Trouble shooting 17
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
OK
OK
OK
OK
Heat Ex. Liquid Outlet Thermistor Error
Outdoor unit Main PCB
Heat exchanger temperature thermistor
When Heat exchanger temperature thermistor open or
short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of connector
Check if connector is removed.
Check if connector is erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-21
7.7
5
9.7
12.4
16.1
20.9
27.5
49.2
Resistance value (k )
0
-5
-10
-20
92.3
-30
Temperature (°C )
10
15
0.9
1.3
1.8
2.6
4.0
Resistance value (k )
70
0.7
80
0.5
90
60
50
40
30
6.1
20
Temperature (°C )
Indicate or Display:
Indoor Unit :
Operation indicator: 7 time Flash
Timer indicator : 3 time Flash
BLACK
BLACK
BLACK
BLACK
Thermistor (PIPE temp.)
1
2
3
4
1
2
3
4
P1
Error code: [ E : 73 ]
Economy indicator: Continuous Flash
Содержание AO*G09KXCA Series
Страница 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Страница 28: ...2 TROUBLESHOOTING WALL MOUNTED type INVERTER ...
Страница 82: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Страница 89: ...INDOOR UNIT Main PC board Sub PC board 4 WIRING DIAGRAMS OUTDOOR UNIT 03 07 ...
Страница 90: ...4 DISASSEMBLY PROCESS WALL MOUNTED type INVERTER ...
Страница 110: ...Dec 2016 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...