5. WIRING

 

WARNING

Before starting installation work, turn off the power of this unit and the 
connection destination. Do not turn on the power again until installation 
is completed. Otherwise, it will cause electric shock or 

fi

 re.

Use speci

fi

 ed cables or accessory cables to connect to this unit.

Do not modify the cables to connect this unit other than those speci

fi

 ed, 

do not use extension cables, and do not use independent branch wiring. 
It may cause electric shock or 

fi

 re.

Install the transmission cables securely to the terminal block. Con

fi

 rm 

that external force is not applied to the cable. Use transmission cables 
made of the speci

fi

 ed cable. If intermediate connection or insertion 

fi

 x-

ing are imperfect, it will cause electric shock, 

fi

 re, etc.

When connecting the cables to this unit, route the cables so that the 
cover of this unit is securely 

fi

 xed. If the cover is imperfectly 

fi

 xed, it may 

cause 

fi

 re or overheating of the terminals.

Perform earth (ground) work positively. Do not connect the earth (ground) 
cable to a telephone cable, water pipe, or conductor rod.

Always fasten the outside covering of the cables with the cable clamp. (If 
the insulator is chafed, electric leakage may occur.)

Perform all wiring works so that the user does not touch the wiring. 
Otherwise, injury or electric shock could result.

If any cable is damaged, do not repair or modify it yourself. Improper 
work will cause electric shock or 

fi

 re.

 

CAUTION

Do not bind the remote controller cable and the transmission cable 
together with or parallel to the power supply cable of the indoor and 
outdoor units. It may cause erroneous operation.

When performing wiring work, be careful not to damage the cable or 
injure yourself. Also, connect the connectors securely. Loose connec-
tors will cause trouble, heating, 

fi

 re, or electric shock.

Install the indoor and outdoor units, power supply cable, transmission 
cable and remote control cable 1 m (40 in.) away from television and ra-
dio to avoid distorted images and noise. Otherwise, a malfunction could 
result.

Perform wiring so that water does not enter this unit along the external 
wiring. Always install a trap to the wiring or take other countermeasures. 
Otherwise it will cause trouble or electric shock or 

fi

 re.

Con

fi

 rm the name of each unit and name of each terminal block of the 

unit and connect the wiring in accordance with the directions given in 
the manual so that there is no incorrect wiring. Incorrect wiring will dam-
age the electric parts and cause smoke and 

fi

 re.

When installing the connection cables near a source of electromagnetic 
waves, use shielded cable.
Otherwise, a breakdown or malfunction could result.

The terminal screws and earth (ground) screws have different shapes. 
Be sure to install the screws in the correct locations. If the screws are 
installed in the wrong locations, the circuit board could be damaged.

3. ELECTRICAL REQUIREMENT

Use

Size

Wire type

Remarks

Power 
supply 
cable

Maximum

1.25 mm

(16AWG) Type 60245 IEC 

57 or equivalent

1Ø AC220–240 V 
50/60Hz, 2 Cable + 
earth (ground) 
[Always earth (ground) 
the unit]

Minimum

0.8 mm

(18AWG)

Transmis-
sion cable

0.33 mm

2

(22AWG)

22AWG LEVEL4 
(NEMA) 
nonpolar 2 core, 
twisted pair solid 
core Shielded

L

ON

W

ORKS

 

compatible cable

KNX 
cable

Maximum

0.8 mm

(18AWG) AWG18-20 

2Wire twisted pair

KNX TP1
(Twister Pair 1) cable

Minimum

0.5 mm

(20AWG)

L

ON

W

ORKS

 is registered trademark of Echelon Corporation in the 

United States and other countries.

4.  SELECTING AN INSTALLATION LOCATION

4.1. Dimensions

This product  is comprised of a body and cover.

225 (8-7/8)

241 (9-1/2)

260 (10-1/4)

4-Ø5 (3/16)

2-Ø5 (3/16)

54

 (2-1/8)

150 (5-7/8)

55 (2-3/16)

55 (2-3/16)

19 (3/4)

16 (5/8)

Ø22 (7/8)

5-Ø13 (1/2)

10 (3/8)

59 (2-5/16)

5x20=100

 (3-15/16)

For M4x16mm screws

Ho

le

 p

itc

h

Unit : mm (in.)

For conduit

Ho

le

 p

itc

h

Hole pitch

Hole pitch

For dust proof 
bushing

For M4x16mm 

screws

4.2. Speci

fi

 cations

Power supply

1Ø AC220–240V
50/60 Hz

Power consumption (W)

1.5

Temperature 
°C(°F)

Operating

0–46 (32–114)

Packaged

-10–60 (14–140)

Humidity (%)

Packaged

0–95 (RH); No condensation

Dimensions 
H x W x D  mm(in.)

54 × 260 × 150
 (2-1/8 × 10-1/4 × 5-7/8)

Weight g (oz.)

1200 (42)

9374707164-01_IM.indb   Sec1:2

9374707164-01_IM.indb   Sec1:2

4/28/2017   1:29:19 PM

4/28/2017   1:29:19 PM

Содержание AIRSTAGE UTY-VKGX

Страница 1: ...LAZIONE CONVERTITORE KNX PER VRF A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΜΕΤΑΤΡΟΠΕΑΣ KNX ΓΙΑ VRF Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO CONVERSOR KNX PARA VRF Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ КОНВЕРТОР KNX ДЛЯ СИСТЕМЫ VRF Только для авторизованного обслуживающего персонала MONTAJ KILAVUZU VRF IÇIN KNX DÖNÜŞTÜRÜCÜ Y...

Страница 2: ...e unit for special purposes such as storing food raising animals growing plants or preserving precision devices or art objects It can degrade the quality of the preserved or stored objects Install the unit in a well ventilated place avoiding rains and direct sun light Do not operate this unit when your hands are wet Touching the unit with wet hands will cause an electric shock If children may appr...

Страница 3: ...noise Otherwise a malfunction could result Perform wiring so that water does not enter this unit along the external wiring Always install a trap to the wiring or take other countermeasures Otherwise it will cause trouble or electric shock or fire Confirm the name of each unit and name of each terminal block of the unit and connect the wiring in accordance with the directions given in the manual so...

Страница 4: ...e figure below to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate tool so that the cables do not come loose 3 Use the specified cables connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise the sc...

Страница 5: ...essories and specified installation work parts Check the state of the installation parts Not using the specified parts will cause units to fall off electric shock fire etc Install at a place that can withstand the weight of the unit and install pos itively so that the unit will not topple or fall and add the wooden material for reinforce if necessary When installing this unit make sure that there ...

Страница 6: ...eir respective terminal block 6 Securely tighten the cable tie and then confirm that the cable will not come out Tightening strength Cable tie Power supply cable 0 3 to 0 5 N 2 7 to 4 4 lbf 3 to 5 kgf Dust proof bushing Power supply cable Cable tie Accessories Cable tie Accessories The screw hole When wiring the cable to the opposite side fix the cable as shown below 1 Remove the cable tie holder ...

Страница 7: ...roller Address Example When SET 1 x10 is set to 1 and SET 1 x1 is set to 5 This product Remote Controller Address is set to 15 KNX convertor Remote Controller address Rotary Switch Setting KNX convertor Remote Controller address Rotary Switch Setting SET1 10 SET1 1 SET1 10 SET1 1 0 0 0 8 0 8 1 0 1 9 0 9 2 0 2 10 1 0 3 0 3 11 1 1 4 0 4 12 1 2 5 0 5 13 1 3 6 0 6 14 1 4 7 0 7 15 1 5 Factory setting W...

Страница 8: ...ollows Turn on the switch of scan setting Scan display by LED address is registering inside the convertor Number of connected indoor unit display by LED Scan is com plete Turn off the switch of scan setting Address update display by LED Turn on the main power again Address rewriting display by LED Addresses are synchronized among boards When scan error is generated performing the scan again is nec...

Страница 9: ...s at 0 5s interval example of 8 Normal indications Normal contents LED5 green LED6 orange LED7 red Prog LED red Normal starting Flashes alternately Start sequence or address rewriting Flashes simultaneously USB mode indication Programming mode display Display mode On Off 0 5s ON 0 5s OFF 1 0s ON 1 0s OFF State unconcerned 12 2 Error code For the error indications of devices connected to the conver...

Отзывы: