01).
(
. . .Factory setting)
Setting description
Function number
Setting value
Indoor unit
42
00
Both
01
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
*Remote controller sensor must be turned on by using the remote controller.
7. Cold air prevention
• This setting is to disable the cold air prevention function during heating operation. When disabled, the fan setting will always follow the
setting on the remote controller. (Excluding defrost mode)
(
. . .Factory setting)
Setting description
Function number
Setting value
Enable
43
00
Disable
01
8. External input control
• "Operation/Stop" mode or "Forced stop" mode can be selected.
(
. . .Factory setting)
Setting description
Function number
Setting value
Operation/Stop mode
46
00
(Setting prohibited)
01
Forced stop mode
02
9. Room temperature sensor switching (Aux.)
• To use the temperature sensor on the wired remote controller only, change the setting to "Wired remote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01).
(
. . .Factory setting)
Setting description
Function number
Setting value
Both
48
00
Wired remote controller
01
Содержание AOTG54LCTL
Страница 1: ...DESIGN TECHNICAL MANUAL INDOOR OUTDOOR AOTG54LCTL ARTG54LHTC AIR CONDITIONER Duct type ...
Страница 2: ...1 INDOOR UNIT DTR_AR056E_05 2016 04 27 DUCT TYPE ARTG54LHTC ...
Страница 14: ... 01 11 DUCT TYPE ARTG54LHTC DUCT TYPE ARTG54LHTC DIMENSIONS 444 MODEL ARTG54LH Unit mm ...
Страница 16: ... 01 13 DUCT TYPE ARTG54LHTC DUCT TYPE ARTG54LHTC WIRING DIAGRAMS 555 MODEL ARTG54LH ...
Страница 41: ...SINGLE TYPE AOTG54LCTL 2 OUTDOOR UNIT DTR_AO114E_04 2016 04 27 ...
Страница 49: ... 02 07 OUTDOOR UNIT AOTG54LCTL OUTDOOR UNIT AOTG54LCTL REFRIGERANT CIRCUIT 555 MODEL AOTG54LC ...
Страница 50: ... 02 08 OUTDOOR UNIT AOTG54LCTL OUTDOOR UNIT AOTG54LCTL WIRING DIAGRAMS 666 MODEL AOTG54LC ...