En-7

8.  TURNING ON THE POWER

 

CAUTION

Check that the power supply voltage is within the speci

fi

 ed range. If 

the power supply voltage outside the speci

fi

 cation is input, it will cause 

trouble.
Recheck the wiring. Incorrect wiring will cause trouble.

(1)  Check the wiring of this product.
(2)  Check the wiring and switches of units connected to convertor before 

tuning on the power.

(3)  Check that the switches of this product are correct.
(4)  Turn on the power for this product.

• This product is initialized for a period of approximately a few seconds 

after the power is turned on.
LED1 (green), LED2 (orange), LED5 (green), and LED6 (orange) 

fl

 ash.

• After initial setting is completed, operation will be restarted automati-

cally. LED1 (green) and LED5 (green) light.

* This product does not operate during initialization.

If an error occurs, the LED1, LED2, LED3, or  LED5, LED6, LED7, Prog 
LED lights or 

fl

 ashes.

Please refer to “12.2. Error code”.

9. INITIAL SETTING 

Address initial settings are 4 methods as follows.
(1)  Default addresses of indoor unit and outdoor unit are used. (Initial set-

ting is not necessary)
Default address value ([Ref No.—Node No.])
Indoor unit: 

[00

00] [00

01] •••  [00

63]

 [01

00] [01

01] •••  [01

63]

Outdoor unit:   [00

00] [00

01] •••  [00

03]

 [01

00] [01

01] •••  [01

03]

(2) Scan

Scan procedure is as follows.

• Turn on the switch of scan setting.
• “Scan display” by LED (address is registering inside the convertor.)
• “Number of connected indoor unit display” by LED (Scan is com-

plete)

• Turn off the switch of scan setting
• “Address update display” by LED
• Turn on the main power again.
• “Address rewriting display” by LED (Addresses are synchronized 

among boards)

* When scan error is generated, performing the scan again is neces-

sary.

(3)  Setting from PC (Refer to the application manual in the DVD of an ac-

cessary.)

(4) ETS 

For how to con

fi

 gure the settings from the ETS, refer to the Interface 

Speci

fi

 cation.

10. USB CABLE CONNECTION

Connect the accessory USB cable to the terminal below.

USB cable connector

Scan information (indoor unit address and outdoor unit address) can be 
input from the PC.
Connect the USB cable after turning off the power.

11. TEST  RUN

Test run can be performed in the following procedure using the switch 
SET 2-3.

(1)  Turn the test run switch (SET2-3) to ON.
(2)  The indoor unit registered to the convertor starts the test run.
(3)  Check that the indoor unit registered to the convertor performs the test 

run.

(4)  Turn the test run switch (SET2-3) to OFF.
(5)  The indoor unit which performs the test run stops it.

* When 60 minutes passes after the start of test run, test run of indoor unit 

ends automatically. Always turn the test run switch (SET2-3) to OFF.

9374707164-01_IM.indb   Sec1:7

9374707164-01_IM.indb   Sec1:7

4/28/2017   1:29:20 PM

4/28/2017   1:29:20 PM

Содержание AIRSTAGE UTY-VKGX

Страница 1: ...LAZIONE CONVERTITORE KNX PER VRF A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΜΕΤΑΤΡΟΠΕΑΣ KNX ΓΙΑ VRF Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO CONVERSOR KNX PARA VRF Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ КОНВЕРТОР KNX ДЛЯ СИСТЕМЫ VRF Только для авторизованного обслуживающего персонала MONTAJ KILAVUZU VRF IÇIN KNX DÖNÜŞTÜRÜCÜ Y...

Страница 2: ...e unit for special purposes such as storing food raising animals growing plants or preserving precision devices or art objects It can degrade the quality of the preserved or stored objects Install the unit in a well ventilated place avoiding rains and direct sun light Do not operate this unit when your hands are wet Touching the unit with wet hands will cause an electric shock If children may appr...

Страница 3: ...noise Otherwise a malfunction could result Perform wiring so that water does not enter this unit along the external wiring Always install a trap to the wiring or take other countermeasures Otherwise it will cause trouble or electric shock or fire Confirm the name of each unit and name of each terminal block of the unit and connect the wiring in accordance with the directions given in the manual so...

Страница 4: ...e figure below to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate tool so that the cables do not come loose 3 Use the specified cables connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise the sc...

Страница 5: ...essories and specified installation work parts Check the state of the installation parts Not using the specified parts will cause units to fall off electric shock fire etc Install at a place that can withstand the weight of the unit and install pos itively so that the unit will not topple or fall and add the wooden material for reinforce if necessary When installing this unit make sure that there ...

Страница 6: ...eir respective terminal block 6 Securely tighten the cable tie and then confirm that the cable will not come out Tightening strength Cable tie Power supply cable 0 3 to 0 5 N 2 7 to 4 4 lbf 3 to 5 kgf Dust proof bushing Power supply cable Cable tie Accessories Cable tie Accessories The screw hole When wiring the cable to the opposite side fix the cable as shown below 1 Remove the cable tie holder ...

Страница 7: ...roller Address Example When SET 1 x10 is set to 1 and SET 1 x1 is set to 5 This product Remote Controller Address is set to 15 KNX convertor Remote Controller address Rotary Switch Setting KNX convertor Remote Controller address Rotary Switch Setting SET1 10 SET1 1 SET1 10 SET1 1 0 0 0 8 0 8 1 0 1 9 0 9 2 0 2 10 1 0 3 0 3 11 1 1 4 0 4 12 1 2 5 0 5 13 1 3 6 0 6 14 1 4 7 0 7 15 1 5 Factory setting W...

Страница 8: ...ollows Turn on the switch of scan setting Scan display by LED address is registering inside the convertor Number of connected indoor unit display by LED Scan is com plete Turn off the switch of scan setting Address update display by LED Turn on the main power again Address rewriting display by LED Addresses are synchronized among boards When scan error is generated performing the scan again is nec...

Страница 9: ...s at 0 5s interval example of 8 Normal indications Normal contents LED5 green LED6 orange LED7 red Prog LED red Normal starting Flashes alternately Start sequence or address rewriting Flashes simultaneously USB mode indication Programming mode display Display mode On Off 0 5s ON 0 5s OFF 1 0s ON 1 0s OFF State unconcerned 12 2 Error code For the error indications of devices connected to the conver...

Отзывы: