11. Electrical characteristics
Model name
AOYG14KBTA2
AOYG18KBTA2
Power supply
Voltage
V
230 ~
Frequency
Hz
50
Maximum operating current *
1
A
10.9
11.6
Starting current
A
4.7
5.6
Wiring spec. *
2
Main fuse (Circuit breaker) current
A
15
Power cable
mm
2
1.5
Connection
cable *
3
Cross-sectional area
1.5
Limited wiring length
m
21
*
1
: Maximum operating current is the total current of the indoor unit and the outdoor unit.
*
2
: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate de-
vices complied to the regional standard.
*
3
: This is the wiring length in case voltage descent is less than 2%. When the wiring length be-
comes longer, select the wiring of a more larger diameter.