6. PUMP DOWN

6.1. Pump down

PUMP DOWN OPERATION (FORCED COOLING OPERATION)

To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal, 
recover refrigerant by doing the forced cooling operation according to the following proce-
dure. 
(1)  Conduct preliminary operation for 5 to 10 minutes using the forced cooling operation. 

Start the forced cooling operation. Keep on pressing the MANUAL AUTO button of the 
indoor unit for more than 10 seconds. The operation indicator lamp and timer indicator 
lamp will begin to flash simultaneously during test run. (The forced cooling operation 
cannot start if the MANUAL AUTO button is not kept on pressing for more than 10 sec-
onds.)

(2)  Close the valve stem of 2-way valve completely.
(3)  Continue the forced cooling operation for 2 to 3 minutes, then close all the valve stems 

on the 3-way valves

(4)  Stop the operation.

• Press the START/STOP button of the remote controller to stop the operation.
•  Press the MANUAL AUTO button when stopping the operation from the indoor unit 

side. 
(It is not necessary to press down for more than 10 seconds.)

 CAUTION

Please check the refrigerant circuit for any leaks before starting the pump down 
operation.
Do not proceed with the pump down operation if there is no refrigerant left in the 
circuit due to bent or broken piping
During the pump down operation, be sure to turn off the compressor before 
removing the refrigerant piping.

9379069649_IM.indb   6

9379069649_IM.indb   6

12/8/2014   2:04:46 PM

12/8/2014   2:04:46 PM

Содержание 9RLS3H

Страница 1: ...rvicing Turn the power OFF at the main circuit breaker panel before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the customer using th...

Страница 2: ...r for HFC refrigerant R410A Copper pipes It is necessary to use seamless copper pipes and it is desirable that the amount of residual oil is less than 40 mg 10 m Do not use copper pipes having a collapsed deformed or discolored portion especially on the interior surface Otherwise the expansion value or capillary tube may become blocked with contaminants As an air conditioner using R410A incurs pre...

Страница 3: ...door temperature Cooling Dry Mode About 14 to 115 F Heating Mode About 15 to 75 F 2 7 Accessories Installation manual 1 One set of following parts are necessary installation of this product Name Connection pipe assembly Decorative tape Saddle Tapping screws Connection cable Vinyl tape M10 bold nut Sealant Wall pipe Wall cap 3 SELECTING THE MOUNTING POSITION Decide the mounting position with the cu...

Страница 4: ...will not be able to compress 1 Remove the tapping screw then remove the control box cover 2 Fasten the Inter unit wire harness and power supply to the conduit holder using the lock nut 3 Connect inter unit wire harness and power supply to the terminal 4 Use the tapping screw to install the control box cover NOTE Connector trade size for this unit is 1 2 12 7 mm The connector can be bought at a har...

Страница 5: ...ation in order to ensure compressor protection BENDING PIPES 1 When bending the pipe be careful not to crush it 2 To prevent breaking of the pipe avoid sharp bends Bend the pipe with a radius of curvature of 70 mm or over 3 If the copper pipe is bend the pipe or pulled to often it will become stiff Do not bend the pipes more than three times at one place Holding spanner 90 Body side Torque wrench ...

Страница 6: ...nnot start if the MANUAL AUTO button is not kept on pressing for more than 10 sec onds 2 Close the valve stem of 2 way valve completely 3 Continue the forced cooling operation for 2 to 3 minutes then close all the valve stems on the 3 way valves 4 Stop the operation Press the START STOP button of the remote controller to stop the operation Press the MANUAL AUTO button when stopping the operation f...

Отзывы: