![Fujitsu AOHG07KGCA Скачать руководство пользователя страница 69](http://html.mh-extra.com/html/fujitsu/aohg07kgca/aohg07kgca_service-manual_2344036069.webp)
Check point 3. Check the solenoid coil and 4-way valve
NOTE:
Refer solenoid coil and 4-way valve in
•
Solenoid coil
Remove P60 from PCB and check the resistance value of coil. Resistance value is 2.780 kΩ (at
20 °C).
If it is open or abnormal resistance value, replace solenoid coil.
•
4-way valve
Check each piping temperature, and the location of the valve by the temperature difference.
If the value location is not proper, replace 4-way valve.
Check point 4. Replace main PCB
If Check Point 1 to 4 do not improve the symptom, replace main PCB.
End