background image

En-9

3.9. Electrical wiring

 

WARNING

•  Wiring connections must be performed by a qualified person in accordance with 

the specifications. The voltage rating for this product is 230 V at 50 Hz. It should be 
operated within the range of 198 to 264 V.

•  Before connecting the wires, make sure the power supply is off.
•  Never touch electrical components immediately after the power supply has been 

turned off. Electrical shock may occur. After turning off the power, always wait 

 

10 minutes or more before touching electrical components.

•  Use a dedicated power supply circuit. Insufficient power capacity in the electrical 

circuit or improper wiring may cause electric shock or fire.

•  Be sure to install an earth leakage breaker. 

 

Otherwise, it will cause electric shock or fire.

•  A circuit breaker is installed in the permanent wiring. Always use a circuit that can 

trip all the poles of the wiring and has an isolation distance of at least 1/8 in (3 mm) 
between the contacts of each pole.

•  Use designated cables and power cables. Improper use may cause electric shock 

or fire by poor connection, insufficient insulation, or over current.

•  Do not modify power cable, use extension cable or branch wiring. Improper use 

may cause electric shock or fire by poor connection, insufficient insulation or over 

current.

•  Connect the connector cable securely to the terminal. Check no mechanical force 

bears on the cables connected to the terminals. Faulty installation can cause a fire.

•  Use ring terminals and tighten the terminal screws to the specified torques, other

-

wise, abnormal overheating may be produced and possibly cause serious damage 

inside the unit.

•  Make sure to secure the insulation portion of the connector cable with the cable tie. 

Damaged insulation can cause a short circuit.

•  Fix cables so that cables do not make contact with the pipes (especially on high 

pressure side). Do not make power supply cable and transmission cable come in 
contact with valves (Gas).

•  Never install a power factor improvement condenser. Instead of improving the power 

factor, the condenser may overheat.

•  Be sure to perform the grounding work.

 

Do not connect grounding wires to a gas pipe, water pipe, lightning rod or grounding 
wire for a telephone.
•  Connection to a gas pipe may cause a fire or explosion if gas leaks.
•  Connection to a water pipe is not an effective grounding method if PVC pipe is used.
•  Connection to the grounding wire of a telephone or to a lightning rod may cause a 

dangerously abnormal rise in the electrical potential if lightning strikes.

•  Improper grounding work can cause electric shocks.

•  Securely install the electrical box cover on the unit. An improperly installed service 

panel can cause serious accidents such as electric shock or fire through exposure 
to dust or water.

•  Do not connect the AC power supply to the transmission line terminal board. Im

-

proper wiring can damage the entire system.

 

CAUTION

•  The primary power supply capacity is for the air conditioner itself, and does not 

include the concurrent use of other devices.

•  If the electrical power is inadequate, contact your electric power company.
•  Install a breaker in a location that is not exposed to high temperatures.

 

If the temperature surrounding the breaker is too high, the amperage at which the 
breaker cuts out may decrease.

•  When using an earth leakage breaker that has been designed solely for ground fault 

protection, be sure to install a fuse-equipped switch or circuit breaker.

•  This system uses an inverter, which means that it must be used an earth leakage 

breaker that can handle harmonics in order to prevent malfunctioning of the earth 
leakage breaker itself.

•  Do not use crossover power supply wiring for the outdoor unit.
•  If the temperature surrounding the breaker is too high, the amperage at which the 

breaker cuts out may decrease.

•  When the electrical switchboard is installed outdoors, place it under lock and key so 

that it is not easily accessible.

•  Start wiring work after closing branch switch and over current breaker.
•  Connection cable between indoor unit and outdoor unit is 230 V (single-phase).
•  Be sure not to remove thermistor sensor etc. from power wiring and connection wir

-

ing. Compressor may fail if operated while removed.

•  Do not fasten the power supply cable and connection cable together.
•  Always keep to the maximum length of the connection cable. Exceeding the maxi

-

mum length may lead to erroneous operation.

•  Do not start operation until the refrigerant is charged completely. The compressor 

will fail if it is operated before the refrigerant piping charging is complete.

•  The static electricity that is charged to the human body can damage the control PC 

Board when handling the control PC Board for address setting, etc.

 

Please keep caution to the following points.

 

Provide the grounding of Indoor unit, Outdoor unit and Option equipment.

 

Cut off the power supply (breaker).

 

Touch the metal section (such as the unpainted control box section) of the indoor or 
outdoor unit for more than 10 seconds. Discharge the static electricity in your body.

 

Never touch the component terminal or pattern on the PC Board.

•  Be careful not to generate a spark as follows for using a flammable refrigerant.

 -

Do not remove the fuse while power is on.

 -

Do not disconnect plug from the wall outlet and the wiring while the power is on.

 -

It is recommended to position the outlet connection in a high position. Place the 

cords so that they do not get tangled.

•  Confirm the indoor unit model name before connecting.

3.9.1. How to connect wiring to the terminal

 Caution when wiring cable 

•  When stripping off the coating of a lead wire, always use a special tool such as a wire 

stripper. If there is no special tool available, carefully strip the coating with a knife etc.

(1)  Use ring terminals with insulating sleeves as shown in the figure below to connect 

to the terminal block.

(2)  Securely clamp the ring terminals to the wires using an appropriate tool so that the 

wires do not come loose.

Sleeve

Strip : 3/8 in (10 mm)

Ring 

terminal

(3)  Use the specified wires, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws. Do not use a 

screwdriver that is too small, otherwise, the screw heads may be damaged and 
prevent the screws from being properly tightened.

(5)  Do not tighten the terminal screws too much, otherwise, the screws may break.

Wire

Screw with special washer

Ring

 terminal

Terminal blocks

Screw with 

 

special washer 

Wire

Ring 

terminal

(6)  Refer to the table below for the terminal screw tightening torques.

Tightening torque [lbs·in (N·m)]

M4 screw

10.6 to 15.9 (1.2 to 1.8)

M5 screw

17.7 to 26.5 (2.0 to 3.0)

9379113069-02_IM.indb   9

6/11/2021   10:26:45 AM

Содержание 24LMAS1

Страница 1: ... a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run ins...

Страница 2: ...her than as liquid or gas When Servicing Turn the power OFF at the main circuit breaker panel before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct o...

Страница 3: ...re and dust Especially pay attention when passing the pipes through a hole or connecting the end of a pipe to the outdoor unit Location Working period Protection method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes 2 4 Power source WARNING Always use a special branch circuit and install a special receptacle to supply power to the room air cond...

Страница 4: ...e risk of the leakage of flammable gas in the vicinity Area where small animals may live It may cause failure smoke or fire if small animals enter and touch internal electrical parts Area where animals may urinate on the unit or ammonia may be generated Do not tilt the outdoor unit more than 3 degrees However do not install the unit with it tilted towards the side containing the compressor Install...

Страница 5: ... 500 or more 10 250 or more 3 Obstacles at front and rear 20 500 or more 60 1 500 or more 10 250 or more When an obstruction is present also in the upward area Unit in mm 1 Obstacles at rear and above Up to 3 units can be installed side by side When 4 units or more are arranged in a line provide the space as shown below 60 1 500 or more 20 500 or more 10 250 or more Max 11 300 60 1 500 or more 3 1...

Страница 6: ...cing is recommended when blowing and drifting snow is common to the region 3 4 Drain installation CAUTION Perform drain work in accordance with this Manual and ensure that the drain water is properly drained If the drain work is not carried out correctly water may drip down from the unit wetting the furniture When the outdoor temperature is 32 F 0 C or less do not use the accessory drain pipe If t...

Страница 7: ...s Bend the pipe with a radius of curvature of 3 15 16 in 100 mm to 5 7 8 in 150 mm If the pipe is bent repeatedly at the same place it will break If pipes are shaped by hand be careful not to collapse them Do not bend the pipes at an angle of more than 90 When pipes are repeatedly bent or stretched the material will harden making it difficult to bend or stretch them anymore Do not bend or stretch ...

Страница 8: ...he valves Use a hexagon wrench size 4 mm Opening 1 Insert the hexagon wrench into the valve shaft and turn it counterclockwise 2 Stop turning when the valve shaft can no longer be turned Open position Closing 1 Insert the hexagon wrench into the valve shaft and turn it clockwise 2 Stop turning when the valve shaft can no longer be turned Closed position Opening direction Hexagon wrench Seal blank ...

Страница 9: ... amperage at which the breaker cuts out may decrease When using an earth leakage breaker that has been designed solely for ground fault protection be sure to install a fuse equipped switch or circuit breaker This system uses an inverter which means that it must be used an earth leakage breaker that can handle harmonics in order to prevent malfunctioning of the earth leakage breaker itself Do not u...

Страница 10: ... supply matches with the phase of the terminal board If the phases do not match the compressor will rotate in reverse and will not be able to compress Connection diagrams L1 L2 Power supply Outdoor unit side terminal Indoor unit side terminal Power line Ground Earth Ground Earth Cable preparation Keep the ground earth wire longer than the other wires Ground Earth wire 1 9 16 in 40 mm Power supply ...

Страница 11: ...s will start operating Room temperature control will not activate during test operation continuous operation If a knocking sound can be heard in the liquid compression of the compressor stop the unit immediately and then energize the crank case heater for a sufficient length of time before restarting the operation 4 2 1 Setting method on outdoor unit board 1 Turn on the power of the outdoor unit a...

Страница 12: ...Y UNIT 6 1 Display unit position WARNING Never touch electrical components such as the terminal blocks except the button on the display board It may cause a serious accident such as electric shock CAUTION Once refrigerant charging is completed be sure to open the valve prior to performing the local settings Otherwise the compressor may fail Discharge any static electricity from your body before to...

Страница 13: ...ting performance may decrease Depending on the operating condition the noise level may not decrease even if the Low noise mode is on Level 2 Blink 9 times 2 Peak cut mode setting Level 1 Blink 9 times The capacity limit can be selected when operating with the Peak cut mode The operation selection can be done by external input connector PA580 The lower the level the more the effect of energy saving...

Страница 14: ... beginning of operation procedure after returning to Operation status displays normal operation by pressing the EXIT button once 8 EXTERNAL INPUT AND OUTPUT 8 1 External input 8 1 1 Wiring of connector On Off of the Low noise mode and Peak cut mode functions can be enabled with an external field device When installing connection cable specified part optional parts must be used Refer to section 7 2...

Страница 15: ...ical components such as the terminal blocks except the button on the display board It may cause a serious accident such as electric shock During the pump down operation make sure that the compressor is turned off before you remove the refrigerant piping Do not remove the connection pipe while the compressor is in operation with 2 way or 3 way valve open This may cause abnormal pressure in the refr...

Страница 16: ...L5 L6 Sign Lights off Lights on 3 Press PUMP DOWN button S130 for 3 seconds or more after 3 minutes after power on POWER MODE ERROR PUMP DOWN LOW NOISE PEAK CUT L1 L2 L3 L4 L5 L6 Sign Lights off Lights on LED display lights on as shown in the above table and the fans and the compressor start operating If the PUMP DOWN button S130 is pressed while the compressor is operating the compressor will sto...

Страница 17: ...Outdoor temp sensor error Outdoor temp sensor error Blink 2 times Blink 7 times Blink 4 times Heat sink temp sensor error Heat sink temp sensor error Blink 2 times Blink 7 times Blink 7 times Current sensor error Current sensor 1 error stoppage permanently Blink 2 times Blink 8 times Blink 4 times Pressure sensor error High pressure switch 1 error Blink 2 times Blink 8 times Blink 6 times Pressure...

Отзывы: