6.3. Unit wiring

Before attaching the cable to terminal block.

6.3.1. Power supply cable

Adjust the length of power supply cable to avoid excessive tension with referring 

fi

 gure below.

For U.S.A. and Canada

Earth 
(Ground) 
wire

1-31/32 in.
(25 mm)

Conduit connector

1-31/32 in.
(25 mm)

2-15/16 in. 
(75 mm)

2-15/16 in. 
(75 mm)

For Others

Earth (Ground) 
wire

1-25/32 in. (45 mm)

1-25/32 in. (45 mm)

A. For solid core wiring

(1)  To connect the electrical terminal, follow the below diagram and connect after looping 

it around the end of the cable.

(2)  Use the speci

fi

 ed cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(3)  Use an appropriate screwdriver to tighten the terminal screws. Do not use a 

screwdriver that is too small, otherwise, the screw heads may be damaged and 
prevent the screws from being properly tightened.

(4)  Do not tighten the terminal screws too much, otherwise, the screws may break.
(5)  See the table for the terminal screw tightening torques.
(6)  Please do not 

fi

 x 2 power supply cables with 1 screw.

Loop

Screw with 
special washer

Screw with 
special washer

Cable end (Loop)

Cable end (Loop)

Cable

Cable

Terminal block

Strip 31/32 in.

(25 mm)

 

 

WARNING

When using solid core cables, do not use the ring terminal. If you use the solid core 
cables with the ring terminal, the ring terminal’s pressure bonding may malfunction 
and cause the cables to abnormally heat up.

B. For strand wiring

(1)  Use ring terminals with insulating sleeves as shown in the 

fi

 gure below to connect to 

the terminal block.

(2)  Securely clamp the ring terminals to the cables using an appropriate tool so that the 

cables do not come loose.

(3)  Use the speci

fi

 ed cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws. Do not use a 

screwdriver that is too small, otherwise, the screw heads may be damaged and 
prevent the screws from being properly tightened.

(5)  Do not tighten the terminal screws too much, otherwise, the screws may break.
(6)  See the table for the terminal screw tightening torques.
(7)  Please do not 

fi

 x 2 power supply cables with 1 screw.

 Sleeve

Screw with 
special washer

Screw with 
special washer

Ring terminal

Cable

Cable

Terminal block

Ring terminal

Ring terminal

Strip 13/32 in.  

(10 mm)

 

 

WARNING

Use ring terminals and tighten the terminal screws to the speci

fi

 ed torques, otherwise, 

abnormal overheating may be produced and possibly cause heavy damage inside the 
unit.

Tightening torque

M4 screw (Power supply/L1, L2 (N), GND)

11 to 16 lbf·in (1.2 to 1.8 N·m)

6.3.2. Transmission and Remote controller cable

 

Shielded wire 

(no 

fi

 lm)

1-9/16 in. (40 mm)

1-3/16 in. (30 mm)

Transmission cable

Y1

1-9/16 in. (40 mm)

1-3/16 in. (30 mm)

Remote controller cable

Y1: Red
Y2: White
Y3: Black

Y2

Y3

•  Connect remote controller and transmission cables as shown in Fig. B.
•  When the 2 cables are attached.

Fig. B

Good

Prohibited

Prohibited

Different diameter

Connect to 1 side

 

 

WARNING

Tighten the terminal screws to the speci

fi

 ed torques, otherwise, abnormal overheating 

may be produced and possibly cause heavy damage inside the unit.

Tightening torque

M3 screw (Transmission/X1, X2) 

(Remote controller/Y1, Y2, Y3)

4.4 to 5.3 lbf·in (0.5 to 0.6 N·m)

 

 

CAUTION

To peel the 

fi

 lm from the lead cable, use a dedicated tool that will not damage the 

conductor cable.

When installing a screw on the terminal block, do not cut the cable by overtightening 
the screw. On the other hand, an under tightened screw can cause faulty contact, which 
will lead to a communication failure.

9367702091-02_IM.indb   En-9

9367702091-02_IM.indb   En-9

12/29/2011   8:57:45 AM

12/29/2011   8:57:45 AM

Содержание Airstage ABUA30RLAV

Страница 1: ...E INTERIOR Tipo teto For authorized service personnel only Uniquement réservé aux techniciens agréés Sólo para personal de mantenimiento autorizado Apenas para técnicos de assistência autorizados PART NO 9367702091 02 Português Español Français English ABUA30RLAV ABUA36RLAV 9367702091 02_IM indb cover1 9367702091 02_IM indb cover1 12 29 2011 8 57 26 AM 12 29 2011 8 57 26 AM ...

Страница 2: ...er OFF at the main circuit breaker panel before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the customer using the operating manual D...

Страница 3: ...conventional R22 vacuum pump can be used by installing a vacuum pump adapter Be sure that the pump oil does not backflow into the system Use one capable for vacuum suction of 5 Torr 755 mmHg 100 7 kPa Gas leakage detector Special gas leakage detector for R410A refrigerant 1 2 3 Accessories WARNING For installation purposes be sure to use the parts supplied by the manufacturer or other prescribed p...

Страница 4: ...t on a place having a sufficient strength so that it withstands against the weight of the indoor unit 2 The inlet and outlet ports should not be obstructed the air should be able to blow all over the room 3 Leave the space required to service the air conditioner 4 Install the unit where connection to the outdoor unit is easy 5 Install the unit where the connection pipe can be easily installed 6 In...

Страница 5: ...32 in 10 to 15 mm 3 3 6 Installing the indoor unit 1 Lift unit so that suspension bolts pass through the suspension fittings at the sides 4 places and slide the unit back Ceiling Wall 3 3 3 Location of ceiling suspension bolts Fig A 1 3 16 30 Suspension bolt pitch 5 ft 3 in 1 600 1 3 16 30 Dimensions Space required for Installation 13 32 10 5 29 32 150 11 13 16 300 INDOOR UNIT TOP VIEW Unit in mm ...

Страница 6: ...nd both the gas and liquid pipes Failure to do so may cause water leaks Use heat insulation with heat resistance above 248 F 120 C Reverse cycle model only In addition if the humidity level at the installation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant piping If the expected humidity level is 70 to 80 use heat insulation that is 19 32...

Страница 7: ...re nut from the indoor unit pipe until immediately before connecting the connection pipe Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units 1 4 4 Installing heat insulation Install the heat insulation material after performing a refrigerant leak check see the Instal lation Manual for the outdoor unit for details COU...

Страница 8: ...up Prohibited Prohibited 1 Install insulation for the drain pipe Assemble as described below Drain port Assemble Drain hose Accessories and Hose band Accessories to Drain port Hose band Accessories Drain hose Accessories Soft PVC side Drain hose Accessories 13 32 to 19 32 in 10 to 15 mm Hose Band Accessories Soft PVC side Ensure there is no space Drain pan Wrap the drain hose insulation around the...

Страница 9: ...ct power supply cables to the transmission or remote controller terminals as this will damage the product Never bundle the power supply cable and transmission cable remote controller cable together Separate these cable by 1 31 32 in 50 mm or more Bundling these cables together will cause miss operation or breakdown When handling PCB static electricity charged in the body may cause malfunction of t...

Страница 10: ...here is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise the screw heads may be damaged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may break 6 See the table for the terminal screw tightening torques 7 Please do not fix 2 ...

Страница 11: ...ble line Input selection Use either one of these types of terminal according to the application Both types of terminals cannot be used simultaneously Voltage terminal CN6 When a power supply must be provided at the input device you want to connect use the voltage terminal CN6 1 2 3 Input device 1 Input device 2 Load resis tance Load resis tance 1 DC power supply 12 to 24 V Connected unit a a P C B...

Страница 12: ...unit stops and Start Stop operation by a remote controller is restricted When forced stop function is used with forming a remote controller group connect the same equipment to each indoor unit within the group Selection method of functions Start Stop mode or Emergency stop mode Forced stop mode can be selected with function setting of indoor unit 2 External output terminals When picking up output ...

Страница 13: ...n OFF the power before performing the field setting 1 7 1 Setting the address Manual address setting method The indoor unit address and the refrigerant circuit address can also be set up through the wireless remote controller CAUTION Use an insulated screwdriver to set the dip switches Rotary switch Example 0 Rotary switch Example 0 Setting Setting range Type of switch Indoor unit address 0 to 63 ...

Страница 14: ...to make sure no wiring mistakes were made before turning on the power Function details Function Function number Setting number Default Details Filter indicator interval 11 00 Default Adjust the filter cleaning interval notification If the notification is too early change to setting 01 If the notification is too late change to setting 02 01 Longer 02 Shorter Filter indicator action 13 00 Enable Ena...

Страница 15: ...on address 00 to 99 For use with a remote controller set all rotary switches to 0 and refer to 7 1 Setting the address for details All switches are set to 0 at the factory 2 Others Indication pattern Indicator Name Indication pattern OPERATION indicator lamp Green Function number tens place 0 5s ON 0 5s OFF TIMER indicator lamp Orange Function number ones place 0 5s ON 0 5s OFF FILTER indicator la...

Страница 16: ... refrigerant pipes No cooling No heating Has heat insulation work been completed Water leakage Does water drain eas ily from the indoor units Water leakage Is the voltage of the power source the same as that indicated on the label on the indoor unit No operation heat or burn damage Are the wires and pipes all connected completely No operation heat or burn damage Is the indoor unit earthed grounded...

Отзывы: