background image

En-11

7. FIELD SETTING

There are 3 methods for address setting by FIELD SETTING as follows.
Please set by either of the methods.
Each setting method is described in below (1) to (3).
(1)

IU AD, REF AD SW settings: This section (7.1. Setting the address)

(2)

Remote controller settings:

Refer to the wired or wireless remote controller 
manual for detailed setting information. (Set IU AD, 
REF AD SW to 0)

(3)

Automatic address settings: Refer to the outdoor unit manual for detailed setting 

information. (Set IU AD, REF AD SW to 0)

7.1.  Setting the address

 CAUTION

Use an insulated screwdriver to set the dip switches.

The rotary switches and slide switches to configure are located at the location shown 
below.

SET3

×10  IU  AD  ×1

×10 REF AD ×1

SET4

For refrigerant circuit 
address

For indoor unit 
address

7.1.1. Indoor unit address

• Rotary switch (IU AD × 1)...Factory setting “0”
• Rotary switch (IU AD × 10)...Factory setting “0”
When connecting multiple indoor units to 1 refrigerant system, set the address at IU AD 
SW as shown in the Table A.

7.1.2. Refrigerant circuit address

• Rotary switch (IU AD × 1)...Factory setting “0”
• Rotary switch (IU AD × 10)...Factory setting “0”
In the case of  multiple refrigerant systems, set REF AD SW as shown in the Table A for 
each refrigerant system.
Set to the same refrigerant circuit address as the outdoor unit.

Setting

Setting range

Type of switch

Indoor unit ad-
dress

0 to 63

Setting ex-
ample 
2

IU AD × 10

IU AD × 1

Refrigerant 
circuit address

0 to 99

Setting ex-
ample 
63

REF AD × 10

REF AD × 1

• If working in an environment where the wireless remote controller can be used, the ad-

dresses can also be set using the remote controller.

• If setting the addresses using the wireless remote controller, set the indoor unit address 

and refrigerant circuit address to “00”. 
(For information on setting using the wireless remote controller.)

Table A

Address

Rotary Switch Setting

Address

Rotary Switch Setting

Refrigerant circuit

REF AD SW

Indoor unit

IU AD SW

×

 10

×

 1

×

 10

×

 1

0

0

0

0

0

0

1

0

1

1

0

1

2

0

2

2

0

2

3

0

3

3

0

3

4

0

4

4

0

4

5

0

5

5

0

5

6

0

6

6

0

6

7

0

7

7

0

7

8

0

8

8

0

8

9

0

9

9

0

9

10

1

0

10

1

0

11

1

1

11

1

1

12

1

2

12

1

2

99

9

9

63

6

3

Do not set the indoor unit address (IU AD SW) at 64 to 99. 
It may result in failure.

7.2. Custom code setting

• Selecting the custom code prevents the indoor unit mix-up. (figure below)

(Up to 4 codes can be set.)

• Perform the setting for both the indoor unit and the remote controller.

Code change

Indoor unit

Remote 
controller

Confusion

A            B              C           D

A           B            C             D

Custom code setting for indoor unit
Set the DIP switch SET3 SW1, 2, referring to 
the figure and table below.

SET3

×10  IU  AD  ×1

×10 REF AD ×1

SET4

DIP switch 
“SET3”

SW

1

SW

2

SW

3

SW

4

ON

OFF

DIP switch “SET3”

DIP switch 

SET3

Custom code

A (Factory 

setting)

B

C

D

SW1

OFF

ON

OFF

ON

SW2

OFF

OFF

ON

ON

7.3. Function setting

• FUNCTION SETTING can be performed with the wired or wireless remote controller. 

(The remote controller is optional equipment)

• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to “7.1. Setting the address” for indoor unit address and refrigerant circuit address 

settings.

• Turn the power of the indoor unit ON before starting the setting.
*  Turning on the power to the indoor units initializes EEV, so make sure the piping air tight 

test and vacuuming have been conducted before turning on the power.

*  Also check again to make sure no wiring mistakes were made before turning on the 

power.

Function details

Function

Function 

number

Setting number

Default

Details

Filter 
indicator 
interval

11

00 Standard

Adjust the filter cleaning interval 
notification. If the notification is too 
early, change to setting 01. If the 
notification is too late, change to 
setting 02.

01 Longer

02 Shorter

Filter 
indicator 
action

13

00 Enable

Enable or disable the filter indica-
tor. Setting 02 is for use with a 
central remote controller.

01 Disable

02

Display only 
on central 
remote 
controller

Ceiling
airflow

20

00 Standard

Regulate the airflow accordingto 
the needs of the installationloca-
tion. When set to 01, the airflow 
will be stronger. 

01

High
Ceiling 

(Forbidden)

23

(Forbidden)

24

Installation 
position 
setting

27

00 Center

Setting to switch the airflow 
direction based on the installation 
position of the indoor unit.

Center

Right

Left

01 Right

02 Left

Cool air 
tem-
perature 
trigger

30

00 Standard

Adjust the cool air trigger 
temperature. To lower the trigger 
temperature, use setting 01. To 
raise the trigger temperature, use 
setting 02.

01 Adjust (1)

02 Adjust (2)

Heat air 
tempera-
ture trigger

31

00 Standard

Adjust the heat air trigger tempera-
ture. To lower the trigger tempera-
ture by 6 degrees C, use setting 
01. To lower the trigger temperature 
by 4 degrees C, use setting 02. To 
raise the trigger temperature, use 
setting 03.

01 Adjust (1)
02 Adjust (2)

03 Adjust (3)

Auto restart

40

00 Enable

Enable or disable automatic system 
restart after a power outage.

01 Disable

Cool Air 
Prevention

43

00 Super low

Restrain the cold airflow with mak-
ing the airflow lower when starting 
heating operation. To correspond to 
the ventilation, set to 01.

01

Follow the 
setting on 
the remote 
controller

9383489013_IM.indb   11

9383489013_IM.indb   11

08-Feb-19   17:11:26

08-Feb-19   17:11:26

Содержание AIRSTAGE AUXS018GLEH

Страница 1: ...n flusso 3D A uso esclusivo del personale tecnico autorizzato Ελληνικά Português ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΣΩΤΕΡΙΚΗ ΜΟΝΑΔΑ τύπος κασέτας με ροή 3D Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO UNIDADE INTERIOR tipo de cassete de fluxo 3D Apenas para técnicos autorizados Русский Türkçe РУКОВОДСТВО ПО УСТАНОВКЕ ВНУТРЕННИЙ МОДУЛЬ кассетный тип с 3D потоком Только для авторизованного ...

Страница 2: ...rvice person nel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using the R410A refrigerant WARNING Do not introduce any substance other than the prescribed refrigerant into the refrigera tion cycle If air enters the refrigeration cycle the pressure in the refrigeration cycle will become abnormally...

Страница 3: ...unit to leak water Area filled with mineral oil or containing a large amount of splashed oil or steam such as a kitchen It will deteriorate plastic parts causing the parts to fail or the unit to leak water Area that generates substances that adversely affect the equipment such as sulfuric gas chlorine gas acid or alkali It will cause the copper pipes and brazed joints to corrode which can cause re...

Страница 4: ... pipe 50 150 227 204 250 85 120 Drain pipe Connect the attached drain hose 435 105 65 2 Hanging structure Select a strong structure for the hanging location If necessary reinforce the hanging bolt with quakeproof columnar support material to prevent shaking Use hanging bolts of M8 to M10 3 3 2 Hanging preparations Firmly fasten the hanging bolts as shown in the figure or by another method Install ...

Страница 5: ...addition use heat insulation with heat conductivity of 0 045 W m K or less at 20 C 4 3 Flare connection pipe connection WARNING Tighten the flare nuts with a torque wrench using the specified tightening method Other wise the flare nuts could break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a flame 4 3 1 Flaring Use spe...

Страница 6: ...by using the visible portion of transpar ent drain port and the drain piping final outlet on the indoor unit CAUTION Do not apply adhesive agent on the drain port of the indoor unit Use the attached drain hose and connect the drain piping Install the drain pipe with downward gradient 1 100 to 1 50 and so there are no rises or traps in the pipe Unsmooth draining caused by accumulated water flow in ...

Страница 7: ...sufficient insulation or exceeding the allowable current can cause electric shock or fire Do not modify the power cables use extension cables or use any branches in the wir ing Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection cable colors with those of the outdoor unit or RB unit Erroneo...

Страница 8: ...manual of the RB unit 2 Earth Ground the remote controller if it has an earth ground cable 3 The 3 wire type remote controller is not used Crossover wiring of power supply Indoor unit Pull box Pull box Power supply Power supply Power supply Indoor unit Indoor unit Breaker Power supply 6 3 Unit wiring Before attaching the cable to terminal block 6 3 1 Power supply cable Earth Ground cable 20 mm 30 ...

Страница 9: ...d Then loosen one screw and remove the sheet metal Connector 3 After wiring is complete secure the cables with the cable clamps Cable clamp Earth ground Power supply cable 4 Connect the transmission and remote controller cables by passing the cables through the hole shown in the diagram below Once all cables are connected tie the power cable using a push mount cable tie and tie the transmission an...

Страница 10: ...er supply unit Cable of the IR receiver unit Cable clamp Cable clamp Once all connectors required for connection are connected push up the circuit board that was pulled down and endure that the hooks are in place Fix the connected cables by passing them through the hole using the grille accessory cable tie as shown in the following figure Cable tie accessory of the grille 6 6 External input and ex...

Страница 11: ...ergency stop ON OFF Normal Pulse CNA01 or CNA02 Ch1 OFF ON Emergency stop Ch2 OFF ON Normal All indoor units of same refrigerant system stops when Emergency stop operates When function setting is Forced stop mode Input signal type Connector Input signal Command Edge Ch1 of CNA01 or CNA02 OFF ON Forced stop ON OFF Normal Pulse CNA01 or CNA02 Ch1 OFF ON Forced stop Ch2 OFF ON Normal When the forced ...

Страница 12: ...g for indoor unit Set the DIP switch SET3 SW1 2 referring to the figure and table below SET3 10 IU AD 1 10 REF AD 1 SET4 DIP switch SET3 SW 1 SW 2 SW 3 SW 4 ON OFF DIP switch SET3 DIP switch SET3 Custom code A Factory setting B C D SW1 OFF ON OFF ON SW2 OFF OFF ON ON 7 3 Function setting FUNCTION SETTING can be performed with the wired or wireless remote controller The remote controller is optiona...

Страница 13: ...9 4 5 C Forbidden 71 00 Forbidden 72 00 Forbidden 73 00 Forbidden 74 00 Forbidden 75 00 8 GRILLE INSTALLATION Operate according to the installation manual of the grille Be sure to confirm there is no gap between the grille and indoor unit after installing the grille 9 TEST RUN 9 1 Test run using Outdoor unit PCB Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit ...

Страница 14: ...r error 3 10 Indoor unit communication circuit wired remote control ler error 4 1 Indoor unit room temp therm istor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor unit miscellaneous error 10 8 Poor refrigerant circulation 13 1 RB unit error Display mode 0 5 s ON 0 5 s...

Отзывы: