INDOOR UNIT (Setting by remote controller)
12-2.
The function settings of the control of the indoor unit can be changed by this procedure according
•
to the installation conditions. Incorrect settings can cause the indoor unit malfunction.
After the power is turned on, perform the “FUNCTION SETTING” according to the installation
•
conditions using the remote controller.
The settings may be selected between the following two: Function Number or Setting Value.
•
Settings will not be changed if invalid numbers or setting values are selected.
•
PREPARATION
Before turning on the power of the indoor unit:
•
- Confirm whether the piping air-tight test and vacuuming have been conducted.
- Reconfirm whether there is no miswiring.
Turn on the power of the indoor units.
•
FUNCTION SETTING METHOD
12-2-1.
(for AR-WDD1E (Option: UTY-RVNYN))
Setting method
z
1) When [Menu button] is pressed twice while “Monitor”
screen is displayed, it switches to the “Submenu” screen.
If [Menu button] is pressed while the “Submenu” screen is
displayed, the display returns to the “Monitor” screen.
Back:
Setting:
Date and time
Submenu
[
1/2
]
Monitor
Screen
Filter sign
R.C. sensor control
Room temp. display
Off
Off
Mo 10:00
2) Press the [Screen switch button (Left)] and [Screen switch
button (Right)] simultaneously for 5 seconds to switch to
“Service” screen.
Back Setting:
Service
Mo 10:00
Function setting
Error history
I.U.address verification
Version
Test run
3) Select [Function setting] with pressing the [Cursor button
(Up/Down)], and press the [Enter button].
Back: Setting:
Service
Mo 10:00
Function setting
Error history
I.U.address verification
Version
Test run
4) Select [R.C. address] of the target indoor unit with
pressing the [Cursor button (Up/Down)].
(R.C. Address : Remote Controller Address)
Cancel: OK:
Function setting
Mo 10:00
R.C. Function Setting
address No. No.
00
00 00
Version Error history
Содержание AOTG54LCTL
Страница 1: ...DESIGN TECHNICAL MANUAL INDOOR OUTDOOR AOTG54LCTL ARTG54LHTC AIR CONDITIONER Duct type ...
Страница 2: ...1 INDOOR UNIT DTR_AR056E_05 2016 04 27 DUCT TYPE ARTG54LHTC ...
Страница 14: ... 01 11 DUCT TYPE ARTG54LHTC DUCT TYPE ARTG54LHTC DIMENSIONS 444 MODEL ARTG54LH Unit mm ...
Страница 16: ... 01 13 DUCT TYPE ARTG54LHTC DUCT TYPE ARTG54LHTC WIRING DIAGRAMS 555 MODEL ARTG54LH ...
Страница 41: ...SINGLE TYPE AOTG54LCTL 2 OUTDOOR UNIT DTR_AO114E_04 2016 04 27 ...
Страница 49: ... 02 07 OUTDOOR UNIT AOTG54LCTL OUTDOOR UNIT AOTG54LCTL REFRIGERANT CIRCUIT 555 MODEL AOTG54LC ...
Страница 50: ... 02 08 OUTDOOR UNIT AOTG54LCTL OUTDOOR UNIT AOTG54LCTL WIRING DIAGRAMS 666 MODEL AOTG54LC ...