En-5

(1)  Detach the caps and plugs from the pipes.
(2)  Center the pipe against the port on the indoor unit,  and then turn the flare nut by 

hand.

Connection pipe (Gas)

Connection pipe (Liquid)

(3)  When the flare nut is tightened properly 

by your hand, hold the indoor unit side 
coupling with a separate spanner, then 
tighten with a torque wrench. (See the 
table below for the flare nut tightening 
torques.)

Tighten with 2 
wrenches.

Holding 
wrench

Flare nut 

Connection pipe

Indoor unit pipe 
(Body side)

Torque 
wrench

Flare nut 
[mm (in)]

Tightening torque 

[N·m (kgf·cm)]

6.35 (1/4) dia.

16 to 18 (160 to 180)

9.52 (3/8) dia.

32 to 42 (320 to 420)

12.70 (1/2) dia.

49 to 61 (490 to 610)

15.88 (5/8) dia.

63 to 75 (630 to 750)

19.05 (3/4) dia.

90 to 110 (900 to 1,100)

4.4. Installing heat insulation

 CAUTION

After checking for gas leaks (refer to the Installation Manual of the outdoor unit), perform 
this section.

Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to do 
so may cause water leaks.

After checking for gas leaks, 
insulate by wrapping insula-
tion around the 2 parts (gas 
and liquid) of the indoor unit 
coupling, using the Coupler 
heat insulation.
After installing the Coupler 
heat insulation, wrap both ends 
with vinyl tape so that there is 
no gap.

Cable tie (large) 
(accessories)

Indoor  
unit

Be sure to overlap 
the insulation

Coupler heat 
insulation

Coupler heat 
insulation 
(accessories)

No gap

 CAUTION

Must fit tightly against indoor unit without any gap.

5. INSTALLING DRAIN PIPES

 WARNING

Do not insert the drain piping into the sewer where sulfurous gas occurs. (Heat ex-
change erosion may occur)

Insulate the parts properly so that water will not drip from the connection parts.

Check for proper drainage after the construction by using the visible portion of transpar-
ent drain port and the drain piping final outlet on the indoor unit.

 CAUTION

Do not apply adhesive agent on the drain port of the indoor unit. (Use the attached drain 
hose and connect the drain piping)

• Install the drain pipe with downward gradient (1/100 to 1/50) and so there are no rises or 

traps in the pipe. Unsmooth draining caused by accumulated water flow in the pipe may 
cause clogged drain.

• Use general hard polyvinyl chloride pipe (VP25) [outside diameter 32 mm].
• When the pipe is long, install supporters.
• Do not perform air bleeding. Drainage may 

be blown out.

• If it is impossible to have sufficient gradient 

of pipe, perform drain lift-up.

Pipe size

Drain pipe

VP25 (O.D. 32 mm)

Hanging fittings

1.5 to 2 m

VP25 (O.D. 32 mm)
Downward gradient 1/100 to 1/50

Rise

PROHIBITED:

Trap

Air bleeding

When lifting up drain:
• Height of inclined pipe should be less than 850 mm from the ceiling. A rise dimension 

over this range will cause leakage.

• Lift up the pipe vertically at the position of 300 mm or less from the unit.

300 mm or less

VP25 (O.D. 32 mm) local 
arrangement

850 mm or less

650 mm 

or less

Horizontal or upward 
gradient (*1)

Downward gradient 1/100 to 1/50

*1:  Install the drain hose horizontally or with a slight upward gradient so air pocket is not 

generated in the drain pipe. The air pocket may cause noise occurred due to water 
backfl ow when the drain pump is stopped.

VP30 (O.D. 38 mm) or more Downward gradient 
1/100 to 1/50

850 mm or less

Working procedure

(1)  Be sure to use supplied Drain hose 

 and Hose band 

.

 Hose band (accessories)

Drain hole

 Drain hose (accessories)

Hard PVC side 

Hose band

4 mm or less

20 mm

 Hose band

 Drain hose

Fasten the Hose band 

 at the position where horizon-

tal against earth (ground).
The Hose band 

 must be positioned at the right side 

of the Drain hose 

 as in the figure.

9383489013_IM.indb   5

9383489013_IM.indb   5

08-Feb-19   17:11:23

08-Feb-19   17:11:23

Содержание AIRSTAGE AUXS018GLEH

Страница 1: ...n flusso 3D A uso esclusivo del personale tecnico autorizzato Ελληνικά Português ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΣΩΤΕΡΙΚΗ ΜΟΝΑΔΑ τύπος κασέτας με ροή 3D Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO UNIDADE INTERIOR tipo de cassete de fluxo 3D Apenas para técnicos autorizados Русский Türkçe РУКОВОДСТВО ПО УСТАНОВКЕ ВНУТРЕННИЙ МОДУЛЬ кассетный тип с 3D потоком Только для авторизованного ...

Страница 2: ...rvice person nel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using the R410A refrigerant WARNING Do not introduce any substance other than the prescribed refrigerant into the refrigera tion cycle If air enters the refrigeration cycle the pressure in the refrigeration cycle will become abnormally...

Страница 3: ...unit to leak water Area filled with mineral oil or containing a large amount of splashed oil or steam such as a kitchen It will deteriorate plastic parts causing the parts to fail or the unit to leak water Area that generates substances that adversely affect the equipment such as sulfuric gas chlorine gas acid or alkali It will cause the copper pipes and brazed joints to corrode which can cause re...

Страница 4: ... pipe 50 150 227 204 250 85 120 Drain pipe Connect the attached drain hose 435 105 65 2 Hanging structure Select a strong structure for the hanging location If necessary reinforce the hanging bolt with quakeproof columnar support material to prevent shaking Use hanging bolts of M8 to M10 3 3 2 Hanging preparations Firmly fasten the hanging bolts as shown in the figure or by another method Install ...

Страница 5: ...addition use heat insulation with heat conductivity of 0 045 W m K or less at 20 C 4 3 Flare connection pipe connection WARNING Tighten the flare nuts with a torque wrench using the specified tightening method Other wise the flare nuts could break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a flame 4 3 1 Flaring Use spe...

Страница 6: ...by using the visible portion of transpar ent drain port and the drain piping final outlet on the indoor unit CAUTION Do not apply adhesive agent on the drain port of the indoor unit Use the attached drain hose and connect the drain piping Install the drain pipe with downward gradient 1 100 to 1 50 and so there are no rises or traps in the pipe Unsmooth draining caused by accumulated water flow in ...

Страница 7: ...sufficient insulation or exceeding the allowable current can cause electric shock or fire Do not modify the power cables use extension cables or use any branches in the wir ing Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection cable colors with those of the outdoor unit or RB unit Erroneo...

Страница 8: ...manual of the RB unit 2 Earth Ground the remote controller if it has an earth ground cable 3 The 3 wire type remote controller is not used Crossover wiring of power supply Indoor unit Pull box Pull box Power supply Power supply Power supply Indoor unit Indoor unit Breaker Power supply 6 3 Unit wiring Before attaching the cable to terminal block 6 3 1 Power supply cable Earth Ground cable 20 mm 30 ...

Страница 9: ...d Then loosen one screw and remove the sheet metal Connector 3 After wiring is complete secure the cables with the cable clamps Cable clamp Earth ground Power supply cable 4 Connect the transmission and remote controller cables by passing the cables through the hole shown in the diagram below Once all cables are connected tie the power cable using a push mount cable tie and tie the transmission an...

Страница 10: ...er supply unit Cable of the IR receiver unit Cable clamp Cable clamp Once all connectors required for connection are connected push up the circuit board that was pulled down and endure that the hooks are in place Fix the connected cables by passing them through the hole using the grille accessory cable tie as shown in the following figure Cable tie accessory of the grille 6 6 External input and ex...

Страница 11: ...ergency stop ON OFF Normal Pulse CNA01 or CNA02 Ch1 OFF ON Emergency stop Ch2 OFF ON Normal All indoor units of same refrigerant system stops when Emergency stop operates When function setting is Forced stop mode Input signal type Connector Input signal Command Edge Ch1 of CNA01 or CNA02 OFF ON Forced stop ON OFF Normal Pulse CNA01 or CNA02 Ch1 OFF ON Forced stop Ch2 OFF ON Normal When the forced ...

Страница 12: ...g for indoor unit Set the DIP switch SET3 SW1 2 referring to the figure and table below SET3 10 IU AD 1 10 REF AD 1 SET4 DIP switch SET3 SW 1 SW 2 SW 3 SW 4 ON OFF DIP switch SET3 DIP switch SET3 Custom code A Factory setting B C D SW1 OFF ON OFF ON SW2 OFF OFF ON ON 7 3 Function setting FUNCTION SETTING can be performed with the wired or wireless remote controller The remote controller is optiona...

Страница 13: ...9 4 5 C Forbidden 71 00 Forbidden 72 00 Forbidden 73 00 Forbidden 74 00 Forbidden 75 00 8 GRILLE INSTALLATION Operate according to the installation manual of the grille Be sure to confirm there is no gap between the grille and indoor unit after installing the grille 9 TEST RUN 9 1 Test run using Outdoor unit PCB Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit ...

Страница 14: ...r error 3 10 Indoor unit communication circuit wired remote control ler error 4 1 Indoor unit room temp therm istor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor unit miscellaneous error 10 8 Poor refrigerant circulation 13 1 RB unit error Display mode 0 5 s ON 0 5 s...