background image

En-5

Ceiling panel

Wall

INDOOR UNIT

(2)   Fasten the indoor unit into place by tightening-up the special “B” bolts and the M10 

nuts. Make sure that unit is secure and will not shift back and forth.

[For Half-Concealed Installation]

When installing the indoor unit in a semi-concealed orientation, make sure to reinforce the 
insulation (

fi

 eld supply) of the unit on all sides. Drops of water may fall from the unit if it is 

not thoroughly insulated.

INDOOR UNIT

(Top view)

Wall

Ceiling panel

Glass wool insulate (Field supply) 
(13/32 to 25/32 in. (10 to 20 mm) thick)

 CAUTION

In order to check the drainage, be sure to use a level during installation of the indoor 
unit. If the installation site of the indoor unit is not level, water leakage may occur.

4. PIPE INSTALLATION

]

 CAUTION

Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with 
refrigerant R410A models. Also, when storing the piping, securely seal the openings 
by pinching, taping, etc.

While welding the pipes, be sure to blow dry nitrogen gas through them.

]1

4.1. Selecting the pipe material

 CAUTION

Do not use existing pipes from another refrigeration system or refrigerant.

Use pipes that have clean external and internal sides without any contamination which 
may cause trouble during use, such as sulfur, oxide, dust, cutting waste, oil, or water.

It is necessary to use seamless copper pipes.
Material : Phosphor deoxidized seamless copper pipes
It is desirable that the amount of residual oil is less than 0.04 oz /100 ft. (40 mg /10 m).

Do not use copper pipes that have a collapsed, deformed, or discolored portion 
(especially on the interior surface). Otherwise, the expansion valve or capillary tube 
may become blocked with contaminants.

Improper pipe selection will degrade performance. As an air conditioner using R410A 
incurs pressure higher than when using conventional (R22) refrigerant, it is necessary 
to choose adequate materials.

•  Thicknesses of copper pipes used with R410A are as shown in the table.
•  Never use copper pipes thinner than those indicated in the table even if they are 

available on the market.

Thicknesses of Annealed Copper Pipes (R410A)

Pipe outside diameter [in. (mm)]

Thickness [in. (mm)]

1/4 (6.35)

0.032 (0.80)

3/8 (9.52)

0.032 (0.80)

1/2 (12.70)

0.032 (0.80)

5/8 (15.88)

0.039 (1.00)

3/4 (19.05)

0.047 (1.20)

1

4.2. Pipe requirement

 CAUTION

Refer to the Installation Manual of the outdoor unit for description of the length of 
connecting pipe or for difference of its elevation.

Use pipe with water-resistant heat insulation.

• 

 CAUTION

Install heat insulation around both the gas and liquid pipes. Failure to do so may 
cause water leaks. 
Use heat insulation with heat resistance above 248°F (120°C). (Reverse cycle model only) 
In addition, if the humidity level at the installation location of the refrigerant piping is 
expected to exceed 70 %, install heat insulation around the refrigerant piping. 
If the expected humidity level is 70 to 80 %, use heat insulation that is 19/32 in. 
(15 mm) or thicker and if the expected humidity exceeds 80 %, use heat insulation 
that is 25/32 in. (20 mm) or thicker. If heat insulation is used that is not as thick as 
speci

fi

 ed, condensation may form on the surface of the insulation. 

In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less 
(at 68°F (20°C)).

1

4.3. Flare connection (pipe connection)

4.3.1. Flaring

Use special 

fl

 are tool exclusive for R410A.

(1)  Cut the connection pipe to the necessary length with a pipe cutter.
(2)  Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs.
(3) Insert 

the 

fl

 are nut (always use the 

fl

 are nut attached to the indoor and outdoor units 

respectively) onto the pipe and perform the 

fl

 are processing with a 

fl

 are tool. Use 

the special R410A 

fl

 are tool. Leakage of refrigerant may result if other 

fl

 are nuts are 

used.

(4)  Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from 

entering the pipes.

L

Check if [L] is 

fl

 ared uniformly 

and is not cracked or scratched.

Die

Pipe

A

B

Pipe outside diameter 

[in. (mm)]

Dimension A [in. (mm)]

 0 

(0)

Dimension

 

B

-0.015 (-0.4)

[in. (mm)]

Flare tool for R410A, 

clutch type

1/4 (6.35)

0 to 0.020

(0 to 0.5)

11/32 (9.1)

3/8 (9.52)

17/32 (13.2)

1/2 (12.70)

21/32 (16.6)

5/8 (15.88)

25/32 (19.7)

3/4 (19.05)

15/16 (24.0)

When using conventional (R22) 

fl

 are tools to 

fl

 are R410A pipes, the dimension A should 

be approximately 0.020 in. (0.5 mm) more than indicated in the table (for flaring with 
R410A 

fl

 are tools) to achieve the speci

fi

 ed 

fl

 aring. Use a thickness gauge to measure the 

dimension A. It is recommended that a R410A 

fl

 aring tool is used.

Pipe outside diameter 

[in. (mm)]

Width across flats of Flare nut 

[in. (mm)]

1/4 (6.35)

21/32 (17)

3/8 (9.52)

7/8 (22)

1/2 (12.70)

1-1/32 (26)

5/8 (15.88)

1-5/32 (29)

3/4 (19.05)

1-13/32 (36)

4.3.2. Bending pipes

The pipes are shaped by your hands or pipe bender. Be careful not to collapse them.

• 

Do not bend the pipes in an angle more than 90°.

• 

When pipes are repeatedly bend or stretched, the material will harden, making it dif

fi

 cult 

• 

to bend or stretch them any more. Do not bend or stretch the pipes more than 3 times.

 

CAUTION

To prevent breaking of the pipe, avoid sharp bends. 

If the pipe is bent repeatedly at the same place, it will break.

Width across 

fl

 ats

9367702091-02_IM.indb   En-5

9367702091-02_IM.indb   En-5

12/29/2011   8:57:43 AM

12/29/2011   8:57:43 AM

Содержание Airstage ABUA30RLAV

Страница 1: ...E INTERIOR Tipo teto For authorized service personnel only Uniquement réservé aux techniciens agréés Sólo para personal de mantenimiento autorizado Apenas para técnicos de assistência autorizados PART NO 9367702091 02 Português Español Français English ABUA30RLAV ABUA36RLAV 9367702091 02_IM indb cover1 9367702091 02_IM indb cover1 12 29 2011 8 57 26 AM 12 29 2011 8 57 26 AM ...

Страница 2: ...er OFF at the main circuit breaker panel before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the customer using the operating manual D...

Страница 3: ...conventional R22 vacuum pump can be used by installing a vacuum pump adapter Be sure that the pump oil does not backflow into the system Use one capable for vacuum suction of 5 Torr 755 mmHg 100 7 kPa Gas leakage detector Special gas leakage detector for R410A refrigerant 1 2 3 Accessories WARNING For installation purposes be sure to use the parts supplied by the manufacturer or other prescribed p...

Страница 4: ...t on a place having a sufficient strength so that it withstands against the weight of the indoor unit 2 The inlet and outlet ports should not be obstructed the air should be able to blow all over the room 3 Leave the space required to service the air conditioner 4 Install the unit where connection to the outdoor unit is easy 5 Install the unit where the connection pipe can be easily installed 6 In...

Страница 5: ...32 in 10 to 15 mm 3 3 6 Installing the indoor unit 1 Lift unit so that suspension bolts pass through the suspension fittings at the sides 4 places and slide the unit back Ceiling Wall 3 3 3 Location of ceiling suspension bolts Fig A 1 3 16 30 Suspension bolt pitch 5 ft 3 in 1 600 1 3 16 30 Dimensions Space required for Installation 13 32 10 5 29 32 150 11 13 16 300 INDOOR UNIT TOP VIEW Unit in mm ...

Страница 6: ...nd both the gas and liquid pipes Failure to do so may cause water leaks Use heat insulation with heat resistance above 248 F 120 C Reverse cycle model only In addition if the humidity level at the installation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant piping If the expected humidity level is 70 to 80 use heat insulation that is 19 32...

Страница 7: ...re nut from the indoor unit pipe until immediately before connecting the connection pipe Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units 1 4 4 Installing heat insulation Install the heat insulation material after performing a refrigerant leak check see the Instal lation Manual for the outdoor unit for details COU...

Страница 8: ...up Prohibited Prohibited 1 Install insulation for the drain pipe Assemble as described below Drain port Assemble Drain hose Accessories and Hose band Accessories to Drain port Hose band Accessories Drain hose Accessories Soft PVC side Drain hose Accessories 13 32 to 19 32 in 10 to 15 mm Hose Band Accessories Soft PVC side Ensure there is no space Drain pan Wrap the drain hose insulation around the...

Страница 9: ...ct power supply cables to the transmission or remote controller terminals as this will damage the product Never bundle the power supply cable and transmission cable remote controller cable together Separate these cable by 1 31 32 in 50 mm or more Bundling these cables together will cause miss operation or breakdown When handling PCB static electricity charged in the body may cause malfunction of t...

Страница 10: ...here is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise the screw heads may be damaged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may break 6 See the table for the terminal screw tightening torques 7 Please do not fix 2 ...

Страница 11: ...ble line Input selection Use either one of these types of terminal according to the application Both types of terminals cannot be used simultaneously Voltage terminal CN6 When a power supply must be provided at the input device you want to connect use the voltage terminal CN6 1 2 3 Input device 1 Input device 2 Load resis tance Load resis tance 1 DC power supply 12 to 24 V Connected unit a a P C B...

Страница 12: ...unit stops and Start Stop operation by a remote controller is restricted When forced stop function is used with forming a remote controller group connect the same equipment to each indoor unit within the group Selection method of functions Start Stop mode or Emergency stop mode Forced stop mode can be selected with function setting of indoor unit 2 External output terminals When picking up output ...

Страница 13: ...n OFF the power before performing the field setting 1 7 1 Setting the address Manual address setting method The indoor unit address and the refrigerant circuit address can also be set up through the wireless remote controller CAUTION Use an insulated screwdriver to set the dip switches Rotary switch Example 0 Rotary switch Example 0 Setting Setting range Type of switch Indoor unit address 0 to 63 ...

Страница 14: ...to make sure no wiring mistakes were made before turning on the power Function details Function Function number Setting number Default Details Filter indicator interval 11 00 Default Adjust the filter cleaning interval notification If the notification is too early change to setting 01 If the notification is too late change to setting 02 01 Longer 02 Shorter Filter indicator action 13 00 Enable Ena...

Страница 15: ...on address 00 to 99 For use with a remote controller set all rotary switches to 0 and refer to 7 1 Setting the address for details All switches are set to 0 at the factory 2 Others Indication pattern Indicator Name Indication pattern OPERATION indicator lamp Green Function number tens place 0 5s ON 0 5s OFF TIMER indicator lamp Orange Function number ones place 0 5s ON 0 5s OFF FILTER indicator la...

Страница 16: ... refrigerant pipes No cooling No heating Has heat insulation work been completed Water leakage Does water drain eas ily from the indoor units Water leakage Is the voltage of the power source the same as that indicated on the label on the indoor unit No operation heat or burn damage Are the wires and pipes all connected completely No operation heat or burn damage Is the indoor unit earthed grounded...

Отзывы: