01-17
Compressor OFF
Outdoor fan motor OFF
50sec. later four - way valve OFF
55sec. later compressor ON
3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time, outdoor temperature
and outdoor heat exchanger temperature as follows.
(Not defrosted for 10min.)
Heating operation start : Compressor ON
Outdoor heat exchanger temperature:
Over +16°C
or
Compressor ON time: Maximum 15min.
Defrost end
Integrating defrost
(Constant monitoring)
Defrost Indicator:
[Operation indicator]
6sec. ON
/ 2sec. OFF
Defrost start
Compressor
OFF count :
40 times
(Less than 10min.)
Normal defrost
Compressor
integrating
operation:
Over 240min.
Outdoor
heat exchanger
temperature:
Below - 3°C
Compressor
integrating
operation:
Over 215min.
Outdoor
heat exchanger
temperature:
Below - 5°C
Compressor
integrating
operation:
Over 40min.
Tn-Tn10 < - 5deg
Tn-Tnb < - 2deg
However, Tn < - 6 °C
=
Tn < - 17°C
=
Содержание AO*G09KXCA Series
Страница 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Страница 28: ...2 TROUBLESHOOTING WALL MOUNTED type INVERTER ...
Страница 82: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Страница 89: ...INDOOR UNIT Main PC board Sub PC board 4 WIRING DIAGRAMS OUTDOOR UNIT 03 07 ...
Страница 90: ...4 DISASSEMBLY PROCESS WALL MOUNTED type INVERTER ...
Страница 110: ...Dec 2016 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...