External input and output PCB
The indoor unit Operation/Stop can be set by using the input connector on the PCB.
•
Input select
Use either one of these types of connectors according to the application. (Both types of connec-
tors cannot be used simultaneously.)
–
Dry contact
In case of internal power supply, set the slide switch of S→301 to "NON VOL" side.
1
2
3
Input 1
PCB
Connected device
*
+
-
1
2
3
Input 2
*
+
-
CN313
CN314
*1: The switches can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
–
Apply voltage
In case of external power supply, set the slide switch of S→301 to "VOL" side.
1
2
3
Input 1
Power supply
PCB
Connected device
*
*
*2
+
-
1
2
3
Input 2
CN313
CN314
*1: The switches can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
*2: Make the power supply DC 12 V to 24 V, 10 mA or more.
2-1. External input
- (05-11) -
2. External input and output
FI
EL
D
W
O
R
K
IN
G
FI
EL
D
W
O
R
K
IN
G
Содержание AOHG07KGCA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 3 11 SR_CH01_AS069EG_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 3 11 SR_CH02_AS069EG_01 ...
Страница 33: ...3 TROUBLESHOOTING 2022 03 25 SR_CH03_AS069EG_01 ...
Страница 36: ......
Страница 89: ...4 CONTROL AND FUNCTIONS 2022 03 25 SR_CH04_AS069EG_01 ...
Страница 91: ...8 6 High temperature and high pressure release control heating mode 04 32 CONTENTS continued ...
Страница 92: ......
Страница 125: ...5 FILED WORKING 2022 03 25 SR_CH05_AS069EG_01 ...