En-6

4.3.3. Pipe connection

 

CAUTION

Be sure to install the pipe against the port on the indoor unit correctly. If the centering 
is improper, the flare nut cannot tighten smoothly. If the flare nut is forced to turn, the 
threads will be damaged.

Do not remove the flare nut from the indoor unit pipe until immediately before connect-
ing the connection pipe.

Hold the torque wrench at its grip, keeping at the right angle with the pipe, in order to 
tighten the flare nut correctly.

Tighten the flare nuts with a torque wrench using the specified tightening method. Other-
wise, the flare nuts could break after a prolonged period, causing refrigerant to leak and 
generate hazardous gas if the refrigerant comes into contact with a flame.

When the flare nut is tightened 
properly by your hand, hold the body 
side coupling with a separate spanner, 
then tighten with a torque wrench. 
(See the table below for the flare nut 
tightening torques.)

Tighten with 
2 wrenches.

Holding 
wrench

Flare nut 

Connection pipe

Torque wrench

Indoor unit pipe 
(body side)

Flare nut [in (mm)]

Tightening torque [lbf·ft (N·m)]

1/4 (6.35) dia.

11.8 to 13.3 (16 to 18)

3/8 (9.52) dia.

23.6 to 31.0 (32 to 42)

1/2 (12.70) dia.

36.1 to 45.0 (49 to 61)

5/8 (15.88) dia.

46.5 to 55.3 (63 to 75)

3/4 (19.05) dia.

66.4 to 81.1 (90 to 110)

4.4. Installing heat insulation

Install the heat insulation material after performing a refrigerant leak check (see the Instal-
lation Manual for the outdoor unit for details).

4.4.1. Coupler heat insulation

• Insulate by the coupler heat insulation 

(accessories) around the gas pipe and 
liquid pipe of indoor side.

• After installing the coupler heat insula-

tion, wrap both end with vinyl tape so 
that there is no gap.

• After affixing the coupler heat insula-

tion, secure it with 2 cable ties (large), 
one on each end of the insulation.

• Make sure that the cable ties overlap 

the heat insulation pipe.

Coupler heat 
insulation 
(accessories)

Cover this portion with 
heat insulation.

cable tie (large) 
(accessories)

Heat insulation

 CAUTION

After checking for gas leaks (refer to the Installation Manual of the outdoor unit), per-
form this section.

Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to do 
so may cause water leaks.

5. INSTALLING DRAIN PIPES

Use general hard polyvinyl chloride pipe and connect it with adhesive (polyvinyl chloride) 
so that there is no leakage.
Always heat insulate the indoor side of the drain hose.
Use a drain hose that matches the size of the drain pipe.
• Do not perform a rise, trap and air bleeding.
• Provide a downward gradient (1/100 or more).
• Provide supporters when long pipes are installed.
• Use an insulation material as needed, to prevent the pipes from freezing.
• Install the pipes in a way that allows for the removal of the control box.

(Right side) 

Unit: in (mm)

Liquid pipe

Drain port

Gas pipe

9-7/16 (240)

1-1/4 (32)

2-5/8 (66)

4-1/2 (1

14)

(Left side) Unit: in (mm)

Drain port
The drain cap is attached at 
the factory setting.

1-1/4 (32)

9-7/16 (240)

Pipe size

Drain pipe

Φ 3/4 in (19 mm) [I.D.], 

Φ 1-1/16 in (27 mm) [O.D.]

• When the unit is shipped from the factory, the drain port is on the right side (control box 

side).

• When using the drain port on the left side of the unit, reinstall the drain cap to the right 

side drain port.

Drain port

Drain cap

Cable tie (large) 
(accessories)

• Cover the drain cap with the drain hose insulation.

Drain hose insulation (accessories)

Unit

Unit

Drain hose insula-
tion (accessories)

Drain cap

0 in (0 mm)

Install the drain hose

Working procedure
(1)  Install the attached drain 

hose to the drain port of the 
body. Install the hose band 
from the top of the hose 
within the graphic display 
area. Secure firmly with the 
hose band.

  

Ensure there is no space

Hose band 
(accessories)

Soft PVC side

Drain hose 
(accessories)

Drain pan

3/8 to 9/16 
(10 to 15)

Unit: in (mm)

(2)  Use vinyl adhesive agent to 

glue the drain piping (PVC pipe) 
[Φ 3/4 in (19 mm) I.D. Φ 1-1/16 
in (27 mm) O.D.] which is pre-
pared on site or socket. (Apply 
color adhesive agent evenly 
until the gauge line and seal)

Hard PVC 
side

Applying 
area of 
adhesive 

Joint pipe 
(locally purchased)

Drain pipe (locally 
purchased)
Φ 3/4 (19) [I.D.], 
Φ 1-1/16 (27) [O.D.]

0.16 (4) or less

Unit: in (mm)

(3)  Check the drainage. 
(4)  Install the heat insulation.
(5)  Use the attached heat insulation to insulate the drain port and band parts of the 

body.

Wrap the Drain hose insulation around 
the drain hose connection.

  

  

Drain pan

Drain hose

3-15/16 

(100)

Drain hose insula-
tion (accessories)

Unit: in (mm)

9373385264-02_IM_L3.indb   Sec1:6

9373385264-02_IM_L3.indb   Sec1:6

9/24/2019   11:06:29 AM

9/24/2019   11:06:29 AM

Содержание Airstage ARUM24TLAV2

Страница 1: ...e For authorized service personnel only MANUEL D INSTALLATION UNITÉ INTÉRIEURE type conduit Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN UNIDAD INTERIOR Tipo conducto Únicamente para personal de servicio autorizado 9373385264 02_IM_L3 indb 1 9373385264 02_IM_L3 indb 1 9 24 2019 11 06 28 AM 9 24 2019 11 06 28 AM ...

Страница 2: ...ng Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the customer using the operating manual DANGER Never touch electrical components immediately after the power supply has been turned off Electrical shock ...

Страница 3: ...acuum pump can be used by installing a vacuum pump adapter Be sure that the pump oil does not backflow into the system Use one capable for vacuum suction of 500 microns 100 7 kPa Gas leakage detector Special gas leakage detector for HFC refrigerant R410A 2 3 Accessories WARNING For installation purposes be sure to use the parts supplied by the manufacturer or other prescribed parts The use of non ...

Страница 4: ...as Install the unit where drainage does not cause any trouble Install the indoor unit power supply cable transmission cable and remote controller cable at least 40 in 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 40 in 1 m apart you could still receive noise under some signal conditions ...

Страница 5: ... exchanger may be clogged and its performance may decrease WARNING When fastening the hangers make the bolt positions uniform The distance of is adjustable according to the place of the hanging bolts MAX 21 5 8 in 550 mm MIN 16 1 8 in 410 mm Slide the unit in the arrow direction and fasten it Hanging bolt M10 locally purchased Special nut A accessories Washer locally purchased Special nut B access...

Страница 6: ...the humidity level at the installation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant piping If the expected humidity level is 70 to 80 use heat insulation that is 9 16 in 15 mm or thicker and if the expected humidity exceeds 80 use heat insulation that is 13 16 in 20 mm or thicker If heat insulation is used that is not as thick as specif...

Страница 7: ... pipes Failure to do so may cause water leaks 5 INSTALLING DRAIN PIPES Use general hard polyvinyl chloride pipe and connect it with adhesive polyvinyl chloride so that there is no leakage Always heat insulate the indoor side of the drain hose Use a drain hose that matches the size of the drain pipe Do not perform a rise trap and air bleeding Provide a downward gradient 1 100 or more Provide suppor...

Страница 8: ...by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard CAUTION Earth Ground the unit Do not connect the earth ground cable to a gas pipe water pipe lightning rod or a telephone earth ground cable Improper earthing grounding may cause electric shock Do not connect power supply cables to the transmission or remote controller terminals as this will damage the ...

Страница 9: ... pressure bonding may malfunction and cause the cables to abnormally heat up B For strand wiring 1 Use ring terminals with insulating sleeves as shown in the figure below to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate tool so that the cables do not come loose 3 Use the specified cables connect them securely and fasten them so that there is n...

Страница 10: ...tact terminal CNA04 DIP switch SET 2 SW2 Input signal type switching CNB01 Output terminal For external output CN8 For Remote sensor unit 1 CN48 For IR receiver unit 1 CN65 For one of the following MODBUS convertor 1 Wireless LAN adapter 1 CNA05 For Drain pump unit 1 CN106 CN820 For External power supply unit 1 1 For details refer to each installation manual 6 5 2 Power indicator lamp status Power...

Страница 11: ...CNA03 When a power supply must be provided at the input device you want to connect use the Apply voltage terminal CNA01 CNA03 a b 1 CNA01 CNA03 a a Input device 1 Input device 2 Input device 3 Load resistance Load resistance Load resistance DC power supply 12 to 24 V Connected unit P C B 1 Make the power supply DC 12 to 24 V Select a power supply capacity with an ample surplus for the connected lo...

Страница 12: ...nected unit P C B When connecting with unit equipped with a power supply CNB 01 P C B Connected device 1 Connected device 2 Connected device 3 Connected device 4 Connected unit Relay locally purchased Operation behavior If function setting 60 is set to 00 Connector Output voltage Status CNB01 External output 1 Pins 1 2 0 V Stop DC 12 V Operation External output 2 Pins 1 3 0 V Normal DC 12 V Error ...

Страница 13: ...Rotary switch setting Address Rotary switch setting Refrigerant circuit REF AD SW Indoor unit IU AD SW 10 1 10 1 0 0 0 0 0 0 1 0 1 1 0 1 2 0 2 2 0 2 3 0 3 3 0 3 4 0 4 4 0 4 5 0 5 5 0 5 10 1 0 10 1 0 11 1 1 11 1 1 99 9 9 63 6 3 7 2 Custom code setting Selecting the custom code prevents the indoor unit mix up Up to 4 codes can be set Perform the setting for both the indoor unit and the remote contro...

Страница 14: ... filter cleaning interval notification If the notification is too early change to setting 01 If the notification is too late change to setting 02 01 Longer 02 Shorter Filter indica tor action 13 00 Enable Enable or disable the filter indica tor Setting 02 is for use with a central remote controller 01 Disable 02 Display only on central remote controller Forbidden 20 00 Forbidden 23 00 Forbidden 24...

Страница 15: ... F 0 5 C t 1 8 F 1 C t 0 F 0 C 08 t 3 6 F 2 C t 0 9 F 0 5 C t 3 6 F 2 C t 0 F 0 C 09 t 5 4 F 3 C t 0 9 F 0 5 C t 5 4 F 3 C t 0 F 0 C 10 t 7 2 F 4 C t 0 9 F 0 5 C t 7 2 F 4 C t 0 F 0 C 11 t 9 0 F 5 C t 0 9 F 0 5 C t 9 0 F 5 C t 0 F 0 C 12 t 5 4 F 3 C t 0 F 0 C t 0 9 F 0 5 C t 0 9 F 0 5 C 13 t 3 6 F 2 C t 0 F 0 C t 1 8 F 1 C t 0 9 F 0 5 C 14 t 3 6 F 2 C t 0 F 0 C t 3 6 F 2 C t 0 9 F 0 5 C 15 t 5 4 F...

Страница 16: ...or 4 1 Indoor unit room temp therm istor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor unit miscellaneous error 10 8 Poor refrigerant circulation 13 1 RB unit error Display mode 0 5 s ON 0 5 s OFF 0 1 s ON 0 1 s OFF Number of flashing Wired Remote Controller Display ...

Отзывы: