background image

En-12

External input and external output

6. 6. 

Terminal position

6. 6. 1. 

Base heater
(CN115:Black)

Outdoor unit 
PC board

Input 4
(CN134:Red)

Input 3
(CN133:White)

Input 2
(CN132:Green)

Input 1
(CN131:Yellow)

BASE HEATER

CN115 (BLK)

Input 5

(CN135 : 

Orange)

PULSE 
IN

CN134

CN133

CN132

CN1

35

CN1

36

CN1

37

CN131

EXT.
OUT. 1

EXT.
IN. 4

EXT.
IN. 3

EXT.
IN. 2

EXT.
IN. 1

EXT.
OUT. 2

(ORG)

(RED)

(WHT)

(GRN)

(YEL)

(BLK)

(BLU)

Output 1 
(CN136 : 
Black)

Output 2

(CN137: 
Blue)

CAUTION

Do not bundle the cable for base heater with other cables.

When connecting cable to Input2

Cable (for external input and output)

Cable tie (tightened with transmission cable)

Cable (for external input and output)

* If the outdoor unit is not installed in the wall, cover the exposed 

part of cable with a 1 mm thick or more insulation tubing.

about 550mm

External input terminal

6. 6. 2. 

Service parts : EXTERNAL INPUT WIRE A (9368777005)

Setting to low noise mode, cooling priority/heating priority selection, outdoor unit 

• 

operation peak control setting, emergency/batch stop and electricity meter pulse are 
possible from the outside.

Wiring method and speci

fi

 cations

A twisted pair cable (0.33mm

2

 (22AWG)) should be used. Maximum length of cable is 

150m.
 Use an external input and output cable with appropriate external dimension, depend-

ing on the number of cables to be installed
For each input, pin No.1 is of positive polarity and pin No.2 is of ground level.

connected unit connected unit connected unit

connected unit connected unit

Input1

CN131 

(Yellow)

Input2

CN132 

(Green)

Input3

CN133 

(White)

Input4

CN134 

(Red)

Input5

CN135 

(Orange)

P.C.B

Operation behavior

Each input terminal works as follows.

Connector

Input signal

Status

Input1
CN131 (Yellow)

OFF

Normal operation

ON

Low noise mode operation

Input2
CN132 (Green) *1

OFF

Cooling priority

ON

Heating priority

Input3
CN133 (White)

OFF

Normal operation

ON

Outdoor unit operation peak control

Input4
CN134 (Red)

OFF

Normal operation

ON

Batch stop or Emergency stop operation *2, *3

Input5
CN135 (Orange) *4

No pulse

No information from electricity meter

Pulse

Power usage information from electricity meter

The operations of each input terminal and the selection of function are set with the push button 
on the PC board of outdoor unit. About the setting, please refer to 7.4. Push button setting.

Note : 
*1:  The “external input priority mode” must be set by pressing push button on PC 

board of outdoor unit. (Refer to “7.FIELD SETTING”.)

*2:  Batch stop or Emergency stop pattern can be selected by outdoor unit PC board 

push button. (Refer to “7.FIELD SETTING”.)

*3:  The emergency stop function mounted in the J-II does not guarantee the regulations 

of each country. For this reason, suf

fi

cient checking is necessary regarding use. 

Especially, since the fact that the equipment may not be emergency-stopped in the 
case of breaking of the wiring to the external input terminals and communication 
line, communication error due to noise, VRF external input circuit trouble, etc. must 
be considered, the provision of double measures that add direct interruption of the 
power supply by switch, etc. is recommended as a precaution.

*4:  Pulse input to CN135 must be width 50ms or more, and must be interval 50ms or more.

External output terminal

6. 6. 3. 

Service parts : EXTERNAL INPUT WIRE A (9368777005)

You can detect the operation condition of outdoor unit and the abnormal situation of 

• 

both indoor and outdoor unit.

Wiring method and speci

fi

 cations

Error display

This output indicates the outdoor unit and connected indoor unit's “Normal” or “Error” 
status.

Operation display

This output indicates the outdoor unit's “Operation” status.

Connector

Output voltage

Status

Output1
CN136 (Black)

0V

Normal

DC 12-24 V  *5

Error

Output2
CN137 (Blue)

0V

Stop

DC 12-24 V  *5

Operation

+

+

-

P.C.B

*7

*5

*6

1

2

CN136 
(Black) 
or CN137 
(Blue)

DC power supply 
(External) 12 - 24V

Connected load 
(Operation Indicator 
or Error Indicator)

connected unit

9380545026-02_IM.indb   12

9380545026-02_IM.indb   12

19/08/2013   17:20:04

19/08/2013   17:20:04

Содержание AJHA36LALH

Страница 1: ...ΙΚΉ ΜΟΝΆΔΑ UNIDADE EXTERIOR ВНЕШНИЙ МОДУЛЬ DIŞ ÜNİTE For authorized service personnel only Nur für autorisiertes Fachpersonal Uniquement réservé aux techniciens agréés Sólo para personal de servicio autorizado A uso esclusivo del personale tecnico autorizzato Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό Apenas para técnicos de assistência autorizados Только для авторизованного обслуживающего персона...

Страница 2: ...performed electrical work can cause serious accidents such as electric shock or fire For wiring use the prescribed type of cables connect them securely making sure that there are no external forces of the cables applied to the terminal connections Improperly connected or secured cables can cause serious accidents such as over heating the terminals electric shock or fire Securely install the electr...

Страница 3: ...pe lightning rod or a telephone ground cable Improper grounding may cause electric shock Perform draining for the unit according to the Installation manual Check that the water is properly drained If the drain processing is improperly installed water may drip down from the unit wet ting the furniture Do not touch the fins with bare hands Be sure not to start or stop the operation of air conditioni...

Страница 4: ...part you could still receive noise under some signal conditions Keep the length of the piping of the indoor and outdoor units within the allowable range For maintenance purposes do not bury the piping Drain processing 3 2 CAUTION Perform drain work in accordance with this Manual and ensure that the drain water is properly drained If the drain work is not carried out correctly water may drip down f...

Страница 5: ... the upward area When the upward area is open Unit mm 1 Obstacles at rear only 300 2 Obstacles at front only 1500 or more 3 Obstacles at front and rear only 500 1500 or more When an obstruction is present also in the upward area Unit mm Obstacles at rear and above only 1500 500 Max 300 1500 3 3 3 Outdoor units installation in multi row Unit mm The following settings are not recommended in case of ...

Страница 6: ...5 Use reducer to change the diameter of connection pipe Installation the unit 3 5 Please install the outdoor unit without slant within 3 degrees Install 4 anchor bolts at the locations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base such as concrete blocks The foundation shall support the legs of the unit and have a...

Страница 7: ...g nitrogen gas it will create an oxidation film This can degrade performance or damage the parts in the unit such as the compres sor or valves Do not use flux to braze pipes If the flux is the chlorine type it will cause the pipes to corrode In addition if the flux contains fluoride it will affect the refrigerant piping system due to deterioration of refrigerant oil For brazing material use phosph...

Страница 8: ...g with R410A flare tools to achieve the specified flaring Use a thickness gauge to measure the dimension A Pipe outside diameter mm in Width across flats of Flare nut mm 6 35 1 4 17 9 52 3 8 22 12 70 1 2 26 15 88 5 8 29 19 05 3 4 36 Width across flats Bending pipes 5 4 2 CAUTION To prevent breaking of the pipe avoid sharp bends Bend the pipe with a radius of curvature of 100mm or more If the pipe ...

Страница 9: ...es Use a hexagon wrench size 4mm Opening 1 Insert the hexagon wrench into the valve shaft and turn it counterclockwise 2 Stop turning when the valve shaft can no longer be turned Open position Closing 1 Insert the hexagon wrench into the valve shaft and turn it clockwise 2 Stop turning when the valve shaft can no longer be turned Closed position Opening direction Hexagon wrench Seal blank cap inst...

Страница 10: ...urr on the edges to prevent snapping of cables It is recommended to apply rust proof paint on the edges to prevent rust Knockout holes are provided for wiring Fig A Knockout holes are provided 2 each in the same size in front lateral and rear sides Fig B Fig A Service panel Fig B Front connection Rear connection Lateral connection Selecting power supply cable and breaker 6 3 CAUTION Regulation of ...

Страница 11: ...etwork Convertor etc 1 Fig Transmission line Outdoor unit Indoor unit System Controller Touch Panel Controller Terminal resistor When AB BC BD 500m Signal Amplifier is required A B C D 2 Fig Do not use loop wiring NOTE This may lead to parts damage and erroneous operation Outdoor unit Indoor unit Signal Amplifier System Controller Touch Panel Controller Transmission line Terminal resistor Terminal...

Страница 12: ...re to connect to the terminal block 2 Securely clamp the crimp type terminals to the cables using an appropriate tool so that the cables do not come loose 3 Use the specified cables connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise the screw he...

Страница 13: ... ON Outdoor unit operation peak control Input4 CN134 Red OFF Normal operation ON Batch stop or Emergency stop operation 2 3 Input5 CN135 Orange 4 No pulse No information from electricity meter Pulse Power usage information from electricity meter The operations of each input terminal and the selection of function are set with the push button on the PC board of outdoor unit About the setting please ...

Страница 14: ...it printed circuit board DIP switch Terminating resistor setting 7 2 2 CAUTION Be sure to set the terminal resistor according to specifications Set the terminal resistor for every network segment NS If terminal resistor is set in multiple devices the overall communication system may be damaged If terminal resistor is not set in a device abnormal communication may occur Be sure to set 1 terminal re...

Страница 15: ...rbidden 2 2 0 0 Factory default 23 Forbidden 2 3 0 0 Factory default 24 Forbidden 2 4 0 0 Factory default 25 Forbidden 2 5 0 0 Factory default 26 Forbidden 2 6 0 0 Factory default 27 Forbidden 2 7 0 0 Factory default 28 Forbidden 2 8 0 0 Factory default 29 Forbidden 2 9 0 0 Factory default 30 Outdoor unit capacity save setting Level 1 stop 3 0 0 0 The capacity limit can be selected by the external...

Страница 16: ...play LED105 LED104 Flashing When F3 to F9 are displayed continue to press the SELECT button until F2 is displayed Use the MODE EXIT SELECT and ENTER buttons to configure settings according to the procedures below If no setting is made the factory default setting will be displayed Press the MODE EXIT button Press the SELECT button Press the ENTER button 2 Setting the first 2 digits 3 Setting the la...

Страница 17: ...operating manual When setting with a remote control refer to the remote control operating manual Automatic setting Check that the wiring is as shown in the figure below Operate using the outdoor master unit of each refrigerant system Wiring example for automatic address setting Fig 1 Signal amplifier wiring example 2 3 4 Indoor unit wiring example Connect the indoor and outdoor units of the same r...

Страница 18: ...re of nitrogen gas before blazing After completing the sealing test release the nitrogen gas from both valves Release the nitrogen gas slowly It may take about 10 minutes for completing the processing End 1 4 4 ﻸ ﻮ ﻮ ﻮ ﻮ ﻺ ﻶ First 2 digits Last 2 digits Press the SELECT button until 11 is displayed Press the ENTER button for more than 3 seconds Automatic address setting for indoor units The number...

Страница 19: ...nt in the liquid state If the refrigerant cylinder is equipped with a siphon it is not necessary to place the cylinder upright Check if the steel cylinder has a siphon installed or not before filling There is an indication with siphon for filling liquid on the steel cylinder Filling method for cylinder with siphon Set the cylinder vertical and fill with the liquid Liquid can be filled without turn...

Страница 20: ...Insulation Fig A TEST OPERATION 9 Indoor unit connection check 9 1 Normal operation will not be possible without performing the Indoor unit connection check Things to confirm before starting the Indoor unit 9 1 1 connection check To ensure safety check that the following work inspections and operations have been completed Check Item Check Column 1 Check that all work on the wiring connecting the o...

Страница 21: ...gerant Is the refrigerant circuit address correct Is a breaker installed at the power supply cable of outdoor unit Are the cable connected to the terminals without looseness and in accordance with the specifications Are the initial settings of the switches of the outdoor unit correctly configured Is the 3 way valve of the outdoor unit open Gas pipe and liquid pipe Is power supplied to the crank ca...

Страница 22: ...r 5 seconds Press the ENTER button for more than 3 seconds This will be displayed when the cooling operation mode is canceled This will be displayed after 5 seconds This will be displayed after 5 seconds This will be displayed when the heat ing operation mode is canceled Press the ENTER button for more than 3 seconds This will be displayed after 5 seconds Settings for stopping test run operation S...

Страница 23: ...rror permanent stop E 8 6 1 Outdoor unit discharge pressure sensor error E 8 6 3 Outdoor unit suction pressure sensor error E 8 6 4 Outdoor unit high pressure switch 1 error Outdoor unit actuator error E 9 3 1 Outdoor unit inverter compressor start up error E 9 4 1 Outdoor unit trip detection E 9 5 5 Outdoor unit compressor motor loss of synchro nization E 9 7 1 Outdoor unit fan motor 1 lock error...

Отзывы: