![Fuji Electric SPF Series Скачать руководство пользователя страница 35](http://html1.mh-extra.com/html/fuji-electric/spf-series/spf-series_user-manual_2341814035.webp)
1-26
Section 1 Specifications
Address
Name
Description
Attribute
%MD3.61546
High-speed counter CH0
current value
Stores the current value of the high-speed counter.
* Updated at the end of the scan or at the execution of the high-
speed counter current value direct read instruction (R_READ)
or high-speed counter current/set value write instruction
(W_HSC).
R
|
|
%MD3.61560
High-speed counter CH7
current value
%MD3.61562
High-speed counter CH0
set value
Stores the set value of the high-speed counter.
* Updated at the execution of the high-speed counter current/set
value write instruction (W_HSC).
R
|
|
%MD3.61576
High-speed counter CH7
set value
3) High-speed counter direction signal %MW3.61536
4) High-speed counter current value register / set value register %MD3.61546 to %MD3.61576
Address
Name
Description
Attribute
%MX3.61536.0
High-speed counter CH0
direction signal (by software)
Sets the direction signal (by software) of the high-speed counter.
OFF: Forward, OFF: Reverse
* This setting is reflected at the end of the scan or at the execution
of the high-speed counter flag control instruction
(W_HSC_FLG).
R/W
|
|
%MX3.61536.7
High-speed counter CH7
direction signal (by software)
%MX3.61536.8
|
%MX3.61536.15
Not used