background image

En-13

*5:  Provide a DC12 to 24V power supply. 

Select a power supply capacity with an ample surplus for the connected load.

*6:  The allowable current is 30mA or less. 

Provide a load resistance such that the current becomes 30mA or less.

*7:  Polarity is [+] for pin 1 and [-] for pin 2. Connect correctly.

Do not impress a voltage exceeding 24V across pins 1-2.

A twisted pair cable (0.33mm

2

 (22AWG)) should be used. Maximum length of cable is 150m.

Use an external input and output cable with appropriate external dimension, depend-

ing on the number of cables to be installed.

Base heater terminal

6. 6. 4. 

Service parts : WIRE WITH CONNECTOR (9708642000)
This is the output signal for base heater. Output signal ON, when the outdoor tempera-
ture goes down below 2°C, and signal OFF at the outdoor temperature 4°C.

1

2

3

4

  

Voltage:  power supply 

input voltage

cable

(0.82mm

2

 (18AWG))

P.C.B.

Base heater *9

CN115 

(Black)

*8

8: Connect to pin 1 and pin 3.  No connection pin2 and pin4.

9: The allowable current is 1A or less.

FIELD SETTING

7. 

CAUTION

Discharge the static electricity from your body before setting up the DIP switches.
Never touch the terminals or the patterns on the parts that are mounted on the PC 
board.

Field setting switches

7. 1. 

Remove the service panel of the outdoor unit and the cover of the electrical component 
box to access the PC board of the outdoor unit.
PC board switches for various settings and LED displays are shown in the 

fi

 gure.

DIP switch setting

7. 2. 

List of Settings

7. 2. 1. 

SET5 must be set for the DIP switch.
Con

fi

 gure the settings before turning on the power. Settings for SET1, SET2, SET3 and 

SET4 DIP switches are factory default ones. Do not change them.

DIP Switch

Function

SET1

1-4

Forbidden

SET2

1-4

Forbidden

SET3

1-4

Forbidden

SET4

1-4

Forbidden

SET5

1-3

Forbidden

4

Terminal resistor setting

X 10

X 1

5'6

7 Segment 

display

Push button

LED lamp

POWER

LED105

LED104

REF AD

SET 1

SW101

SET 2

SW102

SET 3

SW103

SET 4

SW104

ERROR

MODE

LED101

(GREEN)

MODE

/EXIT SELECT ENTER

SW106

SW107 SW108 SW109

SW105

LED102

(RED)

Rotary switch

Outdoor unit printed circuit board

DIP switch

Terminating resistor setting

7. 2. 2. 

CAUTION

Be sure to set the terminal resistor according to speci

fi

 cations.

Set the terminal resistor for every network segment (NS).

If terminal resistor is set in multiple devices, the overall communication system may 
be damaged.
If terminal resistor is not set in a device, abnormal communication may occur.

Be sure to

• 

 set 1 terminal resistor in a network segment. You can set the terminal 

resistor at the outdoor unit or signal ampli

fi

 er.

When settin

• 

g the terminal resistor of a signal ampli

fi

 er, refer to the installation manual 

of the signal ampli

fi

 er.

When settin

• 

g multiple terminal resistors, take note of the following items.

How many network segments are there in a VRF system?

 

Where will you set the terminal resistors in a network segment? (Condition for 1 

 

segment: Total number of outdoor and indoor units and signal ampli

fi

 ers is less than 

64, or the total length of the transmission cable is less than 500m)
How many outdoor units are connected to 1 refrigerant system?

 

Con

fi

 gure the setting (DIP switch SET5) of the terminal resistor of the outdoor units as 

shown below from conditions 

1

 to 

3

.

SET5

Terminal resistor

Remarks

4

OFF

Disable

-

ON

Enable

(Factory setting)

Figure: Terminal resistor setting

NS2 (Network segment 2)

NS3 (Network segment 3)

NS4 (Network segment 4)

NS1 (Network segment 1)

(Set terminal resistor at outdoor units)

Master unit

Master unit

Master unit

Refrigerant system1

Refrigerant system2

Refrigerant system3

Terminal resistor: off

Terminal resistor: on

Terminal resister: on

About the setting of terminal resistor

Outdoor unit

Install

Do not install

:on

:off

Signal ampli

fi

 er

Rotary switch setting

7. 3. 

The rotary switch (REF AD) sets the refrigerant circuit address of the outdoor unit. Con-

fi

 gure the settings only on the master unit of a refrigerant system.

If multiple refrigerant systems are connected, set the rotary switch (REF AD) as shown 
in the table below.

Refrigerant 

circuit 

address

Rotary 
Switch 

Setting

Setting

Setting 

range

Type of switch

REF AD

×10

×1

Refrigerant 

circuit 

address

0–99

Setting 

example

63

0

0

0

1

0

1

2

0

2

REF AD × 10 REF AD × 1

Rotary Switch (REF AD × 1): Factory setting “0”
Rotary Switch (REF AD × 10): Factory setting “0”

98

9

8

99

9

9

9380545026-02_IM.indb   13

9380545026-02_IM.indb   13

19/08/2013   17:20:05

19/08/2013   17:20:05

Содержание AJHA36LALH

Страница 1: ...ΙΚΉ ΜΟΝΆΔΑ UNIDADE EXTERIOR ВНЕШНИЙ МОДУЛЬ DIŞ ÜNİTE For authorized service personnel only Nur für autorisiertes Fachpersonal Uniquement réservé aux techniciens agréés Sólo para personal de servicio autorizado A uso esclusivo del personale tecnico autorizzato Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό Apenas para técnicos de assistência autorizados Только для авторизованного обслуживающего персона...

Страница 2: ...performed electrical work can cause serious accidents such as electric shock or fire For wiring use the prescribed type of cables connect them securely making sure that there are no external forces of the cables applied to the terminal connections Improperly connected or secured cables can cause serious accidents such as over heating the terminals electric shock or fire Securely install the electr...

Страница 3: ...pe lightning rod or a telephone ground cable Improper grounding may cause electric shock Perform draining for the unit according to the Installation manual Check that the water is properly drained If the drain processing is improperly installed water may drip down from the unit wet ting the furniture Do not touch the fins with bare hands Be sure not to start or stop the operation of air conditioni...

Страница 4: ...part you could still receive noise under some signal conditions Keep the length of the piping of the indoor and outdoor units within the allowable range For maintenance purposes do not bury the piping Drain processing 3 2 CAUTION Perform drain work in accordance with this Manual and ensure that the drain water is properly drained If the drain work is not carried out correctly water may drip down f...

Страница 5: ... the upward area When the upward area is open Unit mm 1 Obstacles at rear only 300 2 Obstacles at front only 1500 or more 3 Obstacles at front and rear only 500 1500 or more When an obstruction is present also in the upward area Unit mm Obstacles at rear and above only 1500 500 Max 300 1500 3 3 3 Outdoor units installation in multi row Unit mm The following settings are not recommended in case of ...

Страница 6: ...5 Use reducer to change the diameter of connection pipe Installation the unit 3 5 Please install the outdoor unit without slant within 3 degrees Install 4 anchor bolts at the locations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base such as concrete blocks The foundation shall support the legs of the unit and have a...

Страница 7: ...g nitrogen gas it will create an oxidation film This can degrade performance or damage the parts in the unit such as the compres sor or valves Do not use flux to braze pipes If the flux is the chlorine type it will cause the pipes to corrode In addition if the flux contains fluoride it will affect the refrigerant piping system due to deterioration of refrigerant oil For brazing material use phosph...

Страница 8: ...g with R410A flare tools to achieve the specified flaring Use a thickness gauge to measure the dimension A Pipe outside diameter mm in Width across flats of Flare nut mm 6 35 1 4 17 9 52 3 8 22 12 70 1 2 26 15 88 5 8 29 19 05 3 4 36 Width across flats Bending pipes 5 4 2 CAUTION To prevent breaking of the pipe avoid sharp bends Bend the pipe with a radius of curvature of 100mm or more If the pipe ...

Страница 9: ...es Use a hexagon wrench size 4mm Opening 1 Insert the hexagon wrench into the valve shaft and turn it counterclockwise 2 Stop turning when the valve shaft can no longer be turned Open position Closing 1 Insert the hexagon wrench into the valve shaft and turn it clockwise 2 Stop turning when the valve shaft can no longer be turned Closed position Opening direction Hexagon wrench Seal blank cap inst...

Страница 10: ...urr on the edges to prevent snapping of cables It is recommended to apply rust proof paint on the edges to prevent rust Knockout holes are provided for wiring Fig A Knockout holes are provided 2 each in the same size in front lateral and rear sides Fig B Fig A Service panel Fig B Front connection Rear connection Lateral connection Selecting power supply cable and breaker 6 3 CAUTION Regulation of ...

Страница 11: ...etwork Convertor etc 1 Fig Transmission line Outdoor unit Indoor unit System Controller Touch Panel Controller Terminal resistor When AB BC BD 500m Signal Amplifier is required A B C D 2 Fig Do not use loop wiring NOTE This may lead to parts damage and erroneous operation Outdoor unit Indoor unit Signal Amplifier System Controller Touch Panel Controller Transmission line Terminal resistor Terminal...

Страница 12: ...re to connect to the terminal block 2 Securely clamp the crimp type terminals to the cables using an appropriate tool so that the cables do not come loose 3 Use the specified cables connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise the screw he...

Страница 13: ... ON Outdoor unit operation peak control Input4 CN134 Red OFF Normal operation ON Batch stop or Emergency stop operation 2 3 Input5 CN135 Orange 4 No pulse No information from electricity meter Pulse Power usage information from electricity meter The operations of each input terminal and the selection of function are set with the push button on the PC board of outdoor unit About the setting please ...

Страница 14: ...it printed circuit board DIP switch Terminating resistor setting 7 2 2 CAUTION Be sure to set the terminal resistor according to specifications Set the terminal resistor for every network segment NS If terminal resistor is set in multiple devices the overall communication system may be damaged If terminal resistor is not set in a device abnormal communication may occur Be sure to set 1 terminal re...

Страница 15: ...rbidden 2 2 0 0 Factory default 23 Forbidden 2 3 0 0 Factory default 24 Forbidden 2 4 0 0 Factory default 25 Forbidden 2 5 0 0 Factory default 26 Forbidden 2 6 0 0 Factory default 27 Forbidden 2 7 0 0 Factory default 28 Forbidden 2 8 0 0 Factory default 29 Forbidden 2 9 0 0 Factory default 30 Outdoor unit capacity save setting Level 1 stop 3 0 0 0 The capacity limit can be selected by the external...

Страница 16: ...play LED105 LED104 Flashing When F3 to F9 are displayed continue to press the SELECT button until F2 is displayed Use the MODE EXIT SELECT and ENTER buttons to configure settings according to the procedures below If no setting is made the factory default setting will be displayed Press the MODE EXIT button Press the SELECT button Press the ENTER button 2 Setting the first 2 digits 3 Setting the la...

Страница 17: ...operating manual When setting with a remote control refer to the remote control operating manual Automatic setting Check that the wiring is as shown in the figure below Operate using the outdoor master unit of each refrigerant system Wiring example for automatic address setting Fig 1 Signal amplifier wiring example 2 3 4 Indoor unit wiring example Connect the indoor and outdoor units of the same r...

Страница 18: ...re of nitrogen gas before blazing After completing the sealing test release the nitrogen gas from both valves Release the nitrogen gas slowly It may take about 10 minutes for completing the processing End 1 4 4 ﻸ ﻮ ﻮ ﻮ ﻮ ﻺ ﻶ First 2 digits Last 2 digits Press the SELECT button until 11 is displayed Press the ENTER button for more than 3 seconds Automatic address setting for indoor units The number...

Страница 19: ...nt in the liquid state If the refrigerant cylinder is equipped with a siphon it is not necessary to place the cylinder upright Check if the steel cylinder has a siphon installed or not before filling There is an indication with siphon for filling liquid on the steel cylinder Filling method for cylinder with siphon Set the cylinder vertical and fill with the liquid Liquid can be filled without turn...

Страница 20: ...Insulation Fig A TEST OPERATION 9 Indoor unit connection check 9 1 Normal operation will not be possible without performing the Indoor unit connection check Things to confirm before starting the Indoor unit 9 1 1 connection check To ensure safety check that the following work inspections and operations have been completed Check Item Check Column 1 Check that all work on the wiring connecting the o...

Страница 21: ...gerant Is the refrigerant circuit address correct Is a breaker installed at the power supply cable of outdoor unit Are the cable connected to the terminals without looseness and in accordance with the specifications Are the initial settings of the switches of the outdoor unit correctly configured Is the 3 way valve of the outdoor unit open Gas pipe and liquid pipe Is power supplied to the crank ca...

Страница 22: ...r 5 seconds Press the ENTER button for more than 3 seconds This will be displayed when the cooling operation mode is canceled This will be displayed after 5 seconds This will be displayed after 5 seconds This will be displayed when the heat ing operation mode is canceled Press the ENTER button for more than 3 seconds This will be displayed after 5 seconds Settings for stopping test run operation S...

Страница 23: ...rror permanent stop E 8 6 1 Outdoor unit discharge pressure sensor error E 8 6 3 Outdoor unit suction pressure sensor error E 8 6 4 Outdoor unit high pressure switch 1 error Outdoor unit actuator error E 9 3 1 Outdoor unit inverter compressor start up error E 9 4 1 Outdoor unit trip detection E 9 5 5 Outdoor unit compressor motor loss of synchro nization E 9 7 1 Outdoor unit fan motor 1 lock error...

Отзывы: