PEAK CUT MODE
Operation that suppressed the current value can be performed by means of the following on-
•
site work.
The air conditioner is set to the Peak cut mode by applying the contact input of a
commercial ON/OFF switch to a connector on the outdoor control PC board.
Circuit diagram example
z
Outdoor
control PC board
Connected unit
Connector
1
2
3
Signal
Field supply
* Make the distance from the PC board to the connected unit within 10 m.
Surely insulate with
insulation tape etc. since
this wire is not used.
*10 m
Red
White
Black
Vcc
R
SW
Vcc
Power
supply
Use the following parts and construct a circuit like that shown above.
•
Input Signal∙∙∙ON : Peak cut mode/OFF : Normal operation
•
*Set the "Peak cut mode" level by "Push switch" on the outdoor control PC board.
ON
OFF
ON
OFF
Input Signal
Peak cut mode
Parts (Optional)
z
Model name
UTY-XWZXZ2
Wire (External input)
1) Power supply
●Voltage (Chart sign=Vcc) : DC 5V to 24V
●The current capacity : About 100mA
2) Switch (Chart sign=SW)
● Toggle switch or Rocker switch, etc : Switch which maintains the
states.
● Prepare switches which are enough capable for DC 10mA
current or more
3) Resistance (Chart sign=R)
●Adjust the resistance for current to about DC 10mA
(Example)
●In case of Vcc=DC 5V : Rated resistance value 470Ω 1/4W
●In case of Vcc=DC 12V : Rated resistance value 1kΩ 1/4W
●In case of Vcc=DC 24V : Rated resistance value 2.2kΩ 1/4W
Содержание AOA72LALT
Страница 2: ...1 INDOOR UNIT DTR_AR061E_03 2013 11 08 DUCT TYPE AR C72LHTA AR C90LHTA ...
Страница 12: ... 01 09 DUCT TYPE AR C72 90LHTA DUCT TYPE AR C72 90LHTA DIMENSIONS 444 MODEL AR C72LHTA Unit mm ...
Страница 13: ... 01 10 DUCT TYPE AR C72 90LHTA DUCT TYPE AR C72 90LHTA MODEL AR C90LHTA Unit mm ...
Страница 15: ... 01 12 DUCT TYPE AR C72 90LHTA DUCT TYPE AR C72 90LHTA WIRING DIAGRAMS 555 MODEL AR C72LHTA AR C90LHTA ...
Страница 39: ...SINGLE TYPE AO A72LALT AO A90LALT 2 OUTDOOR UNIT DTR_AO133E_02 2013 11 08 ...
Страница 52: ... 02 11 OUTDOOR UNIT AO A72 90LALT OUTDOOR UNIT AO A72 90LALT WIRING DIAGRAMS 555 MODEL AO A72LALT AO A90LALT ...
Страница 58: ... 02 17 OUTDOOR UNIT AO A72 90LALT OUTDOOR UNIT AO A72 90LALT SOUND LEVEL CHECK POINT 111111 Microphone 1 m 1 m ...