En-4

2.6. Additional charge amount

 CAUTION

When adding refrigerant, add the refrigerant from the charging port at the completion 

of work.

2.6.1. For Pre-charge length

Model

Piping length (L) *Pre-Charge [ft (m)]

18

49 (15)

24

66 (20)

2.6.2. If additional refrigerant is required

•  When the piping is longer than Pre-charge length, additional charging is necessary.
•  For the additional amount, refer to the following table.

Additional charging amount

L1 > Pre-charge length

Piping 

length

Model

49 ft 

 

(15 m)

66 ft 

 

(20 m)

99 ft 

 

(30 m)

131 ft

 

 (40 m)

165 ft 

 

(50 m)

Rate

Additional 

charge

18

None

7 oz

 

(200 g)

1 lb 5 oz

 

(600 g)

2 lb 3 oz

 

(1,000 g)

3 lb 1 oz

 

(1,400 g)

0.43 oz/ft

 

(40 g/m)

24

None

14 oz

 

(400 g)

1 lb 12 oz

 

(800 g)

2 lb 10 oz

 

(1,200 g)

0.43 oz/ft

 

(40 g/m)

2.7. General information

• 

If the unit is operated outside the operating temperature range, various protective 

circuit mechanisms may be activated and the unit may stop operating. For the 
operating temperature range, refer to the product FICHE or the specification manual.

3.  INSTALLATION WORK

Make sure to obtain the customer’s approval for selecting and installing the outdoor unit.

 WARNING

•  Securely install the outdoor unit at a location that can withstand the weight of the 

unit. Otherwise, the outdoor unit may fall and cause injury.

•  Be sure to install the outdoor unit as prescribed, so that it can withstand earthquakes 

and typhoons or other strong winds. Improper installation can cause the unit to topple 

or fall, or other accidents.

•  Do not install the outdoor unit near the edge of a balcony. Otherwise, children may 

climb onto the outdoor unit and fall off of the balcony.

 CAUTION

•  Do not install the outdoor unit in the following areas:

 -

Area with high salt content, such as at the seaside. It will deteriorate metal parts, 

causing the parts to fail or the unit to leak water.

 -

Area filled with mineral oil or containing a large amount of splashed oil or steam, 

such as a kitchen. It will deteriorate plastic parts, causing the parts to fail or the 

unit to leak water.

 -

Area that generates substances that adversely affect the equipment, such as 

sulfuric gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed 

joints to corrode, which can cause refrigerant leakage.

 -

Area containing equipment that generates electromagnetic interference. It will 

cause the control system to malfunction, preventing the unit from operating 

normally.

 -

Area that can cause combustible gas to leak, contains suspended carbon fibers or 

flammable dust, or volatile inflammables such as paint thinner or gasoline. If gas 

leaks and settles around the unit, it can cause a fire.

 -

Area that has heat sources, vapors, or the risk of the leakage of flammable gas in 

the vicinity.

 -

Area where small animals may live. It may cause failure, smoke or fire if small 

animals enter and touch internal electrical parts.

 -

Area where animals may urinate on the unit or ammonia may be generated.

•  Do not tilt the outdoor unit more than 3 degrees. However, do not install the unit with 

it tilted towards the side containing the compressor.

•  Install the outdoor unit in a well-ventilated location away from rain or direct sunlight.

•  If the outdoor unit must be installed in an area within easy reach of the general pub

-

lic, install as necessary a protective fence or the like to prevent their access.

•  Install the outdoor unit in a location that would not inconvenience your neighbors, as 

they could be affected by the airflow coming out from the outlet, noise, or vibration. If 

it must be installed in proximity to your neighbors, be sure to obtain their approval.

•  If the outdoor unit is installed in a cold region that is affected by snow accumulation, 

snow fall, or freezing, take appropriate measures to protect it from those elements. 

To ensure a stable operation, install inlet and outlet ducts.

•  Install the outdoor unit in a location that is away from exhaust or the vent ports that 

discharge vapor, soot, dust, or debris.

•  Install the indoor unit, outdoor unit, power supply cable, connection cable, and 

remote controller cable at least 40 in (1 m) away from a television or radio receivers. 

The purpose of this is to prevent TV reception interference or radio noise. (Even if 

they are installed more than 40 in (1 m) apart, you could still receive noise under 

some signal conditions.)

•  If children under 10 years old may approach the unit, take preventive measures so 

that they cannot reach the unit.

•  Keep the length of the piping of the indoor and outdoor units within the allowable 

range.

•  For maintenance purposes, do not bury the piping.

Decide the mounting position with the customer as follows:

(1) Install the outdoor unit in a location which can withstand the weight of the unit and 

vibration, and which can install horizontally.

(2) Provide the indicated space to ensure good airflow.
(3) If possible, do not install the unit where it will be exposed to direct sunlight.
  (If necessary, install a blind that does not interfere with the airflow.)
(4) Do not install the unit near a source of heat, steam, or flammable gas.
(5) During heating operation, drain water flows from the outdoor unit.
  Therefore, install the outdoor unit in a place where the drain water flow will not be 

obstructed.

(6) Do not install the unit where strong wind blows or where it is very dusty.
(7) Do not install the unit where people pass.
(8) Install the outdoor unit in a place where it will be free from being dirty or getting wet by 

rain as much as possible.

(9) Install the unit where connection to the indoor unit is easy.

9379113069-02_IM.indb   4

6/11/2021   10:26:36 AM

Содержание 24LMAS1

Страница 1: ... a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run ins...

Страница 2: ...her than as liquid or gas When Servicing Turn the power OFF at the main circuit breaker panel before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct o...

Страница 3: ...re and dust Especially pay attention when passing the pipes through a hole or connecting the end of a pipe to the outdoor unit Location Working period Protection method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes 2 4 Power source WARNING Always use a special branch circuit and install a special receptacle to supply power to the room air cond...

Страница 4: ...e risk of the leakage of flammable gas in the vicinity Area where small animals may live It may cause failure smoke or fire if small animals enter and touch internal electrical parts Area where animals may urinate on the unit or ammonia may be generated Do not tilt the outdoor unit more than 3 degrees However do not install the unit with it tilted towards the side containing the compressor Install...

Страница 5: ... 500 or more 10 250 or more 3 Obstacles at front and rear 20 500 or more 60 1 500 or more 10 250 or more When an obstruction is present also in the upward area Unit in mm 1 Obstacles at rear and above Up to 3 units can be installed side by side When 4 units or more are arranged in a line provide the space as shown below 60 1 500 or more 20 500 or more 10 250 or more Max 11 300 60 1 500 or more 3 1...

Страница 6: ...cing is recommended when blowing and drifting snow is common to the region 3 4 Drain installation CAUTION Perform drain work in accordance with this Manual and ensure that the drain water is properly drained If the drain work is not carried out correctly water may drip down from the unit wetting the furniture When the outdoor temperature is 32 F 0 C or less do not use the accessory drain pipe If t...

Страница 7: ...s Bend the pipe with a radius of curvature of 3 15 16 in 100 mm to 5 7 8 in 150 mm If the pipe is bent repeatedly at the same place it will break If pipes are shaped by hand be careful not to collapse them Do not bend the pipes at an angle of more than 90 When pipes are repeatedly bent or stretched the material will harden making it difficult to bend or stretch them anymore Do not bend or stretch ...

Страница 8: ...he valves Use a hexagon wrench size 4 mm Opening 1 Insert the hexagon wrench into the valve shaft and turn it counterclockwise 2 Stop turning when the valve shaft can no longer be turned Open position Closing 1 Insert the hexagon wrench into the valve shaft and turn it clockwise 2 Stop turning when the valve shaft can no longer be turned Closed position Opening direction Hexagon wrench Seal blank ...

Страница 9: ... amperage at which the breaker cuts out may decrease When using an earth leakage breaker that has been designed solely for ground fault protection be sure to install a fuse equipped switch or circuit breaker This system uses an inverter which means that it must be used an earth leakage breaker that can handle harmonics in order to prevent malfunctioning of the earth leakage breaker itself Do not u...

Страница 10: ... supply matches with the phase of the terminal board If the phases do not match the compressor will rotate in reverse and will not be able to compress Connection diagrams L1 L2 Power supply Outdoor unit side terminal Indoor unit side terminal Power line Ground Earth Ground Earth Cable preparation Keep the ground earth wire longer than the other wires Ground Earth wire 1 9 16 in 40 mm Power supply ...

Страница 11: ...s will start operating Room temperature control will not activate during test operation continuous operation If a knocking sound can be heard in the liquid compression of the compressor stop the unit immediately and then energize the crank case heater for a sufficient length of time before restarting the operation 4 2 1 Setting method on outdoor unit board 1 Turn on the power of the outdoor unit a...

Страница 12: ...Y UNIT 6 1 Display unit position WARNING Never touch electrical components such as the terminal blocks except the button on the display board It may cause a serious accident such as electric shock CAUTION Once refrigerant charging is completed be sure to open the valve prior to performing the local settings Otherwise the compressor may fail Discharge any static electricity from your body before to...

Страница 13: ...ting performance may decrease Depending on the operating condition the noise level may not decrease even if the Low noise mode is on Level 2 Blink 9 times 2 Peak cut mode setting Level 1 Blink 9 times The capacity limit can be selected when operating with the Peak cut mode The operation selection can be done by external input connector PA580 The lower the level the more the effect of energy saving...

Страница 14: ... beginning of operation procedure after returning to Operation status displays normal operation by pressing the EXIT button once 8 EXTERNAL INPUT AND OUTPUT 8 1 External input 8 1 1 Wiring of connector On Off of the Low noise mode and Peak cut mode functions can be enabled with an external field device When installing connection cable specified part optional parts must be used Refer to section 7 2...

Страница 15: ...ical components such as the terminal blocks except the button on the display board It may cause a serious accident such as electric shock During the pump down operation make sure that the compressor is turned off before you remove the refrigerant piping Do not remove the connection pipe while the compressor is in operation with 2 way or 3 way valve open This may cause abnormal pressure in the refr...

Страница 16: ...L5 L6 Sign Lights off Lights on 3 Press PUMP DOWN button S130 for 3 seconds or more after 3 minutes after power on POWER MODE ERROR PUMP DOWN LOW NOISE PEAK CUT L1 L2 L3 L4 L5 L6 Sign Lights off Lights on LED display lights on as shown in the above table and the fans and the compressor start operating If the PUMP DOWN button S130 is pressed while the compressor is operating the compressor will sto...

Страница 17: ...Outdoor temp sensor error Outdoor temp sensor error Blink 2 times Blink 7 times Blink 4 times Heat sink temp sensor error Heat sink temp sensor error Blink 2 times Blink 7 times Blink 7 times Current sensor error Current sensor 1 error stoppage permanently Blink 2 times Blink 8 times Blink 4 times Pressure sensor error High pressure switch 1 error Blink 2 times Blink 8 times Blink 6 times Pressure...

Отзывы: