5.2.  Install the drain pipe

 CAUTION

Be sure to fix the drain hose to the drain port with the hose band. Do not apply glue to 

the drain port. Otherwise it will cause water leakage.

(1)  Be sure to use 

supplied drain 

hose (a) and hose 

band (b).

(b) Hose band (accessories)

Drain port

(a) Drain hose (accessories)

Hard PVC side 

Hose band

4 mm or less

20 mm

(b) Hose band

(a) Drain hose

Fasten the hose band (b) at the position where 

horizontal against ground.

The hose band (b) must be positioned at the right 

side of the drain hose (a) as in the figure.

(2)  Be sure to connect 

Drain pipe with adhe

-

sive (polyvinyl chloride) 

so that there is no 

leakage.

Applying 

area of 

adhesive

Joint pipe (lo

-

cally purchased)

Drain pipe (VP25) 

(locally purchased)

4 mm or less

 CAUTION

Do not connect to the drain hole with adhesive. Using adhesive may cause damage and 

water leaks.

(3)  After installing the drain hose (a), check if the drainage is smooth.

 CAUTION

To prevent excessive force on drain hose (a), avoid bends or twists. (To bend or twist 

may cause water leaks.)

(4)  After checking for 

drainage, attach 

the drain hose 

insulation B (c) to 

insulate, following the 

instructions as in the 

figures.

 

To avoid space with 

drain hose (a) and 

hose band (b), press 

firmly the drain hose 

insulation B (c).

(c) Drain hose insulation B 

(accessories)

Ensure there 

is no space.

• STEP1 - STEP3

Butt the insulation 

against the unit.

STEP 1

Unit

Slit

Press firmly

Press firmly

STEP 2

Slit

Press firmly

Roll the in

-

sulation over 

the joint.

Press firmly

STEP 3

Press firmly

Slit

4.4.  Installing heat insulation

Install the heat insulation material after performing a refrigerant leak check (refer to the 

installation manual for the outdoor unit for details).

4.4.1.  Coupler heat insulation

• Insulate by the coupler heat insulation 

(accessories) around the gas pipe and 

liquid pipe of indoor side.

• After installing the coupler heat insula

-

tion, wrap both end with vinyl tape so 

that there is no gap.

• After affixing the coupler heat insulation, 

secure it with 2 cable ties (large), one on 

each end of the insulation.

• Make sure that the cable ties overlap the 

heat insulation pipe.

Coupler heat 

insulation 

 

(accessories)

Cover this portion with 

heat insulation.

Cable tie (large) 

(accessories)

Heat insulation

 CAUTION

After checking for gas leaks (refer to the Installation Manual of the outdoor unit), per

-

form this section.
Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to do 

so may cause water leaks.

5.  INSTALLING DRAIN PIPES

 WARNING

Do not insert the drain piping into the sewer where sulfurous gas occurs. (Heat ex

-

change erosion may occur)
Insulate the parts properly so that water will not drip from the connection parts.
Check for proper drainage after the construction by using the visible portion of transpar

-

ent drain port and the drain piping final outlet on the body.

 CAUTION

Do not apply adhesive agent on the drain port of the body.

(Use the attached drain hose and connect the drain piping)

5.1.  Drain  piping

• Use general hard polyvinyl chloride pipe (VP25) [outside diameter 32 mm].

• Do not perform a rise, trap and air bleeding.

• Provide a downward gradient (1/100 or more).

• Provide supporters when long pipes are installed.

• Use an insulation material as needed, to prevent the pipes from freezing.

• Install the pipes in a way that allows for the removal of the control box.

Gap of 1.5 to 2 m

700 mm or less

Horizontal or 

upward gradient

Drain hose (accessories)

Ceiling

Supporter

Max. 300 mm

Locally arranged pipe

GOOD

VP25 [O.D 

32 mm or more]

Rise

Air bleeding

Trap

Drain hose is not used

PROHIBITED

Observe the following procedures to construct centralized drain pipe fittings.

VP30 or more [O.D 38 mm or more]

Downward gradient 1/100 or more

700 mm or less

9384723017_IM.indb   5

14-Oct-20   13:29:51

Содержание Airstage AUXV004GLEH

Страница 1: ...a cassetta flusso a 1 via A uso esclusivo del personale tecnico autorizzato Ελληνικά Português ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΣΩΤΕΡΙΚΗ ΜΟΝΑΔΑ Τύπος κασέτας ροής 1 δρόμου Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO UNIDADE INTERIOR tipo de cassete de fluxo 1 via Apenas para técnicos autorizados Русский Türkçe РУКОВОДСТВО ПО УСТАНОВКЕ ВНУТРЕННИЙМОДУЛЬ 1 стороннийкассетноготипасвоздушны...

Страница 2: ...g consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using the R410A refrigerant WARNING Do not introduce any substance other than the prescribed refrigerant into the refrigera tion cycle If air enters the refrigeration cycle the pressure in the refrigeration cycle will become abnormally high and cause the piping to rupture ...

Страница 3: ...te metal parts causing the parts to fail or the unit to leak water Area filled with mineral oil or containing a large amount of splashed oil or steam such as a kitchen It will deteriorate plastic parts causing the parts to fail or the unit to leak water Area that generates substances that adversely affect the equipment such as sulfuric gas chlorine gas acid or alkali It will cause the copper pipes...

Страница 4: ...lp you install the indoor unit The template helps you determine the appropriate locations for suspension bolts and pipe openings drain pipe and connection cable 3 4 1 Indoor unit dimensions Top view Unit mm A Hanger bolt pitch C Ceiling opening D Cassette grille size 590 Ceiling opening 295 Hanger bolt pitch 620 Cassette grille size B Indoor unit size 570 Indoor unit size Model AUXV004 007 009 012...

Страница 5: ...and generate hazardous gas if the refrigerant comes into contact with a flame 4 3 1 Flaring Use special flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units or RB unit respectiv...

Страница 6: ... accessories around the gas pipe and liquid pipe of indoor side After installing the coupler heat insula tion wrap both end with vinyl tape so that there is no gap After affixing the coupler heat insulation secure it with 2 cable ties large one on each end of the insulation Make sure that the cable ties overlap the heat insulation pipe Coupler heat insulation accessories Cover this portion with he...

Страница 7: ...AUTION Earth Ground the unit Do not connect the earth ground cable to a gas pipe water pipe lightning rod or a telephone earth ground cable Improper earthing grounding may cause electric shock Do not connect power supply cables to the transmission or remote controller terminals as this will damage the product Never bundle the power supply cable and transmission cable remote controller cable togeth...

Страница 8: ...iring 1 Use ring terminals with insulating sleeves as shown in the figure below to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate tool so that the cables do not come loose 3 Use the specified cables connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal s...

Страница 9: ...n Fast flashing every 0 1 second There is a fault with the communication board or the main board Blinking repeat 3 seconds ON and 1 second OFF The indoor unit is turned off and power is supplied from the External power supply unit optional to the indoor unit PCB 6 5 3 Connection methods Wire modification for External input output wire 1 Remove insulation from wire at tached to wire kit connector 2...

Страница 10: ...t DC 12 V DC 1 mA or less d The wiring is different from apply voltage terminals Be sufficiently careful when wir ing When connected to dry contact terminals of multiple indoor units with a connected unit insulate each indoor unit with relay etc as shown on below example K1 CNA02 CNA02 CNA02 K2 K3 K4 K5 K6 Power supply for relay Indoor unit Indoor unit Indoor unit Input device 2 Input device 1 K1 ...

Страница 11: ...al for detailed setting informa tion Set IU AD REF AD SW to 0 CAUTION Be sure to turn OFF the power before performing the field setting 7 1 Setting the address 7 1 1 Manual address setting method If the receiver unit is attached the indoor unit address and the refrigerant circuit address can also be set up through the wireless remote controller CAUTION Use an insulated screwdriver to set the DIP s...

Страница 12: ...aise the trigger temperature use setting 03 01 Adjust 1 02 Adjust 2 03 Adjust 3 Auto restart 40 00 Enable Enable or disable automatic system restart after a power outage 01 Disable Cool Air Prevention 43 00 Super low Restrain the cold airflow with making the airflow lower when starting heat ing operation To correspond to the ventilation set to 01 01 Follow the setting on the remote controller Exte...

Страница 13: ...vice No operation After installation is completed has the proper operation and handling been explained to the user 12 ERROR CODES If you use a wired type remote controller error codes will appear on the remote controller display If you use a wireless remote controller the lamp on the photodetector unit will output error codes by way of blinking patterns Refer to the following table for lamp blink ...

Отзывы: