background image

En-8

5.4. Flare connection (pipe connection)

 

CAUTION

Do not use mineral oil on a 

fl

 ared part. Prevent mineral oil from getting into the system 

as this would reduce the lifetime of the units.

While welding the pipes, be sure to blow dry nitrogen gas through them.

Flaring

(1)  Cut the connection pipe to the necessary length with a pipe cutter.
(2)  Hold the pipe downward so that cuttings will not enter the pipe and remove the 

burrs.

(3)   Insert the 

fl

 are nut onto the pipe and 

fl

 are the pipe with a 

fl

 aring tool.

Insert the 

fl

 are nut (always use the 

fl

 are nut attached to the indoor and outdoor 

units respectively) onto the pipe and perform the 

fl

 are processing with a 

fl

 are tool.

Use the special R32(R410A) 

fl

 are tool, or the conventional (for R22) 

fl

 are tool.

When using the conventional 

fl

 are tool, always use an allowance adjustment gauge and 

secure the A dimension shown in table 2.

Check if [L] is 

fl

 ared uniformly and 

is not cracked or scratched.

Die

A

Pipe

Pipe outside

diameter

A (mm)

Flaring tool for 

R32 or R410A, clutch type

Conventional (R22) Flaring tool

Clutch type

Wing nut type

ø 6.35 mm (1/4")

0 to 0.5

1.0 to 1.5

1.5 to 2.0

ø 9.52 mm (3/8")

ø 12.70 mm (1/2”)
ø 15.88 mm (5/8")
ø 19.05 mm (3/4”)

Bending pipes

(1)  When bending the pipe, be careful not to crush it.
(2)  To prevent breaking of the pipe, avoid sharp bends.
 

Bend the pipe with a radius of curvature of 70 mm or over.

(3)   If the copper pipe is bend the pipe or pulled to often, it will become stiff. Do not 

bend the pipes more than three times at one place.

Pipe connection

(1)  Detach the caps and plugs from the pipes.

 

CAUTION

Be sure to apply the pipe against the port on the indoor unit and the outdoor unit 
correctly. If the centering is improper, the 

fl

 are nut cannot be tightened smoothly. If the 

fl

 are nut is forced to turn, the threads will be damaged.

Do not remove the 

fl

 are nut from the indoor unit pipe until immediately before 

connecting the connection pipe.

(2)  Centering the pipe against port on the outdoor unit, turn the 

fl

 are nut with your 

hand.

To prevent gas leakage, 
coat the 

fl

 are surface with 

alkylbenzene oil (HAB). 
Do not use mineral oil.

(3) Tighten 

the 

fl

 are nut of the connection pipe at the outdoor unit valve connector.

Flare nut 

Connection pipe
(liquid) 

Connection pipe 
(gas) 

Flare nut 

3-way valve
(liquid)

3-way valve
(gas)

(5)  Do not tighten the terminal screws too much, otherwise, the screws may break.

Wire

Screw with special washer

Ring terminal

Terminal blocks

Screw with 
special washer 

Wire

Ring terminal

(6)  See the table below for the terminal screw tightening torques.

Tightening torque [N·m (kgf·cm)]

M4 screw

1.2 to 1.8 (12 to 18)

M5 screw

2.0 to 3.0 (20 to 30)

5.3. Wiring method

 

CAUTION

When connecting the power supply cable, make sure that the phase of the power 
supply matches with the phase of the terminal board. If the phases do not match, the 
compressor will rotate in reverse and will not be able to compress.

(1)

 

Remove the outdoor unit Switch cover A, B.(See “5.1. Switch cover remove”.)

(2)

 

Remove the outdoor unit cable clamp.

(3)

 

Connect the power supply cable and the connection cable to terminal.

(4)

 

Fasten the power supply cable and connection cable with cable clamp.

(5)

 

Install the Switch cover A, B.(See “5.1. Switch cover remove”.)

N

L

3

2

1

Screw

Cable clamp

5.3.1. Connection diagrams

3

1 2

N

L

3

1 2

Power supply

Power line

Earth(Ground) line

Outdoor unit side terminal 

Indoor unit side terminal

Earth
(Ground) line

EARTH
(GROUND)

EARTH
(GROUND)

5.3.2. Connection cable preparation

•  Keep the earth wire longer than the other wires.

Earth wire

30 mm

Power supply cable or 
Connection cable

35 mm

5.3.3. Connection cable wiring

10 mm

Connection and Power 
supply cable

Run the connection cable to the rear of 
the outdoor unit within the range of the 
arrows shown in the 

fi

 gure.

(The switch cover becomes dif

fi

 cult to 

install.)

Cutout

9319205151-04_IM.indb   8

9319205151-04_IM.indb   8

1/12/2017   11:49:08 AM

1/12/2017   11:49:08 AM

Содержание 9319205151-04

Страница 1: ... autorizado MANUALE D INSTALLAZIONE UNITÀ ESTERNA A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΞΩΤΕΡΙΚΗ ΜΟΝΑΔΑ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO UNIDADE EXTERIOR Semente para pessoal do serviço técnico autorizado РУКОВОДСТВО ПО УСТАНОВКЕ ВНЕШНИЙ МОДУЛЬ Только для авторизованного обслуживающего персонала KURULUM KILAVUZU DIŞ ÜNİTE Yalnızca...

Страница 2: ...ay damage the vacuum pump or the unit Use a clean gauge manifold and charging hose for R32 or R410A exclusively Do not use means to accelerate the defrosting process or to clean other than those recommended by the manufacturer The appliance shall be stored in a room without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do...

Страница 3: ...rant R410A R22 models However pay careful attention to the following points WARNING Since the working pressure is 1 6 times higher than that of refrigerant R22 models some of the piping and installation and service tools are special See 2 1 Special tools for R32 Especially when replacing a refrigerant R22 model with a new refrigerant R32 model always replace the conventional piping and flare nuts ...

Страница 4: ...ylinders conform to the appropriate standards d Pump down refrigerant system if possible e If a vacuum is not possible make a manifold so that refrigerant can be removed from various parts of the system f Make sure that cylinder is situated on the scales before recovery takes place g Start the recovery machine and operate in accordance with manufacturer s instructions h Do not overfill cylinders N...

Страница 5: ...ype60245 IEC57 3 wire Ground 1 Φ 230 V 1 Selected sample Select the correct cable type and size according to the country or region s regulations Max wire length Set a length so that the voltage drop is less than 2 Increase the wire diameter when the wire length is long Breaker capacity A Earth leakage breaker mA 09 type 16 30 12 type 20 Selected sample Select the correct cable type and size accord...

Страница 6: ... outlet ducts Install the outdoor unit in a location that is away from exhaust or the vent ports that discharge vapor soot dust or debris Install the indoor unit outdoor unit power supply cable connection cable and remote controller cable at least 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more...

Страница 7: ...tated above the condition will be the same as when there is no obstacle Height above the floor level should be 50 mm or more When installing the outdoor unit be sure to open the front and left side to obtain better operation efficiency 4 4 Installation Unit mm 570 340 Install 4 anchor bolts at the locations indicated with arrows in the above figure To reduce vibration do not install the unit direc...

Страница 8: ...if lightning strikes Improper grounding work can cause electric shocks Securely install the electrical box cover on the unit An improperly installed service panel can cause serious accidents such as electric shock or fire through exposure to dust or water Do not connect the AC power supply to the transmission line terminal board Improper wiring can damage the entire system CAUTION The primary powe...

Страница 9: ... damaged Do not remove the flare nut from the indoor unit pipe until immediately before connecting the connection pipe 2 Centering the pipe against port on the outdoor unit turn the flare nut with your hand To prevent gas leakage coat the flare surface with alkylbenzene oil HAB Do not use mineral oil 3 Tighten the flare nut of the connection pipe at the outdoor unit valve connector Flare nut Conne...

Страница 10: ...ease the nitrogen gas slowly 5 6 Vacuum process CAUTION Perform a refrigerant leakage test air tightness test to check for leaks using nitrogen gas while all valves in the outdoor unit are closed Use the test pressure indicated on the nameplate Be sure to evacuate the refrigerant system using a vacuum pump The refrigerant pressure may sometimes not rise when a closed valve is opened after the syst...

Страница 11: ...label Item Detail MODEL Model name Electric characteristics Rated voltage phase and frequency COOLING CAPACITY Cooling capacity under cooling condition CURRENT Electric current during cooling operation under cooling condition INPUT POWER Input during cooling operation under cooling condition ENERGY EFFICIENCY RATIO Ratio of output cooling energy to electrical input energy HEATING CAPACITY Heating ...

Отзывы: