4) Special register retain area (for expansion left side unit)
Address
Name
Description
Attribute
%MW3.62432
|
%MW3.62435
Not used
%MW3.62436
IP address (L)
Indicates the IP address of the self station.
R/W
%MW3.62437
IP address (H)
%MW3.62438
Subnet mask (L)
Indicates the subnet mask
R/W
%MW3.62439
Subnet mask (H)
%MW3.62440
Default gateway address (L)
Indicates the IP address of the default gateway
R/W
%MW3.62441
Default gateway address (H)
%MW3.62442
TCP sending and receiving
timeout value
Indicates the TCP sending timeout value.
R/W
%MW3.62443
Not used
%MW3.62444
Loader command watch timer
value
Indicates the timer to monitor access from the target station in the
loader command (server operation) mode.
R/W
%MW3.62445
Not used
%MW3.62446
Sending retry number of times Indicates the number of sending retries in TCP communication.
(Fixed to 8)
R/W
%MW3.62447
Close process during TCP
sending timeout
Not supported
%MW3.62448
Close process during
response receiving timeout
Not supported
%MW3.62449
Not used
%MW3.62450
Not used
%MW3.62451
Response watch timer value
Not supported
%MW3.62452
Loader command receive port
Indicates the port No. of the self station in the loader communication
(server operation) mode.
In the loader communication (client operation) mode,
the port No. of the self station = “Loader command receive port” +
“Internal socket No.” + 1.
R/W
%MW3.62453
Loader commend send port
Indicates the port No. of the target station in the loader
communication (client operation) mode.
R/W
%MW3.62454 Parameter setting request flag
Used to write the contents of the special register.
R/W
%MW3.62455
|
%MW3.62463
Not used