- (02 - 19) -
O
U
TD
O
O
R U
N
IT
AO
A
72
-9
0L
A
LT
O
U
TD
O
O
R U
N
IT
AO
A
72
-9
0L
A
LT
SAFETY DEVICES
12.
Protection form
Model
AO
A72LALT
AO
A90LALT
Circuit protection
Fuse (Main PCB)
AC400V 15A
AC250V 3.15A
Protector
(
FILTER PCB)
AC500V 25A
Indoor unit protection
Fuse
AC250V 20A
Compressor protection
Thermal protection program
(Compressor temp.)
OFF : 112°C
ON : 80°C
Thermal protection program
(Discharge temp.)
OFF : 115°C
ON : After 7 minutes
.
High pressure protection
Pressure switch
OFF : 4.2MPa
ON : 3.2MPa
Low pressure protection
Pressure sensor
OFF : 0.02MPa
ON : 0.05MPa
Fan motor protection
Thermal protection program
OFF :100
+15
°C
-10
ON : 95
+15
°C
-10
Содержание AOA72LALT
Страница 2: ...1 INDOOR UNIT DTR_AR061E_03 2013 11 08 DUCT TYPE AR C72LHTA AR C90LHTA ...
Страница 12: ... 01 09 DUCT TYPE AR C72 90LHTA DUCT TYPE AR C72 90LHTA DIMENSIONS 444 MODEL AR C72LHTA Unit mm ...
Страница 13: ... 01 10 DUCT TYPE AR C72 90LHTA DUCT TYPE AR C72 90LHTA MODEL AR C90LHTA Unit mm ...
Страница 15: ... 01 12 DUCT TYPE AR C72 90LHTA DUCT TYPE AR C72 90LHTA WIRING DIAGRAMS 555 MODEL AR C72LHTA AR C90LHTA ...
Страница 39: ...SINGLE TYPE AO A72LALT AO A90LALT 2 OUTDOOR UNIT DTR_AO133E_02 2013 11 08 ...
Страница 52: ... 02 11 OUTDOOR UNIT AO A72 90LALT OUTDOOR UNIT AO A72 90LALT WIRING DIAGRAMS 555 MODEL AO A72LALT AO A90LALT ...
Страница 58: ... 02 17 OUTDOOR UNIT AO A72 90LALT OUTDOOR UNIT AO A72 90LALT SOUND LEVEL CHECK POINT 111111 Microphone 1 m 1 m ...